Product successfully added to your shopping cart
VAL-MS-T1/T2 335/12.5/1+1
2800187
PHOENIX_CONTACT
1
Lightning/surge arrester type 1/2
Trabtech (TT)
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Orderkey | 2800187 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 37 (C-4-2017) |
GTIN | 4046356518581 |
Weight per Piece (excluding packing) | 347.000 g |
Custom tariff number | 85363030 |
Country of origin | DE (Germany) |
Degree of protection | IP20 (only when all terminal points are used) |
---|---|
Ambient temperature (operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
IEC test classification | I / II |
---|---|
T1 / T2 | |
T1 | |
EN type | T1 / T2 |
T1 | |
IEC power supply system | TT |
TN-C | |
TN-S | |
Mode of protection | L-N |
L-PE | |
N-PE | |
Mounting type | DIN rail: 35 mm |
Color | jet black RAL 9005 |
Housing material | PA 6.6 |
PBT | |
Degree of pollution | 2 |
Flammability rating according to UL 94 | V-0 |
Type | DIN rail module, two-section, divisible |
Surge protection fault message | optical |
Nominal voltage UN | 240 V AC (TN-S) |
---|---|
240 V AC (TT) | |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous operating voltage UC(L-N) | 335 V AC |
Maximum continuous voltage UC(N-PE) | 264 V AC |
Rated load current IL | 80 A |
Residual current IPE | ≤ 5 µA |
Standby power consumption PC | ≤ 270 mVA |
Nominal discharge current In(8/20) µs (L-N) | 12.5 kA |
Nominal discharge current In(8/20) µs (L-PE) | 12.5 kA |
Nominal discharge current In(8/20) µs (N-PE) | 50 kA |
Maximum discharge current Imax(8/20) µs | 50 kA |
Impulse discharge current (10/350) µs (L-N), charge | 6.25 As |
Impulse discharge current (10/350) µs (L-N), specific energy | 39 kJ/Ω |
Impulse discharge current (10/350) µs (L-N), peak current value Iimp | 12.5 kA |
Impulse discharge current (10/350) µs (L-PE), charge | 6.25 As |
Impulse discharge current (10/350) µs (L-PE), specific energy | 39 kJ/Ω |
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp | 12.5 kA |
Impulse discharge current (10/350) µs (N-PE), charge | 25 As |
Impulse discharge current (10/350) µs (N-PE), specific energy | 625 kJ/Ω |
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp | 50 kA |
Total discharge current Itotal(8/20) µs | 50 kA |
Total discharge current Itotal(10/350) µs | 25 kA |
Follow current interrupt rating Ifi(N-PE) | 100 A |
Short-circuit current rating ISCCR | 25 kA |
Voltage protection level Up(L-N) | ≤ 1.2 kV |
≤ 1.6 kV (30 kA - 8/20 µs) | |
Voltage protection level Up(L-PE) | ≤ 2 kV |
Voltage protection level Up(N-PE) | ≤ 1.7 kV |
Residual voltage Ures(L-N) | ≤ 1.2 kV (at In) |
≤ 1.1 kV (at 10 kA) | |
≤ 1 kV (at 5 kA) | |
≤ 0.9 kV (at 3 kA) | |
Residual voltage Ures(L-PE) | ≤ 2 kV (at In) |
≤ 1.5 kV (at 10 kA) | |
≤ 1.2 kV (at 5 kA) | |
≤ 1.1 kV (at 3 kA) | |
Residual voltage Ures(N-PE) | ≤ 0.6 kV (at In) |
≤ 0.5 kV (at 10 kA) | |
≤ 0.5 kV (at 5 kA) | |
≤ 0.4 kV (at 3 kA) | |
TOV behavior at UT(L-N) | 415 V AC (5 s / withstand mode) |
457 V AC (120 min / safe failure mode) | |
TOV behavior at UT(N-PE) | 1200 V AC (200 ms / withstand mode) |
Response time tA(L-N) | ≤ 25 ns |
Response time tA(L-PE) | ≤ 100 ns |
Response time tA(N-PE) | ≤ 100 ns |
Max. backup fuse with V-type through wiring | 80 A (gG - 16 mm²) |
Max. backup fuse with branch wiring | 160 A (gG) |
Connection method | Screw connection |
---|---|
Screw thread | M5 |
Tightening torque | 3 Nm (1,5 mm² ... 16 mm²) |
4.5 Nm (25 mm² ... 35 mm²) | |
Stripping length | 16 mm |
Conductor cross section flexible | 1.5 mm² ... 25 mm² |
Conductor cross section solid | 1.5 mm² ... 35 mm² |
Conductor cross section AWG | 15 ... 2 |
Connection method | Fork-type cable lug |
Conductor cross section flexible | 1.5 mm² ... 16 mm² |
SPD Type | 4CA |
---|---|
Maximum continuous operating voltage MCOV (L-N) | 335 V AC |
Maximum continuous operating voltage MCOV (L-G) | 335 V AC |
Maximum continuous operating voltage MCOV (N-G) | 264 V AC |
Nom. voltage | 240 V AC |
Mode of protection | L-N |
L-G | |
N-G | |
Power distribution system | Single phase |
Nominal frequency | 50/60 Hz |
Measured limiting voltage MLV (L-N) | 2630 V |
Measured limiting voltage MLV (L-G) | 3600 V |
Measured limiting voltage MLV (N-G) | 2600 V |
Nominal discharge current In(L-N) | 20 kA |
Nominal discharge current In(L-G) | 20 kA |
Nominal discharge current In(N-G) | 20 kA |
Title: | Size: | Type: |
---|---|---|
PHOENIX CONTACT-2800187-VAL-MS-T1/T2 335/12.5/1+1 | 132 Kbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.