QUINT-PS-3X400-500AC/24DC/20 2938727 PHOENIX CONTACT Power supply unit View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

QUINT-PS-3X400-500AC/24DC/20 2938727 PHOENIX CONTACT Power supply unit

QUINT-PS-3X400-500AC/24DC/20

2938727

PHOENIX_CONTACT

Power supply unit

Power supply for 24 V DC/20 A DIN rail, primary switched, three-phase
For new installations, use the following items: 2904622

DIN rail power supply unit 24 V DC/20 A, primary-switched, 3-phasePlease use the following item in new systems: 2904622

More details


Power Supplies (PS)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete.

Go to successor article: QUINT4-PS/3AC/24DC/20 2904622

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Technical data

Input data
AC operation
Nominal input voltage range3x 400 V AC ... 500 V AC
Input voltage range3x 320 V AC ... 575 V AC (for all three phases)
450 V DC ... 800 V DC
Input voltage range AC3x 320 V AC ... 575 V AC (for all three phases)
Input voltage range DC450 V DC ... 800 V DC
Voltage type of supply voltageAC/DC
Inrush current< 15 A (typical)
Inrush current integral (I2t)1 A2s
AC frequency range45 Hz ... 65 Hz
Frequency range DC0 Hz
Mains buffering time> 23 ms (400 V AC)
> 25 ms (480 V AC)
Current consumptionapprox. 3x 1.1 A (400 V AC)
3x 1 A (480 V AC)
Nominal power consumption526 W
Protective circuitTransient surge protection; Varistor
Typical response time< 1 s
Recommended breaker for input protection3x 6 A ... 16 A (Characteristics B, C, D, K)
Discharge current to PE< 3.5 mA

Output data
Efficiency> 91 % (at 400 V AC and nominal values)
Nominal output voltage24 V DC ±1 %
Setting range of the output voltage (USet)22.5 V ... 28.5 V
Nominal output current (IN)20 A (up to 60 °C)
POWER BOOST (IBoost)27 A
Derating60 °C (2.5 %/K)
Active current limitationApprox. IBOOST= 27 A (for short-circuit)
Control deviation< 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple< 10 mVPP(with nominal values)
Output power480 W
Peak switching voltages nominal load< 60 mVPP(20 MHz)
Maximum no-load power dissipation< 7 W
Power loss nominal load max.< 47 W
Rise time< 2 ms (UOUT(10 % ... 90 %))
Connection in parallelyes, for redundancy and increased capacity
Connection in seriesyes
Signal: DC OK active
Output descriptionUOUT> 0.9 x UN: High signal
Maximum switching voltage≤ 24 V
Output voltage+ 24 V DC (Signal)
Maximum inrush current≤ 40 mA
Continuous load current≤ 40 mA
Signal: DC OK floating
Output descriptionRelay contact, UOUT> 0.9 x UN: Contact closed
Maximum switching voltage≤ 30 V AC/DC
Maximum inrush current≤ 1 A
Continuous load current≤ 1 A

Connection data
Input
Connection methodScrew connection
Conductor cross section, rigid min.0.2 mm²
Conductor cross section, rigid max.6 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.4 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.10
Stripping length8 mm
Screw threadM3
Tightening torque, min0.5 Nm
Tightening torque max0.6 Nm
Output
Connection methodScrew connection
Conductor cross section, rigid min.0.5 mm²
Conductor cross section, rigid max.16 mm²
Conductor cross section flexible min.0.5 mm²
Conductor cross section flexible max.10 mm²
Conductor cross section AWG min.20
Conductor cross section AWG max.6
Stripping length10 mm
Screw threadM4
Tightening torque, min1.2 Nm
Tightening torque max1.5 Nm
Signal
Conductor cross section, rigid min.0.5 mm²
Conductor cross section, rigid max.16 mm²
Conductor cross section flexible min.0.5 mm²
Conductor cross section flexible max.10 mm²
Conductor cross section AWG min.20
Conductor cross section AWG max.6
Screw threadM4
Tightening torque, min1.2 Nm
Tightening torque max1.5 Nm

Signaling
Types of signalingLED
Active switching output
Relay contact
Operating voltage displayGreen LED
Signal output: DC OK active
Status display"DC OK" LED green
Note on status displayUOUT< 0.9 x UN: LED flashing
Signal output: DC OK floating
Status display"DC OK" LED green

Electrical properties
Number of phases3.00
Insulation voltage input/output4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE500 V DC (routine test)
Insulation voltage input / PE3.5 kV AC (type test)
2 kV AC (routine test)

Product properties
Product typePower supply
Product familyQUINT POWER
MTBF (IEC 61709, SN 29500)> 500000 h
Data management status
Article revision12
Insulation characteristics
Protection classI (with PE connection)
Degree of pollution2

Dimensions
Width160 mm
Height130 mm
Depth125 mm
Installation dimensions
Installation distance right/left0 mm / 0 mm
Installation distance top/bottom50 mm / 50 mm
Alternative assembly
Width122 mm
Height130 mm
Depth163 mm

Mounting
Assembly notealignable: horizontally 0 mm, vertically 50 mm
Mounting positionhorizontal DIN rail NS 35, EN 60715

Material specifications
Housing materialMetal
Type of housingAluNox (AlMg1)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Climatic class3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation)95 % (at 25 °C, non-condensing)
Shock18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.

Standards and regulations
Standard – Limitation of mains harmonic currentsEN 61000-3-2
Standard - Electrical safetyEN 62368-1
Standard - Equipment safetyGS (tested safety)
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipmentEN 62368-1
Standard – Safety extra-low voltageEN 62368-1 (SELV)
EN 60204 (PELV)
Standard - Safe isolationDIN VDE 0100-410
Overvoltage category
EN 62477-1III

Approvals
Shipbuilding approvalDNV GL (EMC A)
UL approvalsUL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D

EMC data
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Low Voltage DirectiveConformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emissionEN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunityEN 61000-6-1
EN 61000-6-2
Noise emissionEN 55011 (EN 55022)
Electrostatic discharge
Standards/regulationsEN 61000-4-2
HousingLevel 4
Electrostatic discharge
Contact discharge8 kV
Discharge in air15 kV
CommentsCriterion B
Electromagnetic HF field
Standards/regulationsEN 61000-4-3
Electromagnetic HF field
Frequency range80 MHz ... 2 GHz
Test field strength10 V/m
CommentsCriterion A
Fast transients (burst)
Standards/regulationsEN 61000-4-4
Fast transients (burst)
Input4 kV (level 4 - asymmetrical)
Output2 kV (Level 3 - asymmetrical)
Signal1 kV (Level 2 - asymmetrical)
CommentsCriterion B
Surge voltage load (surge)
Standards/regulationsEN 61000-4-5
Surge voltage load (surge)
Input4 kV (inst. class 4 - asymmetrical: conductor to ground)
2 kV (inst. class 4 -symmetrical: conductor to conductor)
Output0.5 kV (level 1 - asymmetrical: conductor to ground)
0.5 kV (level 1 - symmetrical: conductor to conductor)
Signal1 kV (level 2 - asymmetrical: conductor to ground)
CommentsCriterion B
Conducted interference
Standards/regulationsEN 61000-4-6
Conducted interference
I/O/SLevel 3 - asymmetrical
Frequency range0.15 MHz ... 80 MHz
CommentsCriterion A
Voltage10 V
Voltage dips
Standards/regulationsEN 61000-4-11
Emitted interference
Standards/regulationsEN 61000-6-3
Radio interference voltage in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011EN 55011 (EN 55022) Class B, area of application: Industry and residential

Datasheet - PDF

Title: Size: Type:
PDF CATALOG PHOENIX PROTECTION EN .pdf 27 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.