Dimensions (W x H x D)
71.5 x 90 x 58 (4 PE) mm
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Solid
0.2/4 (AWG 22 - 12) mm2
Flexible with ferrule
0.2/2.5 (AWG 22 - 12) mm2
Standard screwdriver
0.8 x 3.5 mm
Max. tightening torque
0.6 Nm
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
Ambient conditions, mechanical
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
II/2
Electrostatic discharge (ESD)applied standard
IEC/EN 61000-4-2, Level 3
Electrostatic discharge (ESD)Air discharge
8 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
10 V/m
Burst
according to IEC/EN 61000-4-4 kV
power pulses (Surge)
2 kV (supply cables, symmetrical, EASY...AC)
0.5 kV (supply cables, symmetrical, easy-DC)
according to IEC/EN 61000-4-5
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Clearance in air and creepage distances
EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
EN 50178
Rated operational voltage [Ue]
24 DC (-15/+20%) V
Permissible range [Ue]
20.4 - 28.8 V DC
Input current
150 mA at Ueat no load
Voltage dips
≤ 20
(IEC/EN 61131-2) ms
Heat dissipation [P]
Normally 3.5 W
CANopen®Data transfer rate
500 kBit/s, 25 m250 kBit/s, 40m125 kBit/s, 125 m50 kBit/s, 300 m20 kBit/s, 700 m10 kBit/s, 1000 m
CANopen®Bus termination (first and last station)
Via integrated Dip switch
CANopen®Connection types
2 x terminals (see terminal capacity)
Mode slaveStations
max. 62 Number
Mode slavePDO type
Asynchronous, cyclic, acyclic
Mode slaveControl contact rated current
to DS301V4
Potential isolation
from the outputs: yes
Rated operational voltage [Ue]
24 V DC
Input voltage
< 5 (R1 - R6) at signal "0"
> 15 (R1 - R6) at signal "1" V DC
Input current on 1 signalInput current at signal 1
3.3 (R1 to R6 (R12)) mA
Deceleration time
20 (from “0” to “1”, debounce ON)
Normally 0.25 (R1 - R12) (from “0” to “1”, debounce OFF)
20 (from „1“ to „0“) ms
Cable length
100 (unshielded) m
Rated operational voltage [Ue]
24 V DC
Permissible range [Ue]
20.4 - 28.8 V DC
Supply current
Norm./max. 9/16 at signal 0
12/22 at signal 1 mA
Protection against polarity reversal
yes (Caution: A short circuit will result if 0 V or earth is applied to the outputs in the event that the supply voltage is connected to the wrong poles.)
Potential isolation
from power supply, inputs
to the memory card: yes
Rated operational current at signal „1” DC per channel [Ie]
Max. 0.5 A
Lamp load without Rvper channel
5 W
Residual current on 0 signal per channel
< 0.1 mA
Max. output voltage
2.5 (signal 0 at external load < 10 MΩ)
U = Ue- 1 V (signal 1 at Ie= 0.5 A) V
Short-circuit protection
Yes, thermal (analysis via diagnostics input I16, I15; R15, R16)
Short-circuit tripping current for Ra≦ 10 mΩ
0.7 ≦ Ie≦ 2 per output A
Total short-circuit current
8 A
Peak short-circuit current
16 A
Max. operating frequency with constant resistive load
40000 Operations/h
Parallel connection of outputsWith resistive load, inductive load with external suppressor circuit, combination within a group
Group 1: Q1 to Q4
Parallel connection of outputsNumber of outputs [max.]
4
Parallel connection of outputsMax. total current
2 (Caution! Outputs must be actuated simultaneously and for the same length of time.) A
Protection against polarity reversal
yes (Caution: A short circuit will result if 0 V or earth is applied to the outputs in the event that the supply voltage is connected to the wrong poles.)
Bus termination (first and last station)
Via integrated Dip switch