Combination of type 2 surge protection and arrester pre-fuse, with arrester monitoring, in combination with status indication and remote indication contact. Version: 4-conductor system (L1, L2, L3, PEN), installation in 60 mm system technology (busbar system)

More details


Earthing, lightning and surge protection > Surge protection device for power supply systems

Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total: $614.71
Unit price: $614.71
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Key Commercial Data

Orderkey2804416
Packing unit1 pc
Catalog pagePage 68 (C-4-2017)
GTIN4046356317832
Weight per Piece (excluding packing)1,200.000 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height220 mm
Width54 mm
Depth134 mm

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 55 °C
Ambient temperature (storage/transport)-40 °C ... 75 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN-C
TT
Mode of protectionL-PEN
Mounting type60 mm system technology (power rail)
Colorblue-gray
jet black RAL 9005
Housing materialPBT
PA 6
PA 6.6
Degree of pollution2
Flammability rating according to UL 94V-0
TypeModule for 60 mm system technology
Number of positions3
Surge protection fault messageOptical, remote indicator contact

Protective circuit

Nominal voltage UN240/415 V AC (TN-C)
240/415 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC350 V AC
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs25 kA
Short-circuit current rating ISCCR25 kA
Voltage protection level Up≤ 2.5 kV
Residual voltage Ures≤ 2.1 kV (at In)
≤ 1.9 kV (at 10 kA)
≤ 1.8 kV (at 5 kA)
≤ 1.7 kV (at 3 kA)
TOV behavior at UT415 V AC (5 s / withstand mode)
440 V AC (120 min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with branch wiringnot required

Indicator/remote signaling

Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
125 V DC (200 mA DC)
Operating current5 mA AC ... 1 A AC
1 A DC (30 V DC)
Connection methodPluggable screw connection
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection namePEN conductor connection
Connection methodScrew connection
Screw threadM5
Tightening torque4.5 Nm
Stripping length16 mm
Conductor cross section flexible2.5 mm² ... 16 mm²
Conductor cross section solid2.5 mm² ... 25 mm²
Conductor cross section AWG12 ... 4
Connection namePhase conductor connection
Connection method60 mm power rail system

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2804416 Earthing, lightning and surge protection (EC000941)
Feature Name Feature Value
System configuration DC (EF009926) No
System configuration IT (EF009927) No
System configuration TN (EF009928) No
System configuration TN-C (EF009929) Yes
System configuration TN-C-S (EF009933) No
System configuration TN-S (EF009930) No
System configuration TT (EF009931) No
System configuration other (EF009932) No
Nominal discharge surge current (8/20) (EF004214) 20 kA
Max. discharge surge current (8/20) (EF012274) 25 kA
Max. continuous voltage AC (EF004198) 350 V
Voltage protection level L-N (EF004236) 2.5 kV
Short-circuit breaking capacity (Isccr) (EF012627) 25 kA
Integrated backup fuse (EF008797) Yes
Leakage-current free (EF016002) No
Max. conductor cross section solid (solid, stranded) (EF008827) 2.5 mm²
Max. conductor cross section flexible (fine-strand) (EF008828) 16 mm²
With remote signalling contact (EF000422) Yes
Signalling at the device (EF004241) Optic
Category type 2 (EF004230) Yes
Degree of protection (IP) (EF005474) IP20

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.