Combination of type 2 surge protection and arrester backup fuse, with arrester monitoring, in combination with a status indicator and remote indication contact. Design: 5-conductor system (L1, L2, L3, N, PE), mounting on 60 mm system technology (power rail system)

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection - PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
1+$444.86
2+$429.68
3+$422.57
4+$420.38
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Height220 mm
Width54 mm
Depth134 mm

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 55 °C
Ambient temperature (storage/transport)-40 °C ... 75 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %

General

IEC power supply systemTN-S
TT
Housing materialPBT
PA 6
PA 66
Flammability rating according to UL 94V-0
Colorblue-gray
jet black RAL 9005
Standards for cearances and creepage distancesDIN VDE 0110-1
IEC 60664-1
IEC 61643-11
Mounting type60 mm system technology (power rail)
TypeModule for 60 mm system technology
Number of positions4
Surge protection fault messageOptical, remote indicator contact
Direction of action3L-N & N-PE

Protective circuit

IEC test classificationII
T2
EN typeT2
Nominal voltage UN240/415 V AC (TN-S)
Maximum continuous operating voltage UC (L-N)350 V AC
Maximum continuous operating voltage UC (N-PE)264 V AC
Nominal frequency fN50 Hz (60 Hz)
Residual current IPE≤ 1 µA
Max. discharge current Imax (8/20) µs maximum (L-N)25 kA
Max. discharge current Imax (8/20) µs maximum (L-PE)25 kA
Max. discharge current Imax (8/20) µs maximum (N-PE)40 kA
Nominal discharge current In (8/20) µs20 kA
Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE)≤ 1.5 kV
Insulation resistance Riso> 5 MΩ (500 V DC)
Voltage protection level Up (L-N)≤ 2.5 kV
Voltage protection level Up (N-PE)≤ 1.5 kV
Response time tA (L-N)≤ 25 ns
Response time tA (N-PE)≤ 100 ns
Max. backup fuse with branch wiringNot required
Short-circuit current rating ISCCR25 kA
Follow current quenching capacity Ifi (N-PE)100 A (264 V AC)

PE conductor connection

Connection methodScrew connection
Connection type INBiconnect screw terminal block
Connection type OUTBiconnect screw terminal block
Connection methodBiconnect terminal block
Screw threadM5
Stripping length16 mm
16 mm
Conductor cross section flexible min.2.5 mm²
Conductor cross section flexible max.16 mm²
Conductor cross section solid min.2.5 mm²
Conductor cross section solid max.25 mm²
Conductor cross section AWG min.12
Conductor cross section AWG max.4

N conductor connection

Connection methodScrew connection
Connection type INBiconnect screw terminal block
Connection type OUTBiconnect screw terminal block
Connection methodBiconnect terminal block
Screw threadM5
Stripping length16 mm
Conductor cross section flexible min.2.5 mm²
Conductor cross section flexible max.16 mm²
Conductor cross section solid min.2.5 mm²
Conductor cross section solid max.25 mm²
Conductor cross section AWG min.12
Conductor cross section AWG max.4

Phase conductor connection

Connection namePhase conductor connection
Connection method60 mm power rail system

Remote indicator contact

Connection nameRemote fault indicator contact
Switching functionPDT contact
Connection methodPluggable screw connection
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section solid min.0.14 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section AWG28 ... 16

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Datasheet - PDF

Title: Language: Size: Type:
PHOENIX CONTACT-2804403-VAL-CP-MOSO 60-3S-FM English 171 Kbytes PHOENIX CONTACT-2804403-VAL-CP-MOSO 60-3S-FM

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.