PSR-SPP- 24DC/URM4/4X1/2X2/B 2981680 PHOENIX CONTACT Extension module View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PSR-SPP- 24DC/URM4/4X1/2X2/B 2981680 PHOENIX CONTACT Extension module

PSR-SPP- 24DC/URM4/4X1/2X2/B

2981680

PHOENIX_CONTACT

Extension module

More details


Safety

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $238.43
Unit price: $238.43

Quantity Price
1+$238.43
2+$204.37
3+$192.13
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2981680
Packing unit1 pc
Catalog pagePage 265 (C-6-2017)
GTIN4046356081542
Weight per Piece (excluding packing)196.500 g
Custom tariff number85371098
Country of originDE (Germany)

Dimensions

Width22.5 mm
Height112 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 55 °C
Ambient temperature (storage/transport)-40 °C ... 70 °C
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Maximum altitudemax. 2000 m (Above sea level)

Input data

Rated control circuit supply voltage US
Nominal input voltage UN24 V DC
Input voltage range in reference to UN0.9 ... 1.1
Typical input current at UN42 mA
Typical response time10 ms
Typical release time10 ms
Recovery time1 s
Status displayGreen LED
Protective circuitSurge protection Suppressor diode

Output data

Contact type4 enabling current paths
1 signaling current path
1 confirmation current path
Contact materialAgSnO2
Maximum switching voltage250 V AC/DC
Minimum switching voltage15 V AC/DC
Limiting continuous current6 A (N/O contact, DC1/AC1)
3 A (N/C contact)
Maximum inrush current6 A (N/O contact, DC1/AC1)
3 A (N/C contact)
Inrush current, minimum25 mA
Sq. Total current72 A2(ITH2= I12+ I22+ I32+ I42)
Interrupting rating (ohmic load) max.144 W (24 V DC, τ = 0 ms, N/C contact 61/62: 72 W)
288 W (48 V DC, τ = 0 ms, N/C contact 61/62: 144 W)
77 W (110 V DC, τ = 0 ms)
88 W (220 V DC, τ = 0 ms)
1500 VA (250 V AC, τ = 0 ms, N/C contact 61/62: 750 VA)
Maximum interrupting rating (inductive load)48 W (24 V DC, τ = 40 ms)
40 W (48 V DC, τ = 40 ms)
35 W (110 V DC, τ = 40 ms)
33 W (220 V DC, τ = 40 ms)
Switching capacity min.0.4 W
Mechanical service lifeapprox. 107cycles
Switching capacity (360/h cycles)6 A (24 V DC)
5 A (230 V AC)
Switching capacity according to IEC 60947-5-15 A (DC13)
5 A (AC15)
Output fuse10 A gL/gG NEOZED (N/O contact)
4 A gL/gG NEOZED (N/C contact)

General

Relay typeElectromechanical relay with forcibly guided contacts in accordance with EN 50205
Nominal operating mode100% operating factor
Net weight196.5 g
Mounting positionany
Mounting typeDIN rail mounting
Degree of protectionIP20
IP54
Min. degree of protection of inst. locationIP54
Housing coloryellow

Connection data

Connection methodSpring-cage connection
pluggableYes
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

Safety-related characteristic data

Stop category0
DesignationIEC 61508 - High demand
Safety Integrity Level (SIL)3 (In conjunction with suitable evaluating device)
DesignationIEC 61508 - Low demand
Safety Integrity Level (SIL)3 (In conjunction with suitable evaluating device)
DesignationEN ISO 13849
Performance level (PL)e (In conjunction with suitable evaluating device)
Category4 (In conjunction with suitable evaluating device)
DesignationEN 62061
Safety Integrity Level Claim Limit (SIL CL)3 (In conjunction with suitable evaluating device)

Standards and Regulations

DesignationAir clearances and creepage distances between the power circuits
Standards/regulationsIEC 60947-1
Rated insulation voltage250 V
Rated surge voltage/insulation4 kV / basic isolation (safe isolation, reinforced insulation and 6 kV between input circuit/N/C contacts and enabling current paths).
Degree of pollution2
Overvoltage categoryIII

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.