UBK 2-500 2798530 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

UBK 2-500 2798530 PHOENIX CONTACT Surge protection device

UBK 2-500

2798530

PHOENIX_CONTACT

Surge protection device

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total price: $135.18
Unit price: $135.18

Quantity Price
1+$135.18
2+$114.30
3+$105.80
4+$103.78
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2798530
Packing unit10 pc
Catalog pagePage 54 (TT-2002)
GTIN4017918073800
Weight per Piece (excluding packing)60.010 g
Custom tariff number85363010
Country of originGR (Greece)

Dimensions

Height90 mm
Width17.5 mm
Depth46 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 mm (amsl (above mean sea level))
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-2
Colorjet black RAL 9005
Standards for cearances and creepage distancesIEC 60664-1
Mounting typeDIN rail: 35 mm
TypeDIN rail module, one-piece
Direction of actionLine-Earth Ground

Protective circuit

IEC test classificationC2
D1
Nominal voltage UN500 V AC
Maximum continuous voltage UC500 V AC
Rated current2 A
Operating effective current ICat UC≤ 1 µA
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (line-line)10 kA
Nominal discharge current In(8/20) µs (line-earth)10 kA
Pulse discharge current Iimp(10/350) µs2.5 kA
Output voltage limitation at 1 kV/µs (line-line) static≤ 2.5 kV
≤ 2.7 kV (4 kV (1.2/50) µs)
Output voltage limitation at 1 kV/µs (line-earth) static≤ 1.5 kV
≤ 1.7 kV (4 kV (1.2/50) µs)
Voltage protection level Up(line-line)3.5 kV (C2 - 10 kV / 5 kA)
Voltage protection level Up(line-earth)2.2 kV (C2 - 10 kV / 5 kA)
2.3 kV (Iimp -2.5 kA)
Response time tA(line-line)≤ 100 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0 dB (≤ 30 MHz / 50 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm systemtyp. 60 MHz
Capacity (line-line)typ. 7 pF
Surge protection fault messagenone
Max. required back-up fuse2 A (gL)
Impulse durability (line-line)C2 - 10 kV/5 kA
Impulse durability (line-earth)C2 - 10 kV/5 kA
D1 - 2.5 kA
Alternating current carrying capacity (line-line)10 A - 1 s
Alternating current carrying capacity (line-earth)10 A - 1 s

Connection data

Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm
Stripping length8 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Standards and Regulations

Standards/specificationsIEC 61643-21 2000 + A1:2008
EN 61643-21 2001 + A1:2009

Environmental Product Compliance

REACh SVHCLead 7439-92-1

Classifications

Datasheet - PDF

Title: Size: Type:
PDF CATALOG PHOENIX PROTECTION EN.pdf 27 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.