Product successfully added to your shopping cart
TAE-TRAB FM-NFN-AP
2749628
PHOENIX_CONTACT
1
Surge protection device
Spray-protected TAE (NFN) connection box with surge protection for analogue and digital telecommunication interfaces (VDSL up to 50 MBit/s, short distances (< 300 m) up to 100 MBit/s)
Earthing, lightning and surge protection > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Orderkey | 2749628 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 165 (C-4-2017) |
| GTIN | 4017918108199 |
| Weight per Piece (excluding packing) | 79.600 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
| Housing material | ABS |
|---|---|
| Color | cream white |
| Standards for cearances and creepage distances | VDE 0110-1 |
| IEC 60664-1 | |
| For country-specific use in | D |
| Mounting type | Surface/Wall mounting |
| Type | Socket for surface mounting |
| Direction of action | Line-Line & Line-Earth Ground |
| IEC test classification | B2 |
|---|---|
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| VDE requirement class | B2 |
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 60 V DC |
| Maximum continuous voltage UC | 185 V DC |
| Rated current | 450 mA (≤ 40°C) |
| Operating effective current ICat UC | ≤ 10 µA |
| Residual current IPE | ≤ 6 µA |
| Nominal discharge current In(8/20) µs (line-line) | 5 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Total discharge current Itotal(10/350) µs | 5 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 5 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 5 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 100 A |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A |
| Nominal pulse current Ian (10/700) µs (line-line) | 150 A |
| Nominal pulse current Ian (10/700) µs (line-earth) | 150 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 250 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 450 V |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 250 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 450 V |
| Voltage protection level Up(line-line) | ≤ 250 V (C2 - 10 kV / 5 kA) |
| ≤ 250 V (C1 - 1 kV/500 A) | |
| ≤ 250 V (B2 - 4 kV / 100 A) | |
| Voltage protection level Up(line-earth) | ≤ 500 V (C2 - 10 kV / 5 kA) |
| ≤ 450 V (C1 - 1 kV/500 A) | |
| ≤ 400 V (B2 - 4 kV / 100 A) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | 0.3 dB (≤ 1 MHz / 150 Ω) |
| 0.3 dB (≤ 400 kHz / 600 Ω) | |
| Input attenuation aE, asym. | 0.3 dB (≤ 400 kHz / 600 Ω) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 8 MHz |
| Cut-off frequency fg (3 dB), sym. in 600 Ohm system | typ. 2 MHz |
| Capacity (line-line) | typ. 200 pF (f = 1 MHz / VR = 0 V) |
| Capacity (line-earth) | typ. 15 pF (f = 1 MHz / VR = 0 V) |
| Resistance in series | 2.2 Ω 10 % |
| Short-circuit current self-quenching | 150 mA |
| Surge protection fault message | none |
| Impulse durability (line-line) | C2 - 10 kV/5 kA |
| C1 - 1 kV/500 A | |
| B2 - 4 kV/100 A | |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| C1 - 1 kV/500 A | |
| B2 - 4 kV/100 A | |
| D1 - 2.5 kA | |
| Alternating current carrying capacity (line-earth) | 5 A - 1 s |
| Connection method | Screw connection & TAE 6 |
|---|---|
| Connection method IN | Screw terminal blocks |
| Connection method OUT | 3x TAE-NFN |
| Connection technology | Screw connection |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 6 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 26 ... 16 |
| Connection method | Screw terminal block |
|---|---|
| Stripping length | 6 mm |
| Tightening torque, min | 0.5 Nm |
| Conductor cross section flexible min. | 0.14 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section solid min. | 0.14 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 16 |
| Standards/regulations | IEC 61643-21 |
|---|---|
| Standards/specifications | DIN EN 61643-21 2002 |
| IEC 61643-21 2000 |
| Feature Name | Feature Value |
|---|---|
| Nominal voltage AC (EF008798) | 60 V |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOG PHOENIX PROTECTION EN .pdf | 27 Mbytes |
|
| PHOENIX CONTACT-2749628-TAE-TRAB FM-NFN-AP | 116 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.