F-MS 2200/30 ST 2805392 PHOENIX CONTACT Surge protection plug type 2, spark gap with high insulation voltage.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

F-MS 2200/30 ST 2805392 PHOENIX CONTACT Surge protection plug type 2, spark gap with high insulation voltage..

F-MS 2200/30 ST

2805392

PHOENIX_CONTACT

10

Available

Ship on today

Surge protection plug type 2, spark gap with high insulation voltage strength, used only as replacement plug for the corresponding complete item.

More details


Overvoltage Protection Over Voltage

TRABTECH Power and Signal Quality - PHOENIX CONTACT

Surge protection - PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
10+$69.45
20+$67.44
30+$67.25
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Height52.4 mm
Width17.5 mm
Depth55.3 mm
Horizontal pitch1 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g
Vibration (operation)5g

General

Standards/specificationsIEC 61643-11 2011
EN 61643-11 2012
IEC test classificationII
T2
EN typeT2
SPD designVoltage-switching type
Mode of protectionL-PE
Mounting typeOn base element
Colorblack
Housing materialPA 6.6
Pollution degree3
Distance between live and grounded parts8 mm
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions1
Surge protection fault messageoptical

Additional descriptions

NoteThe F-MS 2200/30 ST protective plug is only to be used in connection with VAL-MS 750/30 ST (2920256) in series connection. It is not designed to be directly used on the mains voltage. Replacement plugs for use on product VAL-MS 800/30-VF/FM (2805402).
VSDC > 2200 V

Protective circuit

Nominal frequency fN50 Hz
60 Hz
Residual current IPE≤ 3 µA
Nominal discharge current In (8/20) µs15 kA
Maximum discharge current Imax (8/20) µs30 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 5 kV
Residual voltage Ures≤ 0.4 kV (at In)
≤ 0.25 kV (at 10 kA)
≤ 0.15 kV (at 5 kA)
≤ 0.1 kV (at 3 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 5 kV
TOV behavior at UT1550 V AC (200 ms / withstand mode)
Response time tA≤ 100 ns

Connection data

Connection methodVALVETRAB plug-in system

Datasheet - PDF

Title: Language: Size: Type:
PHOENIX CONTACT-2805392-F-MS 2200/30 ST English 110 Kbytes PHOENIX CONTACT-2805392-F-MS 2200/30 ST

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.