Product successfully added to your shopping cart
CF-UB-280DC-SB-SET
2839541
PHOENIX_CONTACT
1
Surge protection device
Attachment plug with replaceable surge protection for coaxial signal interfaces. Connection: N connector, male-female, with adapter N connector to F connector.
Home > PHOENIX CONTACT
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Product type | Surge protection for transceiver systems |
| IEC test classification | C2 |
| C3 | |
| D1 | |
| VDE requirement class | C2 |
| C3 | |
| D1 | |
| Type | Attachment plug |
| Surge protection fault message | none |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Connection method | F connector |
| Width | 25 mm |
| Height | 25 mm |
| Depth | 72 mm |
| Seal material | Silicon |
| Housing material | Nickel-plated brass |
| Housing surface material | Ni |
| Contact surface material | Au |
| Inner conductor material | CuZn |
| Inner conductor surface material | Gold |
| Insulation body material | PTFE |
| Spring contact material | CuSn |
| Mechanical data | |
| Open side panel | No |
| Direction of action | Line-Shield/Earth Ground |
| Maximum continuous voltage UC | 280 V DC |
| 195 V AC | |
| Maximum continuous voltage UC(line-earth) | 280 V DC |
| 195 V AC | |
| Operating effective current ICat UC | ≤ 1 µA |
| Nominal discharge current In(8/20) µs (line-ground) | 20 kA |
| Nominal discharge current In(8/20) µs (line-shield) | 20 kA |
| Total surge current (8/20) µs | 20 kA |
| Total surge current (10/350) µs | 2.5 kA |
| Max. discharge current Imax(8/20) µs maximum (line-shield) | 20 kA |
| Nominal pulse current Ian (10/1000) µs (line-shield) | 100 A |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 900 V |
| Output voltage limitation at 1 kV/µs (line-shield) spike | ≤ 900 V |
| Voltage protection level Up(line-earth) | ≤ 1.1 kV (C2 - 10 kV / 5 kA) |
| ≤ 900 V (C1 - 1 kV / 500 A) | |
| ≤ 1 kV (C3 - 25 A) | |
| Voltage protection level Up(line-shield) | ≤ 1.1 kV (C2 - 10 kV / 5 kA) |
| 900 V (C1 - 1 kV / 500 A) | |
| ≤ 1 kV (C3 - 25 A) | |
| Response time tA(line-earth) | ≤ 100 ns |
| Response time tA (line-shield) | ≤ 100 ns |
| Cut-off frequency fg (3 dB), asym. (shield) in 50 Ω system | > 2 GHz |
| Permissible HF power Pmaxat VSWR = xx (50 ohm system) | 700 W (VSWR = 1.1) |
| 200 W (VSWR = ∞) | |
| Capacity (Core-Earth) | typ. 1.5 pF |
| Capacity asymmetrical (shield) | typ. 1.5 pF |
| Surge protection fault message | none |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 2.5 kA |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -20 °C ... 80 °C |
| Altitude | 2000 m |
| VDE requirement class | C2 |
| C3 | |
| D1 | |
| Air clearances and creepage distances | |
| Standards/regulations | IEC 60664-1 |
| Standards Information technology specification | |
| Standards/regulations | IEC 61643-21 |
| IEC 61643-21 | |
| Standards/specifications | IEC 61643-21/A1 |
| Note | 2008 |
| Standards/specifications | EN 61643-21/A1 |
| Note | 2009 |
| Mounting type | Connection-specific intermediate plugging |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.