TTC-6-TVSD-C-60DC-UT-I 2906833 PHOENIX CONTACT Fine surge protection with integrated status indicator for a .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

TTC-6-TVSD-C-60DC-UT-I 2906833 PHOENIX CONTACT Fine surge protection with integrated status indicator for a ..

TTC-6-TVSD-C-60DC-UT-I

2906833

PHOENIX_CONTACT

Fine surge protection with integrated status indicator for a signal wire with grounded reference potential.

Fine surge protection with integrated status indication for a grounded signal conductor with reference potential.

Fine surge protection with integrated status indicator for one signal wire with grounded reference potential. Can be used in safety-related circuits up to SIL 3.

More details


Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Technical data

Product properties
Product typeSurge protection for MCR technology
Product familyTERMITRAB complete
IEC test classificationC3
TypeDIN rail module, one-piece
Surge protection fault messageoptical
Data management status
Article revision08
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Nominal voltage UN60 V DC

Connection data
Connection methodScrew connection
Screw threadM3
Tightening torque0.5 Nm ... 0.6 Nm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section rigid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Dimensions
Dimensional drawingdxsjqyksqp.jpg
Width6.2 mm
Height92 mm
Depth69.5 mm (incl. DIN rail 7.5 mm)

Material specifications
Colorgray (RAL 7042)
Flammability rating according to UL 94V-0
Insulating materialPBT
Housing materialPBT

Mechanical properties
Mechanical data
Open side panelYes

Protective circuit
Direction of actionLine-Earth Ground
Maximum continuous voltage UC75 V DC
53 V AC
Rated current10 A (60 °C)
Operating effective current ICat UC≤ 5 µA
Residual current IPE≤ 5 µA
Nominal discharge current In(8/20) µs (line-ground)60 A
Voltage protection level Up(line-earth)≤ 110 V (C3 - 12 A)
Response time tA(line-earth)≤ 1 ns
Input attenuation aE, asym.typ. 0.3 dB (≤ 1.2 MHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω systemtyp. 4 MHz
Capacity (Core-Earth)0.6 nF
Resistance per path≤ 100 mΩ
Surge protection fault messageoptical
Impulse durability (line-earth)C3 - 12 A

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20 (with end cover)
Ambient temperature (operation)-40 °C ... 85 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl)
Permissible humidity (operation)5 % ... 95 %

Standards and regulations
Standards/specificationsIEC 61643-21
Note2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN 61643-21
Standards/specificationsEN 61643-21
Note2001 + A1:2009 + A2:2013

Mounting
Mounting typeDIN rail: 35 mm

Datasheet - PDF

Title: Size: Type:
PDF CATALOG PHOENIX PROTECTION EN .pdf 27 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.