Base element

Base element for type 1/2 unloaders for the VALVETRAB MS T1/T2 product series, with remote indication contact. Construction: 1 channel

More details


Earthing, lightning and surge protection > Accessories/spare parts for surge protection power supply systems

Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total: $557.03
Unit price: $55.70
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Key Commercial Data

Orderkey2801047
Packing unit10 pc
Minimum order quantity10 pc
NoteMade to Order (non-returnable)
GTIN4046356698146
Weight per Piece (excluding packing)82.000 g
Custom tariff number85366990
Country of originDE (Germany)

Dimensions

Height96.8 mm
Width17.6 mm
Depth51.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationI / II
T1 / T2
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPA 6.6
Degree of pollution2
Flammability rating according to UL 94V-0
TypeBase element, DIN rail mounting
Number of positions1
Surge protection fault messageRemote indication contact

Protective circuit

Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC500 V AC
Rated load current IL80 A
Short-circuit current rating ISCCR25 kA
Max. backup fuse with V-type through wiring80 A (gG - 16 mm²)
Max. backup fuse with branch wiring250 A (gG)

Indicator/remote signaling

Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
30 V DC (200 mA DC)
Operating current5 mA AC ... 1 A AC
1 A DC (30 V DC)
Connection methodPlug-in/screw connection via COMBICON
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque3 Nm (1,5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
Stripping length16 mm
Conductor cross section flexible1.5 mm² ... 25 mm²
Conductor cross section solid1.5 mm² ... 35 mm²
Conductor cross section AWG15 ... 2
Connection methodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 16 mm²

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Classifications


Datasheet - PDF

Title: Size: Type:
PDF CATALOG PHOENIX PROTECTION EN .pdf 27 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.