VAL-MS/2+0-BE/FM/S2 2800246 PHOENIX CONTACT Type 2 surge protection base element View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-MS/2+0-BE/FM/S2 2800246 PHOENIX CONTACT Type 2 surge protection base element

VAL-MS/2+0-BE/FM/S2

2800246

PHOENIX_CONTACT

Type 2 surge protection base element

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $88.16
Unit price: $88.16

Quantity Price
1+$88.16
2+$82.98
3+$75.66
4+$71.51
6+$67.59
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2800246
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 50 (C-6-2013)
GTIN4046356519250
Weight per Piece (excluding packing)152.250 g
Custom tariff number85366990
Country of originDE (Germany)

Dimensions

Height96.8 mm
Width35.6 mm
Depth51.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch2 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPBT
Degree of pollution2
Flammability rating according to UL 94V-0
TypeBase element, DIN rail mounting
Number of positions2
Surge protection fault messageRemote indication contact

Protective circuit

Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC500 V AC
Rated load current IL80 A
Short-circuit current rating ISCCR25 kA
Max. backup fuse with V-type through wiring80 A (gG)
Max. backup fuse with branch wiring200 A (gG)

Indicator/remote signaling

Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
30 V DC
Operating current5 mA AC ... 1.5 A AC
1 A DC
Connection methodPlug-in/screw connection via COMBICON
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque3 Nm (1,5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
Stripping length16 mm
Conductor cross section flexible1.5 mm² ... 25 mm²
Conductor cross section solid1.5 mm² ... 35 mm²
Conductor cross section AWG15 ... 2
Connection methodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 16 mm²

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.