Product successfully added to your shopping cart
MACX MCR-SL-CAC-5-I-UP
2810625
PHOENIX_CONTACT
1
Current transducers
Current converter for 1 A and 5 A AC, output signal 0...20 mA or 4...20 mA, configurable via DIP switch with LED service status signalling
Current measuring transducer for 1 A and 5 A AC, the output signal 0...20 mA or 4...20 mA, can be configured using a DIP switch with an operating mode indication through an LED
Sensors > Current value transformer
INTERFACE Components (IF)
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Utilization restriction | |
| EMC note | EMC: class A product, see manufacturer's declaration in the download area |
| Product type | Current transducer |
| Data management status | |
| Article revision | 14 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Maximum power dissipation for nominal condition | < 0.9 W (24 V DC) |
| < 3.4 W (230 V AC) | |
| Protective circuit | Surge protection; 35 V suppressor diode |
| Step response (10-90%) | ≤ 300 ms |
| 200 ms | |
| Maximum temperature coefficient | < 0.02 %/K |
| Temperature coefficient, typical | < 0.015 %/K |
| Maximum transmission error | ≤ 0.5 % (of nominal range value under nominal conditions) |
| Reverse polarity protection | yes |
| Rated insulation voltage | 300 V AC (to earth) |
| Electrical isolation Input/output | |
| Test voltage | 4 kV AC (50 Hz, 60 s) |
| Electrical isolation Output/supply | |
| Test voltage | 2 kV AC (50 Hz, 60 s) |
| Supply | |
| Supply voltage range | 19.2 V AC/DC ... 253 V AC/DC |
| Max. current consumption | < 33 mA (24 V DC) |
| Power consumption | < 0.8 W (24 V DC) |
| Measurement | |
| Configurable/programmable | Via DIP switches |
| Input current range | 0 A AC ... 1 A AC (configurable) |
| 0 A AC ... 5 A AC (configurable) | |
| Voltage input signal | ≤ 300 V AC |
| Input impedance | < 50 mΩ |
| Overload capacity | 2 x IN (continuous) |
| Surge strength | 20 x IN(1 s) |
| Nominal frequency fN | 50 Hz |
| Frequency measuring range | 45 Hz ... 65 Hz |
| Curve type | Sine |
| Signal: Current | |
| Configurable/programmable | Via DIP switches |
| Non-load voltage | 15 V |
| Current output signal | 0 mA ... 20 mA (configurable) |
| 4 mA ... 20 mA (configurable) | |
| Max. current output signal | 25 mA |
| Load/output load current output | < 500 Ω (20 mA) |
| Ripple | < 10 mVPP(500 Ω / 20 mA) |
| Status display | LED red (error), LED green (ready) |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Data communication (bypass) | |
| Limit frequency (3 dB) | approx. 3 Hz |
| Item dimensions | |
| Width | 22.5 mm |
| Height | 104 mm |
| Depth | 114.5 mm |
| Color | gray (RAL 7042) |
| Housing material | Polyamide PA non-reinforced |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -20 °C ... 65 °C |
| -4 °F ... 149 °F | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C (-40 °F ... 185 °F) |
| Altitude | ≤ 2000 m |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| CE | |
| Certificate | CE-compliant |
| ATEX | |
| Identification | II 3 G Ex nA IIC T4 Gc X |
| UKCA Ex (UKEX) | |
| Identification | II 3 G Ex nA IIC T4 Gc |
| Certificate | PxCIF21UKEX2810638X |
| UL, USA/Canada | |
| Identification | UL 508 Recognized |
| EAC Ex | |
| Identification | 2Ex nA IIC T4 Gc |
| Certificate | BY/112 02.01 TP012 103.01 00078 |
| Electromagnetic compatibility | Conformance with EMC directive |
| Noise immunity | EN 61000-6-2 |
| Note | When being exposed to interference, there may be minimal deviations. |
| Noise emission | EN 61000-6-4 |
| Electrostatic discharge | |
| Standards/regulations | EN 61000-4-2 |
| Electromagnetic HF field | |
| Standards/regulations | EN 61000-4-3 |
| Electromagnetic HF field | |
| Comments | Criterion A |
| Fast transients (burst) | |
| Standards/regulations | EN 61000-4-4 |
| Fast transients (burst) | |
| Comments | Criterion B |
| Surge current load (surge) | |
| Standards/regulations | EN 61000-4-5 |
| Surge current load (surge) | |
| Comments | Criterion B |
| Conducted interference | |
| Standards/regulations | EN 61000-4-6 |
| Mounting type | DIN rail mounting |
| Mounting position | any |
| Feature Name | Feature Value |
|---|---|
| Initial value measuring range current (EF008198) | 0 A |
| End value measuring range current (EF008266) | 1 A |
| Frequency rated current (EF005737) | 50 Hz |
| Type of analogy output (EF003958) | 4-20 mA |
| Integrated configuration function (EF003064) | No |
| With switching output (EF005225) | No |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOG PHOENIX INTERFACE TECHNOLOGY AND SWITCHING DEVICES EN.pdf | 29 Mbytes |
|
| PHOENIX CONTACT-2810625-MACX MCR-SL-CAC- 5-I-UP | 144 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.