ANUNCIAR
CBMC E4 24DC/1-10A NO 2906032 PHOENIX CONTACT Electronic device circuit breaker View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

CBMC E4 24DC/1-10A NO 2906032 PHOENIX CONTACT Electronic device circuit breaker

CBMC E4 24DC/1-10A NO

2906032

PHOENIX_CONTACT

Electronic device circuit breaker

Multi-channel electronic equipment protection switch to protect four consumers in 24 V DC in case of overload and short circuit. With electronic locking of the set rated currents. For installation on DIN rails.

Multi-channel electronic circuit breaker for protecting four loads at 24 V DC in the event of overload and short circuit. With electronic locking of the set nominal currents. For installation on DIN rails.

More details


Circuit breakers and fuses > Device circuit breaker

Over Current Protection

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total: $169.83
Unit price: $169.83
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Technical data

Notes
General
NoteRepeated hard short circuits can reduce the melting integral of the integrated backup fuse.

Product properties
Product typeDevice circuit breakers
Product familyCBMC
TypeDIN rail module, one-piece
Number of positions1
No. of channels4
Data management status
Article revision12
Insulation characteristics
Protection classIII
Pollution degree2

Electrical properties
General
Operating voltage18 V DC ... 30 V DC
Rated voltage24 V DC
Rated current INmax. 40 A DC (IN+)
max. 40 A DC (per terminal position when bridging additional devices via IN+)
Rated current IN1 / 2 / 3 / 4 / 5 / 6 / 7 / 8 / 9 / 10 A DC (adjustable per output channel)
Rated current (pre-adjusted)4 A
Rated surge voltage0.5 kV
Tripping methodE (electronic)
Feedback resistancemax. 35 V DC
Required backup fuseOnly required if Imaxof the power supply > the short-circuit switching capacity. Integrated failsafe element.
Short-circuit switching capacity300 A
Dielectric strengthmax. 35 V DC (Load circuit)
Fuseelectronic
Efficiency> 99 %
Closed circuit current I0typ. 25 mA
Power dissipationtyp. 0.6 W (No-load operation)
< 9 W (Nominal operation)
Module initialization time1.6 s
Waiting time after switch off of a channel5 s (at overload / short circuit)
Measuring tolerance I± 15 %
Temperature derating24 A DC (at 60 °C)
28 A DC (at 54 °C)
32 A DC (at 47 °C)
36 A DC (at 41 °C)
40 A DC (at 35 °C)
MTBF (IEC 61709, SN 29500)8403361 h (at 25 °C with 21 % load)
3067484 h (at 40°C with 34.25% load)
534188 h (at 35 °C with 100 % load)
Fail-safe element15 A DC (per output channel)
Load circuit
Shutdown time≤ 10 ms (for short circuit > 2.0 x IN)
1 s (1.2 ... 2.0 x IN)
Undervoltage switch-off≤ 17.8 V DC (active)
≥ 18.8 V DC (inactive)
Overvoltage switch-off≥ 30.5 V DC (active)
≤ 29.5 V DC (inactive)
Max. capacitive load45000 µF (Depending on the current setting and the short-circuit current available)
Switch-on delay0.1 s (per output channel)
Indicator/remote signaling
Connection nameRemote indication circuit
Switching functionN/O contact
Operating voltage0 V DC ... 30 V DC
Operating current100 mA DC

Connection data
Main circuit IN+
Connection methodPush-in connection
Stripping length15 mm
Conductor cross section rigid0.2 mm² ... 10 mm²
Conductor cross section AWG24 ... 8
Conductor cross section, flexible, with ferrule, with plastic sleeve0.25 mm² ... 4 mm²
Conductor cross section flexible, with ferrule without plastic sleeve0.25 mm² ... 6 mm²
Main circuit IN-
Connection methodPush-in connection
Stripping length10 mm
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 12
Conductor cross section, flexible, with ferrule, with plastic sleeve0.25 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve0.25 mm² ... 2.5 mm²
Main circuit OUT
Connection methodPush-in connection
Stripping length10 mm
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 12
Conductor cross section, flexible, with ferrule, with plastic sleeve0.25 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve0.25 mm² ... 2.5 mm²
Remote indication circuit
Stripping length10 mm
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 12
Conductor cross section, flexible, with ferrule, with plastic sleeve0.25 mm² ... 1.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve0.25 mm² ... 2.5 mm²

Signaling
Channel LED offoff (Channel switched off)
Channel LED yellowlit (Channel switched on, channel load > 80% )
flashing (Programming mode active)
Channel LED greenlit (Channel switched on)
Channel LED redlit (Channel switched off, over- or undervoltage active)
ON temporarily (Channel switched off, 5 s cool-down phase, overload or short-circuit release)
flashing (Channel switched off, ready to be switched back on, overload or short-circuit release)
two flashes (Channel switched off, device total current limit 40 A exceeded)

Dimensions
Dimensional drawingfxmazmkjwc.jpg
Width36 mm
Height90 mm
Depth98 mm (incl. DIN rail 7.5 mm)

Material specifications
Colorlight gray (RAL 7035)
MaterialPC
PA 6.6
PA 6.3T
POM
Flammability rating according to UL 94V-0

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 70 °C
Altitude≤ 3000 m up to 52 °C (amsl)
≤ 4000 m up to 46 °C (amsl)
Humidity test96 h, 95 % RH, 40 °C
Shock (operation)30g (IEC 60068-2-27, Test Ea)
Vibration (operation)10 Hz ... 57.6 Hz (Amplitude ±0.35 mm; in accordance with IEC 60068-2-6, Test Fc)
57.6 Hz … 150 Hz (Acceleration 5g; in accordance with IEC 60068-2-6, Test Fc)

Approvals
UL approval
IdentificationUL/C-UL Listed UL 508
UL Recognized UL 2367
Corrosive gas test
IdentificationISA S71.04.2013 G3 Harsh Group A

Standards and regulations
Standards/specificationsEN 61000-6-2
NoteEMC – Immunity for industrial areas
Standards/specificationsEN 61000-6-3
NoteEMC – Emission for residential, business and commercial properties and small operations
Standards/specificationsEN 60068-2-6
NoteEnvironmental influences – Vibrations (sinusoidal)
Standards/specificationsEN 60068-2-27
NoteEnvironmental influences – Shocks
Standards/specificationsEN 60068-2-78
NoteEnvironmental influences – Moisture and heat, constant
Standards/specificationsEN 50178
NoteEquipping power installations with electronic equipment

Mounting
Mounting typeDIN rail: 35 mm

ETIM for 2906032 Circuit breakers and fuses (EC003538)
Feature Name Feature Value
Inflammability class of insulation material according to UL94 (EF002521) Other
Number of poles (EF001391) 1
Width (EF000008) 36 mm
Height (EF000040) 90 mm
Depth (EF000049) 98 mm
Mounting method (EF000003) Other
Operating voltage (EF000111) 30 V
Nominal current (EF000001) 40 A
Active current limitation x IN (EF011922) 0
Fuse type (EF011923) Electronic
Fail safe element (EF011924) 15 A
Switch-off time (EF011925) 0.01 ms
Max. capacitive load (EF011926) 0.045 µF
With remote signalling contact (EF000422) Yes
Ambient temperature during operating (EF007515) -25 °C

Datasheet - PDF

Title: Size: Type:
PDF CATALOG PHOENIX PROTECTION EN.pdf 27 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.