PV-SET 1000 DC 2804445 PHOENIX CONTACT Surge protection in IP65 housing for single string photovoltaic syste.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PV-SET 1000 DC 2804445 PHOENIX CONTACT Surge protection in IP65 housing for single string photovoltaic syste..

PV-SET 1000 DC

2804445

PHOENIX_CONTACT

Available

Ship on today

Surge protection in IP65 housing for single string photovoltaic systems up to 1000 V DC, connection via SUNCLIX male/female connector.

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection - PHOENIX CONTACT

* Brand new produt in its original packing covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article is obsolete. Please ask us for a quotation and we will check if there are units available or we will offer you an alternative product.

Related products

More info



Dimensions

Height200 mm
Width125 mm
Depth122 mm
Horizontal pitch5 Div.

Ambient conditions

Degree of protectionIP65
IP65
Impact strengthIK08
Ambient conditionsA, B
Ambient temperature (operation)-30 °C ... 55 °C

General

Housing materialPolycarbonate, glass-fiber-reinforced
Cover materialPolycarbonate, transparent
Connector materialPA
Flammability rating according to UL 94V2 (Gehäuse / Deckel)
V0 (Steckverbinder)
Colorlight grey RAL 7035
Standards for cearances and creepage distancesEN 50539-11
Protection classII
Mounting typeSurface/Wall mounting
TypeInstallation housing
Number of positions2
Surge protection fault messageoptical
Direction of action(L+)-PE & (L-)-PE & (L+)-(L-)

PV protective circuit DC side

Open circuit voltage UOCSTC830 V DC (Solar generator)
Rated surge voltage resistance Uimp6 kV
Rated insulation voltage Ui1000 V DC
Short-circuit current ISCSTC25 A DC

Protective circuit

IEC test classificationPV T2
Maximum continuous operating voltage UC1000 V DC
Rated load current IL≤ 80 A DC
Residual current IPE≤ 20 µA
≤ 250 µA AC
Standby power consumption PC≤ 20 mW
Insulation resistance Riso> 5 GΩ (at 500 V DC)
Voltage protection level Up (L+) - (L-)≤ 3.7 kV
Max. backup fuse with branch wiringNot required
Recommended backup fuse maximumNot required

Connection, protective circuit

Connection namePE
Connection methodScrew terminal blocks
Biconnect terminal block
Screw threadM5
Tightening torque4.5 Nm
4.5 Nm ... 30 lbf-in. (UL)
Stripping length16 mm
Cable glandM20
Sealing area5 mm ... 13 mm
Cable glandM25
Sealing area3x 5 mm ... 7 mm

Remote indicator contact

Switching functionPDT, 1-pos.
Connection methodMC 1,5/3
Screw threadM2
Tightening torque0.25 Nm
2 lbf-in. ... 4 lbf-in.
Stripping length7 mm
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section solid min.0.14 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section AWG min.30
Conductor cross section AWG max.16

Standards and Regulations

Standards/regulationsIEC 61439-2 2011
EN 61439-2 2011
EN 50539-11 Surge protection

Datasheet - PDF

Title:Language:Size:Type:
PHOENIX CONTACT-2804445-PV-SET 1000 DCEnglish119 KbytesPHOENIX CONTACT-2804445-PV-SET 1000 DC

Reviews (0)