VAL-MS-T1/T2 600DC-PV/2+V 2801163 PHOENIX CONTACT Lightning/surge arrester type 1/2

VAL-MS-T1/T2 600DC-PV/2+V

2801163

PHOENIX_CONTACT

Lightning/surge arrester type 1/2

Lightning surge / current protection device for isolated and grounded 2-pole photovoltaic 600V DC DC systems, for rail mounting, 3-pole base element, three plug-in protection elements with temperature control, status message on each male connector.

More details


Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Key Commercial Data

Orderkey2801163
Packing unit1 pc
Catalog pagePage 41 (C-4-2017)
GTIN4046356714303
Weight per Piece (excluding packing)365.400 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height89.8 mm
Width53.4 mm
Depth65.7 mm (incl. DIN rail 7.5 mm)
Horizontal pitch3 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)60g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)7.5g (5-500 Hz/2.5 h/XYZ)

General

IEC test classificationPV I / II
PV T1 / T2
EN typeT1 / T2
SPD failure behaviorOCM (Open-circuit mode)
Connection configurationY configuration
Installation locationInside
AccessibilityAccessible
Installation location of the disconnect deviceInternal
Mode of protection(L+) - (L-)
(L+) - PE
(L-) - PE
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPA 6.6-FR
PBT-FR
Degree of pollution2
Distance between live and grounded parts8 mm
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Surge protection fault messageoptical

Additional descriptions

NoteThe device is intended for touch proof installation in a housing. Ensure that there is a gap of at least 8 mm between the active and grounded parts in the connection area.

Protective circuit DC voltage side (DC)

Maximum continuous operating voltage UCPV720 V DC
Short-circuit current rating ISCPV2000 A
Continuous operating current ICPV< 20 µA
Rated load current IL80 A
Residual current IPE≤ 20 µA DC
≤ 350 µA AC
Standby power consumption PC≤ 25 mVA
Nominal discharge current (8/20) µs15 kA
Maximum discharge current Imax(8/20) µs40 kA
Impulse discharge current (10/350) µs, charge2.5 As
Impulse discharge current (10/350) µs, specific energy6.25 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp5 kA
Total discharge current Itotal(8/20) µs40 kA
Total discharge current Itotal(10/350) µs7 kA
Voltage protection level Up≤ 2.6 kV
Residual voltage Ures≤ 2.6 kV (at In)
≤ 2 kV (at 5 kA)
≤ 2.3 kV (at 10 kA)
≤ 2.8 kV (at 20 kA)
≤ 3.1 kV (at 30 kA)
≤ 3.6 kV (at 40 kA)
Response time tA≤ 25 ns
Insulation resistance Riso> 5 GΩ (at 500 V DC)

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque3 Nm (1,5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
Stripping length16 mm
Conductor cross section flexible1.5 mm² ... 25 mm²
Conductor cross section solid1.5 mm² ... 35 mm²
Conductor cross section AWG15 ... 2
Connection methodFork-type cable lug
Conductor cross section flexible1.5 mm² ... 16 mm²

UL specifications

SPD Type1
Maximum continuous operating voltage MCOV800 V DC
Nominal voltage800 V DC
Mode of protection(L+) - (L-)
(L+) - G
(L-) - G
Power distribution systemDC PV
Voltage protection rating VPR2 kV
Nominal discharge current In20 kA
Short-circuit current rating (SCCR)50 kA

UL connection data

Conductor cross section AWG10 ... 2
Tightening torque30 lbf-in.

Standards and Regulations

Standards/regulationsEN 50539-11 2013

Classifications


ETIM for 2801163 Earthing, lightning and surge protection (EC000381)
Feature Name Feature Value
System configuration DC (EF009926) Yes
System configuration IT (EF009927) No
System configuration TN (EF009928) No
System configuration TN-C (EF009929) No
System configuration TN-C-S (EF009933) No
System configuration TN-S (EF009930) No
System configuration TT (EF009931) No
System configuration other (EF009932) No
Lightning impulse current (10/350 µs) (EF000421) 5 kA
Nominal discharge surge current (8/20) (EF004214) 40 kA
Max. continuous voltage DC (EF004777) 720 V
Voltage protection level (DC+ - DC-) (EF009643) 2.6 kV
Voltage protection level (DC+/DC- - PE) (EF009644) 2.6 kV
Mounting method (EF000003) DIN rail (top hat rail) 35 mm
Construction size (EF002566) Other
Max. conductor cross section solid (solid, stranded) (EF008827) 35 mm²
Max. conductor cross section flexible (fine-strand) (EF008828) 25 mm²
Signalling at the device (EF004241) Optic
Category type 1 (EF004229) Yes
Degree of protection (IP) (EF005474) IP20

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.