VAL-MS-T1/T2 175/12.5/1+1-FM 2800674 PHOENIX CONTACT Universal varistor-based plug-in lightning/surge arrest.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-MS-T1/T2 175/12.5/1+1-FM 2800674 PHOENIX CONTACT Universal varistor-based plug-in lightning/surge arrest..

VAL-MS-T1/T2 175/12.5/1+1-FM

2800674

PHOENIX_CONTACT

Universal varistor-based plug-in lightning/surge arrester for 1-phase power supply networks with separate N and PE (3-conductor system: L1, N, PE), with remote indication contact.

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Dimensions

Height99 mm
Width35.6 mm
Depth77.5 mm
Horizontal pitch2 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g
Vibration (operation)7.5g

General

IEC power supply systemTT
TN-C
TN-S
Housing materialPA 6.6
PBT
Flammability rating according to UL 94V-0
Colorblack
Standards for cearances and creepage distancesDIN EN 60664-1
EN 61643-11
Mounting typeDIN rail: 35 mm
TypeDIN rail module, two-section, divisible
Surge protection fault messageOptical, remote indicator contact
Direction of action1L-N & N-PE

Protective circuit

IEC test classificationI / II
T1 / T2
T1
I
EN typeT1 / T2
T1
Nominal voltage UN120 V AC (TN-S)
Maximum continuous operating voltage UC(L-N)175 V AC
Maximum continuous operating voltage UC(N-PE)264 V AC
UT(TOV-proof)208 V AC (5 s / L-N)
1200 V AC (200 ms / N-PE)
Nominal frequency fN50 Hz (60 Hz)
Rated load current IL80 A
Residual current IPE≤ 5 µA
Standby power consumption PC≤ 140 mVA
Max. discharge current Imax(8/20) µs maximum (L-N)50 kA
Max. discharge current Imax(8/20) µs maximum (N-PE)50 kA
Nominal discharge current In(8/20) µs (L-N)12.5 kA
Nominal discharge current In(8/20) µs (N-PE)50 kA
Impulse discharge current (10/350) µs (L-N), charge6.25 As
Impulse discharge current (10/350)˽µs, specific energy39 kJ/Ω
Impulse discharge current (10/350) µs (L-N), peak current value Iimp12.5 kA
Impulse discharge current (10/350) µs (N-PE), charge25 As
Impulse discharge current (10/350) µs (N-PE), specific energy625 kJ/Ω
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp50 kA
Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE)≤ 1.7 kV
Voltage protection level Up(L-N)≤ 0.8 kV
Voltage protection level Up(L-PE)≤ 2 kV
Voltage protection level Up(N-PE)≤ 1.7 kV
Residual voltage (L-N)≤ 0.65 kV (at 10 kA)
≤ 0.6 kV (at 5 kA)
≤ 0.5 kV (at 3 kA)
≤ 0.8 kV
Residual voltage (L-PE)≤ 1.5 kV (at 10 kA)
≤ 1.4 kV (at 5 kA)
≤ 1.3 kV (at 3 kA)
≤ 2 kV
Residual voltage (N-PE)≤ 0.5 kV (at 10 kA)
≤ 0.5 kV (at 5 kA)
≤ 0.4 kV (at 3 kA)
≤ 0.6 kV
Response time tA(L-N)≤ 25 ns
Response time (L-PE)≤ 100 ns
Response time tA(N-PE)≤ 100 ns
Max. backup fuse with branch wiring160 A AC (gG)
Max. backup fuse with V-type through wiring80 A AC (gG - 16 mm²)
Short-circuit resistance IPwith max. backup fuse (effective)25 kArms
Short-circuit current rating ISCCR25 kA
Follow current quenching capacity Ifi(N-PE)100 A (264 V AC)

Connection, protective circuit

Connection methodScrew connection
Connection type INBiconnect screw terminal block
Connection type OUTBiconnect screw terminal block
Connection methodBiconnect terminal block
Screw threadM5
Tightening torque4.5 Nm
30 lbf-in. (UL)
Stripping length16 mm
Conductor cross section flexible min.1.5 mm²
Conductor cross section flexible max.25 mm²
Conductor cross section solid min.1.5 mm²
Conductor cross section solid max.35 mm²
Conductor cross section AWG15 ... 2
10 ... 2 (UL)

Remote indicator contact

Connection nameRemote fault indicator contact
Switching functionPDT contact
Connection methodScrew connection
Screw threadM2
Tightening torque0.25 Nm
4 lbf-in.
Stripping length7 mm
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section solid min.0.14 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section AWG28 ... 16
30 ... 14 (UL)
Maximum operating voltage Umax.AC250 V AC
Max. operating current Imax1.5 A AC (250 V AC)
1.5 A DC (30 V DC)

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.