6ES7550-1AA00-0AB0 SIEMENS SIMATIC S7-1500, TM count 2x24V Counter module, 2 channels for 24 V incremental o.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

6ES7550-1AA00-0AB0 SIEMENS SIMATIC S7-1500, TM count 2x24V Counter module, 2 channels for 24 V incremental o..

6ES7550-1AA00-0AB0

SIEMENS

SIMATIC S7-1500, TM count 2x24V Counter module, 2 channels for 24 V incremental or encoder 3 DI, 2 DQ per channel

More details


AUTOMATION SYSTEMS > SIMATIC S7-1500: I / O

Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



ETIM: EC001422 - PLC function/technology module

Value Unit
Suitable for pressure control (EF003252) -
Suitable for NC (EF003253) -
Single-axis positioning possible (EF003268) -
Suitable for cam controller (EF003263) -
Single-axis controller possible (EF003266) -
Suitable for path controller (EF003262) -
Suitable for weighing (EF003249) -
Suitable for temperature control (EF008344) -
Suitable for CNC (EF003256) -
Suitable for flying saw (EF003264) -
Suitable for flux controller (EF003260) -
Suitable for multi-axis positioning (EF003267) -
Number of functions (EF003244) -
Redundancy (EF003156) false
Suitable for counting (EF003248) true
Suitable for welding control (EF003251) false
Suitable for electronic positioning (EF003255) true
Suitable for SSI (EF003254) false
Suitable for incremental data detection (EF003258) true
Suitable for detection absolute value (EF003259) -
Suitable for flux measurement (EF003261) false
Suitable for multi-axis control (EF003265) false
Suitable for safety functions (EF001597) false
Category according to EN 954-1 (EF006782) -
SIL according to IEC 61508 (EF009889) -
Performance level according to EN ISO 13849-1 (EF007399) -
Appendant operation agent (Ex ia) (EF004141) false
Appendant operation agent (Ex ib) (EF004142) false
Explosion safety category for gas (EF003997) ATEX gas-ex-protection, Cat. 3G
Explosion safety category for dust (EF003998) None
Width (EF000008) 35.0mm
Height (EF000040) 147.0mm
Depth (EF000049) 129.0mm


SIMATIC S7-1500, TM count 2x24V Counter module, 2 channels for 24 V incremental or encoder 3 DI, 2 DQ per channel
General information
Product type designationTM Count 2x24V
Firmware versionV1.3
● FW update possibleYes
Product function
● I&M dataYes; I&M0 to I&M3
● Isochronous modeYes
Engineering with
● STEP 7 TIA Portal configurable/integrated from versionV12 (FW V1.0) ... V15 (FW V1.3)/V12 (FW V1.0), V13 (FW V1.1)
● PROFIBUS from GSD version/GSD revisionGSD Revision 5
● PROFINET from GSD version/GSD revisionV2.3 / -
Installation type/mounting
Rail mountingYes; S7-1500 mounting rail
Supply voltage
Load voltage L+
● Rated value (DC)24 V
● permissible range, lower limit (DC)19.2 V
● permissible range, upper limit (DC)28.8 V
● Reverse polarity protectionYes
Input current
Current consumption, max.75 mA; without load
Encoder supply
Number of outputs1; A common 24V encoder supply for both channels
24 V encoder supply
● 24 VYes; L+ (-0.8 V)
● Short-circuit protectionYes
● Output current, max.1 A; total current of all encoders/channels
Power
Power available from the backplane bus1.3 W
Power loss
Power loss, typ.4 W
Address area
Address space per module
● Inputs16 byte; Per channel
● Outputs12 byte; per channel; 4 bytes for Motion Control
Digital inputs
Number of digital inputs6; 3 per channel
Digital inputs, parameterizableYes
Input characteristic curve in accordance with IEC 61131, type 3Yes
Digital input functions, parameterizable
● Gate start/stopYes
● CaptureYes
● SynchronizationYes
● Freely usable digital inputYes
Input voltage
● Type of input voltageDC
● Rated value (DC)24 V
● for signal "0"-5 ... +5 V
● for signal "1"+11 to +30V
● permissible voltage at input, min.-30 V; -5 V continuous, -30 V brief reverse polarity protection
● permissible voltage at input, max.30 V
Input current
● for signal "1", typ.2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizableYes; none / 0.05 / 0.1 / 0.4 / 0.8 / 1.6 / 3.2 / 12.8 / 20 ms
— at "0" to "1", min.6 µs; for parameterization "none"
— at "1" to "0", min.6 µs; for parameterization "none"
for technological functions
— parameterizableYes
Cable length
● shielded, max.1 000 m
● unshielded, max.600 m
Digital outputs
Type of digital outputTransistor
Number of digital outputs4; 2 per channel
Digital outputs, parameterizableYes
Short-circuit protectionYes; electronic/thermal
● Response threshold, typ.1 A
Limitation of inductive shutdown voltage toL+ (-33 V)
Controlling a digital inputYes
Digital output functions, parameterizable
● Switching tripped by comparison valuesYes
● Freely usable digital outputYes
Switching capacity of the outputs
● with resistive load, max.0.5 A; Per digital output
● on lamp load, max.5 W
Load resistance range
● lower limit48 Ω
● upper limit12 kΩ
Output voltage
● Type of output voltageDC
● for signal "1", min.23.2 V; L+ (-0.8 V)
Output current
● for signal "1" rated value0.5 A; Per digital output
● for signal "1" permissible range, max.0.6 A; Per digital output
● for signal "1" minimum load current2 mA
● for signal "0" residual current, max.0.5 mA
Output delay with resistive load
● "0" to "1", max.50 µs
● "1" to "0", max.50 µs
Switching frequency
● with resistive load, max.10 kHz
● with inductive load, max.0.5 Hz; Acc. to IEC 60947-5-1, DC-13; observe derating curve
● on lamp load, max.10 Hz
Total current of the outputs
● Current per module, max.2 A
Cable length
● shielded, max.1 000 m
● unshielded, max.600 m
Encoder
Connectable encoders
● 2-wire sensorYes
— permissible quiescent current (2-wire sensor), max.1.5 mA
Encoder signals, incremental encoder (asymmetrical)
● Input voltage24 V
● Input frequency, max.200 kHz
● Counting frequency, max.800 kHz; with quadruple evaluation
● Cable length, shielded, max.600 m; depending on input frequency, encoder and cable quality; max. 50 m at 200 kHz
● Signal filter, parameterizableYes
● Incremental encoder with A/B tracks, 90° phase offsetYes
● Incremental encoder with A/B tracks, 90° phase offset and zero trackYes
● Pulse encoderYes
● Pulse encoder with directionYes
● Pulse encoder with one impulse signal per count directionYes
Encoder signal 24 V
— permissible voltage at input, min.-30 V
— permissible voltage at input, max.30 V
Interface types
● Source/sink inputYes
● Input characteristic curve in accordance with IEC 61131, type 3Yes
Isochronous mode
Filtering and processing time (TCI), min.130 µs
Bus cycle time (TDP), min.250 µs
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarmYes
● Hardware interruptYes
Diagnoses
● Monitoring the supply voltageYes
● Wire-breakYes
● Short-circuitYes
● A/B transition error at incremental encoderYes
Diagnostics indication LED
● RUN LEDYes; green LED
● ERROR LEDYes; red LED
● MAINT LEDYes; Yellow LED
● Monitoring of the supply voltage (PWR-LED)Yes; green LED
● Channel status displayYes; green LED
● for channel diagnosticsYes; red LED
● Status indicator forward counting (green)Yes
● Status indicator backward counting (green)Yes
Integrated Functions
Number of counters2
Counting frequency (counter) max.800 kHz; with quadruple evaluation
Counting functions
● Can be used with TO High_Speed_CounterYes
● Continuous countingYes
● Counter response parameterizableYes
● Hardware gate via digital inputYes
● Software gateYes
● Event-controlled stopYes
● Synchronization via digital inputYes
● Counting range, parameterizableYes
Comparator
— Number of comparators2; Per channel
— Direction dependencyYes
— Can be changed from user programYes
Position detection
● Incremental acquisitionYes
● Suitable for S7-1500 Motion ControlYes
Measuring functions
● Measuring time, parameterizableYes
● Dynamic measurement period adjustmentYes
● Number of thresholds, parameterizable2
Measuring range
— Frequency measurement, min.0.04 Hz
— Frequency measurement, max.800 kHz
— Cycle duration measurement, min.1.25 µs
— Cycle duration measurement, max.25 s
Accuracy
— Frequency measurement100 ppm; depending on measuring interval and signal evaluation
— Cycle duration measurement100 ppm; depending on measuring interval and signal evaluation
— Velocity measurement100 ppm; depending on measuring interval and signal evaluation
Potential separation
Potential separation channels
● between the channelsNo
● between the channels and backplane busYes
● Between the channels and load voltage L+No
Isolation
Isolation tested with707 V DC (type test)
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.0 °C
● horizontal installation, max.60 °C; Please note derating for inductive loads
● vertical installation, min.0 °C
● vertical installation, max.40 °C; Please note derating for inductive loads
Decentralized operation
to SIMATIC S7-300Yes
to SIMATIC S7-400Yes
to SIMATIC S7-1200Yes
to SIMATIC S7-1500Yes
to standard PROFIBUS masterYes; FW V1.1 and higher
to standard PROFINET controllerYes
Dimensions
Width35 mm
Height147 mm
Depth129 mm
Weights
Weight, approx.250 g
last modified:08/28/2020


Product
Article Number (Market Facing Number)6ES7550-1AA00-0AB0
Product DescriptionSIMATIC S7-1500, TM count 2x24V Counter module, 2 channels for 24 V incremental or encoder 3 DI, 2 DQ per channel
Product familyTM Count 2x24V counter module
Product Lifecycle (PLM)PM300:Active Product
Price data
Price Group219
Surcharge for Raw MaterialsNone
Metal FactorNone
Delivery information
Export Control RegulationsAL : N / ECCN : EAR99H
Standard lead time ex-works1 Day/Days
Net Weight (kg)0,384 Kg
Product Dimensions (W x L x H)Not available
Packaging Dimension16,40 x 19,10 x 4,10
Package size unit of measureCM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4025515080008
UPC887621138790
Commodity Code85389091
LKZ_FDB/ CatalogIDST73
Product Group4502
Group CodeR111
Country of originGermany
Compliance with the substance restrictions according to RoHS directiveSince: 25.02.2013
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Classifications
VersionClassification
eClass627-24-22-05
eClass7.127-24-22-05
eClass827-24-22-05
eClass927-24-22-05
eClass9.127-24-22-05
ETIM4EC001422
ETIM5EC001422
ETIM6EC001422
ETIM7EC001422
IDEA43567
UNSPSC1532-15-17-05

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.