SIPLUS ET 200SP CM PTP -40...+60 °C Start up -25 °C With conformal coating Based on 6ES7137-6AA00-0BA0 . CM PTP communication module For serial connection RS-422, RS-485 and RS-232, Freeport, 3964 (R), USS, Modbus RTU master, slave, 115200 Kbps

SIPLUS ET 200SP -40 ... +60 ° C temp. boot: -25 ° C with coating formed based on 6ES7137-6AA00-0BA0 . CM PTP CM PTP communication module for serial connection RS422, RS485 and RS232, FREEPORT, 3964(R), USS, MODBUS RTU MASTER, SLAVE, 115200 KBIT/S

More details


AUTOMATION SYSTEMS > SIPLUS Extreme (LOGO, S7-1200, S7-1500, etc)

Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



ETIM: EC001604 - Fieldbus, decentr. periphery - communication module

Value Unit
Appendant operation agent (Ex ia) (EF004141) -
Explosion safety category for gas (EF003997) -
Supporting protocol for Foundation Fieldbus (EF007522) -
Suitable for safety functions (EF001597) -
Supporting protocol for DeviceNet (EF003059) -
Appendant operation agent (Ex ib) (EF004142) -
Radio standard WLAN 802.11 (EF007179) -
Fieldbus connection over separate bus coupler possible (EF004002) -
Explosion safety category for dust (EF003998) -
Supply voltage AC 50 Hz (EF007532) ['-', '-']V
Supply voltage AC 60 Hz (EF007533) ['-', '-']V
Supply voltage DC (EF007534) ['19.2', '28.8']V
Voltage type of supply voltage (EF002991) DC
Supporting protocol for TCP/IP (EF003050) NO DATA
Supporting protocol for PROFIBUS (EF003052) false
Supporting protocol for CAN (EF003053) false
Supporting protocol for INTERBUS (EF003054) false
Supporting protocol for ASI (EF003051) false
Supporting protocol for KNX (EF003055) false
Supporting protocol for Modbus (EF003057) true
Supporting protocol for Data-Highway (EF003058) false
Supporting protocol for SUCONET (EF003060) false
Supporting protocol for LON (EF003017) false
Supporting protocol for SERCOS (EF006657) false
Supporting protocol for PROFINET IO (EF007525) false
Supporting protocol for PROFINET CBA (EF007524) false
Supporting protocol for EtherNet/IP (EF007521) false
Supporting protocol for AS-Interface Safety at Work (EF007519) false
Supporting protocol for DeviceNet Safety (EF007520) false
Supporting protocol for INTERBUS-Safety (EF006662) false
Supporting protocol for PROFIsafe (EF007526) false
Supporting protocol for SafetyBUS p (EF007527) false
Supporting protocol for other bus systems (EF003062) true
Radio standard Bluetooth (EF007178) false
Radio standard GPRS (EF008523) false
Radio standard GSM (EF008524) false
Radio standard UMTS (EF008525) false
IO link master (EF007298) false
System accessory (EF004118) true
Degree of protection (IP) (EF005474) IP20
With potential separation (EF003272) true
Rail mounting possible (EF003972) true
Wall mounting/direct mounting (EF007020) false
Front build in possible (EF007016) true
Rack-assembly possible (EF007018) true
Category according to EN 954-1 (EF006782) -
SIL according to IEC 61508 (EF009889) -
Performance level according to EN ISO 13849-1 (EF007399) -
Width (EF000008) 15.0mm
Height (EF000040) 73.0mm
Depth (EF000049) 58.0mm


SIPLUS ET 200SP CM PTP -40...+60 °C Start up -25 °C With conformal coating Based on 6ES7137-6AA00-0BA0 . CM PTP communication module For serial connection RS-422, RS-485 and RS-232, Freeport, 3964 (R), USS, Modbus RTU master, slave, 115200 Kbps
General information
Product type designationCM PtP
Firmware version
● FW update possibleYes
usable BaseUnitsBU type A0
Product function
● I&M dataYes; I&M0 to I&M3
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Input current
Current consumption (rated value)29 mA
Power loss
Power loss, typ.0.7 W
Address area
Address space per module
● Inputs8 byte
1. Interface
Interface types
● RS 485Yes
● RS 422Yes
● RS 232Yes
Interface types
RS 232
● Transmission rate, max.115.2 kbit/s
● Cable length, max.15 m
● RS 232 auxiliary signalsRTS, CTS, DTR, DSR, RI, DCD
RS 485
● Transmission rate, max.115.2 kbit/s
● Cable length, max.1 200 m
RS 422
● Transmission rate, max.115.2 kbit/s
● Cable length, max.1 200 m
● 4-wire full duplex connectionYes
● 4-wire multipoint connectionYes
Protocols
Integrated protocols
Freeport
— Telegram length, max.2 kbyte
— Bits per character7 or 8
— Number of stop bits1 or 2 bit
— ParityNone, even, odd, always 1, always 0, any
3964 (R)
— Telegram length, max.2 kbyte
— Bits per character7 or 8
— Number of stop bits1 or 2 bit
— ParityNone, even, odd, always 1, always 0, any
Modbus RTU master
— Address area1 to 247, extended 1 to 65535
— Number of slaves, max.32
MODBUS RTU slave
— Address area1 to 247, extended 1 to 65535
Telegram buffer
● Buffer memory for telegrams4 kbyte
● Number of telegrams which can be buffered255
Interrupts/diagnostics/status information
Diagnostics functionYes
Alarms
● Diagnostic alarmYes
● Hardware interruptNo
Diagnoses
● Wire-breakYes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
● for module diagnosticsYes; green/red DIAG LED
● Receive RxDYes; green LED
● Transmit TxDYes; green LED
Potential separation
between backplane bus and interfaceYes
Isolation
Isolation tested with707 V DC (type test)
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.-40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C
● horizontal installation, max.60 °C; = Tmax
Altitude during operation relating to sea level
● Installation altitude above sea level, max.5 000 m
● Ambient air temperature-barometric pressure-altitudeTmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068-2-38, max.100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Resistance
Coolants and lubricants
— Resistant to commercially available coolants and lubricantsYes; Incl. diesel and oil droplets in the air
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-3Yes; Class 3S4 incl. sand, dust, *
— Against mechanical environmental conditions acc. to EN 60721-3-3Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Use on ships/at sea
— to biologically active substances according to EN 60721-3-6Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request
— to chemically active substances according to EN 60721-3-6Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); *
— to mechanically active substances according to EN 60721-3-6Yes; Class 6S3 incl. sand, dust; *
— Against mechanical environmental conditions acc. to EN 60721-3-6Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0)
Usage in industrial process technology
— Against chemically active substances acc. to EN 60654-4Yes; Class 3 (excluding trichlorethylene)
— Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil)
Remark
— Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04* The supplied plug covers must remain in place over the unused interfaces during operation!
Conformal coating
● Coatings for printed circuit board assemblies acc. to EN 61086Yes; Class 2 for high reliability
● Protection against fouling acc. to EN 60664-3Yes; Type 1 protection
● Military testing according to MIL-I-46058C, Amendment 7Yes; Discoloration of coating possible during service life
● Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830AYes; Conformal coating, Class A
Decentralized operation
to SIMATIC S7-300Yes
to SIMATIC S7-400Yes
to SIMATIC S7-1200Yes
to SIMATIC S7-1500Yes
to standard PROFINET controllerYes
Dimensions
Width15 mm
Height73 mm
Depth58 mm
Weights
Weight, approx.30 g
last modified:08/19/2020


Product
Article Number (Market Facing Number)6AG1137-6AA00-2BA0
Product DescriptionSIPLUS ET 200SP CM PTP -40...+60 °C Start up -25 °C With conformal coating Based on 6ES7137-6AA00-0BA0 . CM PTP communication module For serial connection RS-422, RS-485 and RS-232, Freeport, 3964 (R), USS, Modbus RTU master, slave, 115200 Kbps
Product familySIPLUS CM PtP serial interface
Product Lifecycle (PLM)PM300:Active Product
Price data
Price Group473
Surcharge for Raw MaterialsNone
Metal FactorNone
Delivery information
Export Control RegulationsAL : N / ECCN : N
Standard lead time ex-works42 Day/Days
Net Weight (kg)0,040 Kg
Product Dimensions (W x L x H)Not available
Packaging Dimension6,40 x 7,80 x 2,30
Package size unit of measureCM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4047618068912
UPC804766242403
Commodity Code85176200
LKZ_FDB/ CatalogIDA&DSE/SIP ADD
Product Group4257
Group CodeR740
Country of originGermany
Compliance with the substance restrictions according to RoHS directiveSince: 25.02.2013
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

4,4'-isopropylidenediphenol (Bisphenol A, BPA)

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Classifications
VersionClassification
eClass627-24-26-08
eClass7.127-24-26-08
eClass827-24-26-08
eClass927-24-26-08
eClass9.127-24-26-08
ETIM5EC001604
ETIM6EC001604
ETIM7EC001604
IDEA43564
UNSPSC1532-15-17-05

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.