Type
- Accessory
- Residual current relays
- Voltage release
Special features
- Adjustable fault current and delay time
- Fault current early warning by flashing, red LED
- Pulse-current sensitive
- Integrated auxiliary contact (1 C/O)
- Ring-type transformer must also be ordered
- not UL/CSA approved
Features
Sealable, setting buttons
1 integrated changeover contact (relay contact)
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Mounting Method
Snap fixing, top-hat rail DIN 46277, IEC/EN 60715
Ambient operating temperature - max
Ambient operating temperature - min
Current rating of relay contact
Power on-delay time - max
Power on-delay time - min
Rated control supply voltage (Us) at AC, 50 Hz - max
Rated control supply voltage (Us) at AC, 50 Hz - min
Rated control supply voltage (Us) at AC, 60 Hz - max
Rated control supply voltage (Us) at AC, 60 Hz - min
Rated control supply voltage (Us) at DC - max
Terminal protection
Finger/back-of-hand proof to BGV A2, VDE 106 part 100
Terminals (top and bottom)
Voltage rating of relay contact
Delay time
0.02, 0.1, 0.3, 0.5, 1, 3, 5 ms
Terminal capacity (solid/flexible conductor)
0.75 mm² - 1.5 mm² (2x) with ferrules
0.75 mm² - 2.5 mm² (2x) solid, 0.75 mm² - 1.5 mm² (2x) flexible/with ferrules
Rated control supply voltage (Us) at DC - min
Rated fault current - max
Rated fault current - min
Rated operating voltage (Ue) - max
Sensitivity type
Pulse current sensitive, type A