Product successfully added to your shopping cart
6AG1137-6BD00-2BA0
SIEMENS
1
SIPLUS ET 200SP CM 4XIO-LINK -40...+60°C start up temperature: -25°C with conformal coating based on 6ES7137-6BD00-0BA0 . CM 4 X IO-LINK ST Communication Module IO-LINK MASTER V1.1
SIPLUS ET 200SP -40...+70 ° C temp. boot: -25 ° C with coating formed based on 6ES7137-6BD00-0BA0 . CM 4 X IO-LINK ST communication module IO-LINK MASTER V1.1
AUTOMATION SYSTEMS > SIPLUS Extreme (LOGO, S7-1200, S7-1500, etc)
Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Value | Unit | |
|---|---|---|
| Radio standard WLAN 802.11 (EF007179) | - | |
| Supporting protocol for DeviceNet (EF003059) | - | |
| Supporting protocol for Foundation Fieldbus (EF007522) | - | |
| Height (EF000040) | - | mm |
| Depth (EF000049) | - | mm |
| Supply voltage AC 50 Hz (EF007532) | ['-', '-'] | V |
| Supply voltage AC 60 Hz (EF007533) | ['-', '-'] | V |
| Supply voltage DC (EF007534) | ['19.2', '28.8'] | V |
| Voltage type of supply voltage (EF002991) | DC | |
| Supporting protocol for TCP/IP (EF003050) | NO DATA | |
| Supporting protocol for PROFIBUS (EF003052) | true | |
| Supporting protocol for CAN (EF003053) | false | |
| Supporting protocol for INTERBUS (EF003054) | false | |
| Supporting protocol for ASI (EF003051) | false | |
| Supporting protocol for KNX (EF003055) | false | |
| Supporting protocol for Modbus (EF003057) | false | |
| Supporting protocol for Data-Highway (EF003058) | false | |
| Supporting protocol for SUCONET (EF003060) | false | |
| Supporting protocol for LON (EF003017) | false | |
| Supporting protocol for SERCOS (EF006657) | false | |
| Supporting protocol for PROFINET IO (EF007525) | true | |
| Supporting protocol for PROFINET CBA (EF007524) | false | |
| Supporting protocol for EtherNet/IP (EF007521) | false | |
| Supporting protocol for AS-Interface Safety at Work (EF007519) | false | |
| Supporting protocol for DeviceNet Safety (EF007520) | false | |
| Supporting protocol for INTERBUS-Safety (EF006662) | false | |
| Supporting protocol for PROFIsafe (EF007526) | false | |
| Supporting protocol for SafetyBUS p (EF007527) | false | |
| Supporting protocol for other bus systems (EF003062) | false | |
| Radio standard Bluetooth (EF007178) | false | |
| Radio standard GPRS (EF008523) | false | |
| Radio standard GSM (EF008524) | false | |
| Radio standard UMTS (EF008525) | false | |
| IO link master (EF007298) | true | |
| System accessory (EF004118) | true | |
| Degree of protection (IP) (EF005474) | IP20 | |
| With potential separation (EF003272) | true | |
| Fieldbus connection over separate bus coupler possible (EF004002) | false | |
| Rail mounting possible (EF003972) | true | |
| Wall mounting/direct mounting (EF007020) | false | |
| Front build in possible (EF007016) | true | |
| Rack-assembly possible (EF007018) | true | |
| Suitable for safety functions (EF001597) | false | |
| Category according to EN 954-1 (EF006782) | - | |
| SIL according to IEC 61508 (EF009889) | - | |
| Performance level according to EN ISO 13849-1 (EF007399) | - | |
| Appendant operation agent (Ex ia) (EF004141) | false | |
| Appendant operation agent (Ex ib) (EF004142) | false | |
| Explosion safety category for gas (EF003997) | None | |
| Explosion safety category for dust (EF003998) | None | |
| Width (EF000008) | 15.0 | mm |
| SIPLUS ET 200SP CM 4XIO-LINK -40...+60°C start up temperature: -25°C with conformal coating based on 6ES7137-6BD00-0BA0 . CM 4 X IO-LINK ST Communication Module IO-LINK MASTER V1.1 | ||
| General information | ||
| Product type designation | CM 4 x IO-Link ST | |
| usable BaseUnits | BU type A0 | |
| Color code for module-specific color identification plate | CC04 | |
| Product function | ||
| ● I&M data | Yes | |
| ● Isochronous mode | Yes; For PROFINET only | |
| Supply voltage | ||
| Rated value (DC) | 24 V | |
| permissible range, lower limit (DC) | 19.2 V; 20.5 V if IO-Link is used, as the supply voltage for IO-Link devices has to be at least 20 V at the master. | |
| permissible range, upper limit (DC) | 28.8 V | |
| Reverse polarity protection | Yes | |
| Input current | ||
| Current consumption, max. | 45 mA; without load | |
| Encoder supply | ||
| Number of outputs | 4 | |
| Output current | ||
| ● Rated value | 200 mA | |
| Power loss | ||
| Power loss, typ. | 1 W | |
| Digital outputs | ||
| Cable length | ||
| ● unshielded, max. | 20 m; Also applies for shielded cables | |
| IO-Link | ||
| Number of ports | 4 | |
| ● of which simultaneously controllable | 4 | |
| IO-Link protocol 1.0 | Yes | |
| IO-Link protocol 1.1 | Yes | |
| Transmission rate | 4.8 kBaud (COM1); 38.4 kBaud (COM2), 230.4 kBaud (COM3) | |
| Cycle time, min. | 2 ms; dynamic, depending on user data length | |
| Size of process data, input per port | 32 byte; max. | |
| Size of process data, input per module | 32 byte; max. | |
| Size of process data, output per port | 32 byte; max. | |
| Size of process data, output per module | 32 byte; max. | |
| Memory size for device parameter | 2 kbyte; for each port | |
| Cable length unshielded, max. | 20 m; max. | |
| Operating modes | ||
| ● IO-Link | Yes | |
| ● DI | Yes | |
| ● DQ | Yes; max. 100 mA | |
| Time Based IO | ||
| — TIO IO-Link IN | Yes | |
| — TIO IO-Link OUT | Yes | |
| — TIO IO-Link IN/OUT | Yes | |
| — TIO Jitter | 36 µs; typically ± | |
| Connection of IO-Link devices | ||
| ● Port type A | Yes | |
| ● Port type B | Yes; 24 V DC via external terminal | |
| Isochronous mode | ||
| Equidistance | Yes | |
| Bus cycle time (TDP), min. | 250 µs | |
| Interrupts/diagnostics/status information | ||
| Status indicator | Yes | |
| Diagnostics function | Yes | |
| Alarms | ||
| ● Diagnostic alarm | Yes; The port diagnosis is available in the IO-Link mode only. | |
| Diagnoses | ||
| ● Monitoring the supply voltage | Yes | |
| Diagnostics indication LED | ||
| ● Monitoring of the supply voltage (PWR-LED) | Yes; green PWR LED | |
| ● Channel status display | Yes; one green LED for channel status Qn (SIO mode) and port status Cn (IO-Link mode) per channel | |
| ● for channel diagnostics | Yes; red Fn LED | |
| ● for module diagnostics | Yes; green/red DIAG LED | |
| Potential separation | ||
| Potential separation channels | ||
| ● between the channels | No | |
| ● between the channels and backplane bus | Yes | |
| Permissible potential difference | ||
| between different circuits | 75 V DC/60 V AC (base isolation) | |
| Isolation | ||
| Isolation tested with | 707 V DC (type test) | |
| Ambient conditions | ||
| Ambient temperature during operation | ||
| ● horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost); start-up @ -25 °C | |
| ● horizontal installation, max. | 60 °C; = Tmax | |
| Altitude during operation relating to sea level | ||
| ● Installation altitude above sea level, max. | 5 000 m | |
| ● Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) | |
| Relative humidity | ||
| ● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
| Resistance | ||
| Coolants and lubricants | ||
| — Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air | |
| Use in stationary industrial systems | ||
| — to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | |
| — to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | |
| — to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * | |
| — Against mechanical environmental conditions acc. to EN 60721-3-3 | Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | |
| Use on ships/at sea | ||
| — to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request | |
| — to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | |
| — to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * | |
| — Against mechanical environmental conditions acc. to EN 60721-3-6 | Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | |
| Usage in industrial process technology | ||
| — Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) | |
| — Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) | |
| Remark | ||
| — Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! | |
| Conformal coating | ||
| ● Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability | |
| ● Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection | |
| ● Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life | |
| ● Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, Class A | |
| Dimensions | ||
| Width | 15 mm | |
| Weights | ||
| Weight, approx. | 30 g | |
| last modified: | 08/29/2020 | |
| Product | ||||||||||||||||||||||||||||||||||
| Article Number (Market Facing Number) | 6AG1137-6BD00-2BA0 | |||||||||||||||||||||||||||||||||
| Product Description | SIPLUS ET 200SP CM 4XIO-LINK -40...+60°C start up temperature: -25°C with conformal coating based on 6ES7137-6BD00-0BA0 . CM 4 X IO-LINK ST Communication Module IO-LINK MASTER V1.1 | |||||||||||||||||||||||||||||||||
| Product family | SIPLUS CM 4x IO-Link | |||||||||||||||||||||||||||||||||
| Product Lifecycle (PLM) | PM300:Active Product | |||||||||||||||||||||||||||||||||
| Price data | ||||||||||||||||||||||||||||||||||
| Price Group | 473 | |||||||||||||||||||||||||||||||||
| Surcharge for Raw Materials | None | |||||||||||||||||||||||||||||||||
| Metal Factor | None | |||||||||||||||||||||||||||||||||
| Delivery information | ||||||||||||||||||||||||||||||||||
| Export Control Regulations | AL : N / ECCN : EAR99H | |||||||||||||||||||||||||||||||||
| Standard lead time ex-works | 42 Day/Days | |||||||||||||||||||||||||||||||||
| Net Weight (kg) | 0,038 Kg | |||||||||||||||||||||||||||||||||
| Product Dimensions (W x L x H) | Not available | |||||||||||||||||||||||||||||||||
| Packaging Dimension | 7,70 x 6,50 x 2,30 | |||||||||||||||||||||||||||||||||
| Package size unit of measure | CM | |||||||||||||||||||||||||||||||||
| Quantity Unit | 1 Piece | |||||||||||||||||||||||||||||||||
| Packaging Quantity | 1 | |||||||||||||||||||||||||||||||||
| Additional Product Information | ||||||||||||||||||||||||||||||||||
| EAN | 4047618072339 | |||||||||||||||||||||||||||||||||
| UPC | 804766353277 | |||||||||||||||||||||||||||||||||
| Commodity Code | 85176200 | |||||||||||||||||||||||||||||||||
| LKZ_FDB/ CatalogID | A&DSE/SIP ADD | |||||||||||||||||||||||||||||||||
| Product Group | 4257 | |||||||||||||||||||||||||||||||||
| Group Code | R740 | |||||||||||||||||||||||||||||||||
| Country of origin | Germany | |||||||||||||||||||||||||||||||||
| Compliance with the substance restrictions according to RoHS directive | Since: 01.06.2016 | |||||||||||||||||||||||||||||||||
| Product class | B: return restricted, please contact your Siemens partner/contact | |||||||||||||||||||||||||||||||||
| WEEE (2012/19/EU) Take-Back Obligation | Yes | |||||||||||||||||||||||||||||||||
| REACH Art. 33 Duty to inform according to the current list of candidates |
| |||||||||||||||||||||||||||||||||
| Classifications | ||||||||||||||||||||||||||||||||||
| ||||||||||||||||||||||||||||||||||
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE SIEMENS EN.pdf | 120 Mbytes |
|
| PDF CATALOGUE SIEMENS EN.pdf | 104 Mbytes |
|
| 6AG1137-6BD00-2BA0 EN_6AG1137-6BD00-2BA0.pdf | 112 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.