QUINT-DC-UPS/24DC/10 2866226 PHOENIX CONTACT Uninterruptible power supply 24 V DC/10 A, with integrated 1.3 .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

QUINT-DC-UPS/24DC/10 2866226 PHOENIX CONTACT Uninterruptible power supply 24 V DC/10 A, with integrated 1.3 ..

QUINT-DC-UPS/24DC/10

2866226

PHOENIX_CONTACT

Available

Ship on today

Uninterruptible power supply 24 V DC/10 A, with integrated 1.3 Ah battery module. In the download area, there is a clearly arranged selection table available with load currents and buffer times, as well as charging times after buffer mode.

More details


Programmable Logic Controllers Plcs

INTERFACE Signal converters, switching devices, and power supply units - PHOENIX CONTACT

Power. Power Supply - PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
1+$429.12
2+$418.33
3+$418.28
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Width100 mm
Height130 mm
Depth125 mm

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)0 °C ... 50 °C
Ambient temperature (storage/transport)0 °C ... 40 °C
Max. permissible relative humidity (operation)95 % (at 25 °C, non-condensing)
Noise immunityEN 61000-6-2:2005

Input data

Nominal input voltage24 V DC
Input voltage range22.5 V DC ... 30 V DC
Current consumptionapprox. 0.1 A
0.5 A (charging process)
10.5 A (max.)
Current consumption (maximum)10.5 A (max.)
Current consumption (idle)approx. 0.1 A
Current consumption (charging process)0.5 A (charging process)
Buffer period1.5 min. (10 A)
20 min. (2 A)
Input fuse15 A (slow-blow, internal)

Output data

Nominal output voltage24 V DC (Normal operation: Uin- 0.5 V DC, buffer mode: 27.9 to 19.2 V DC)
Nominal output current (IN)10 A
Connection in parallelNo
Connection in seriesYes
Output power240 W

General

DisposalUsed batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations. They can also be returned to Phoenix Contact or the manufacturer.
Net weight1.8 kg
Memory mediumInternal, battery 1.3 Ah
Operating voltage displayGreen LED
Efficiency> 91 %
Insulation voltage input/output2 kV (routine test)
4 kV (type test)
Protection classII (in closed control cabinet)
MTBF (IEC 61709, SN 29500)> 500000 h
Mounting positionhorizontal DIN rail NS 35, EN 60715
Assembly instructionsCan be aligned: Horizontally 0 mm, vertically 50 mm

Connection data, input

Connection methodPluggable screw connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length7 mm
Screw threadM3

Connection data, output

Connection methodPluggable screw connection
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length7 mm
Screw threadM3

Signaling

Output descriptionPower OK
Status displayLED "Power OK" green
Note on status displayPower OK: LED permanently lit
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm
Screw threadM3
Output namefloating
Output descriptionAlarm
Maximum switching voltage≤ 30 V AC/DC
Continuous load current≤ 1 A
Status displayLED red
Note on status displayAlarm: LED permanently lit
Output namefloating
Output descriptionBattery Charge
Maximum switching voltage≤ 30 V AC/DC
Continuous load current≤ 1 A
Status displayLED yellow, flashing
Note on status displayBattery charge: LED flashing
Output namefloating
Output descriptionBattery Mode
Type of signalingLED, relay contact
Maximum switching voltage≤ 30 V AC/DC
Continuous load current≤ 1 A
Status displayYellow LED
Note on status displayBattery mode: LED permanently lit

Standards and Regulations

Electromagnetic compatibilityConformance with EMC Directive 2004/108/EC
Noise emissionEN 55011 (EN 55022)
Noise immunityEN 61000-6-2:2005
Connection in acc. with standardCUL
Standard – Electrical equipment of machinesEN 60204-1
Standard - Safety of transformersEN 61558-2-17
Standard - Electrical safetyEN 60950-1/VDE 0805 (SELV)
EN 61558-2-17
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installationsEN 50178/VDE 0160 (PELV)
Standard - Safe isolationDIN VDE 0100-410
Shipbuilding approvalGermanischer Lloyd (EMC 2), ABS, DNV
UL approvalsUL/C-UL listed UL 508
UL/C-UL Recognized UL 60950
UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D
Low Voltage DirectiveConformance with LV directive 2006/95/EC

[email protected]

[email protected] 4.027040603
[email protected] 4.127040603
[email protected] 5.027040603
[email protected] 5.127040603
[email protected] 6.027040603
[email protected] 7.027040603
[email protected] 8.027040603
[email protected] 9.027040705

ETIM

ETIM 2.0EC000382
ETIM 3.0EC000382
ETIM 4.0EC000382
ETIM 5.0EC000382

UNSPSC

UNSPSC 6.0130211510
UNSPSC 7.090139121011
UNSPSC 1139121011
UNSPSC 12.0139121011
UNSPSC 13.239121011

Datasheet - PDF

Title: Language: Size: Type:
PHOENIX CONTACT-2866226-QUINT-DC-UPS/24DC/10 English 135 Kbytes PHOENIX CONTACT-2866226-QUINT-DC-UPS/24DC/10

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.