Product successfully added to your shopping cart
PSR-PC40-2NO-1DO-24DC-SC
2700588
PHOENIX_CONTACT
1
Coupling relay
Coupling relay for high and low demand applications SIL 3, couples digital output signals to the periphery, 2 trip circuits, 1 digital warning output, Safe-State-Off applications, test pulse filter, plug-in screw terminal block
Coupling relay for SIL 3 high- and low-demand applications, couples digital output signals to the I/O, 2 enabling current paths, 1 digital signal output, safe state off applications, test pulse filter, plug-in screw terminal block
Relays > Device for monitoring of safety-related circuits
Safety
Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Note on application | |
| Note on application | Only for industrial use |
| Utilization restriction | |
| CCCex note | Use in potentially explosive areas is not permitted in China. |
| Product type | Coupling relay |
| Product family | PSRmini |
| Application | Safe switch off |
| High demand | |
| Low demand | |
| Ex | |
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
| Data management status | |
| Article revision | 07 |
| Times | |
| Typ. starting time with Us | < 200 ms (when controlled via A1, automatic start) |
| Typical release time | < 35 ms (when controlled via A1) |
| Recovery time | 500 ms |
| Maximum power dissipation for nominal condition | 5.5 W (IL² = 60 A²) |
| Nominal operating mode | 100% operating factor |
| Air clearances and creepage distances between the power circuits | |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage/insulation | Safe isolation, 6 kV reinforced insulation from control circuit, start circuit, signal output to the enabling current paths, 4 kV/basic insulation between the enabling current paths and between all current paths and housing |
| Supply | |
| Designation | A1/A2 |
| Rated control circuit supply voltage US | 20.4 V DC ... 26.4 V DC |
| Rated control circuit supply voltage US | 24 V DC -15 % / +10 % (A1/A2) |
| Rated control supply current IS | typ. 75 mA (depending on load M1 +100 mA) |
| Power consumption at US | typ. 1.8 W |
| Inrush current | typ. 400 mA (Δt s) |
| Filter time | max. 2 ms (at A1-A2; test pulse width) |
| ≥ 100 ms (at A1-A2; test pulse rate) | |
| Protective circuit | Serial protection against polarity reversal; 33 V suppressor diode |
| Digital: Start circuit (Y1, Y2) | |
| Number of inputs | 2 (Non-safety-related start inputs: Y1/Y2) |
| Inrush current | < 10 mA |
| Max. permissible overall conductor resistance | 150 Ω |
| Voltage at input/start and feedback circuit | 24 V DC -15 %; +10 % |
| Current consumption | < 5 mA |
| Relay: Enabling current paths (13/14, 23/24) | |
| Output description | 2 NO contacts each in series, without delay, floating |
| Number of outputs | 2 (safety-related N/O contacts: 13/14, 23/24) |
| Contact switching type | 2 enabling current paths |
| Contact material | AgSnO2 |
| Switching voltage | min. 12 V AC/DC |
| max. 250 V AC/DC (Observe the load curve) | |
| Switching capacity | min. 60 mW |
| Inrush current | min. 3 mA |
| max. 6 A | |
| Switching capacity in accordance with IEC 60947-5-1 | 4 A (24 V (DC13)) |
| 5 A (250 V (AC15)) | |
| Limiting continuous current | 6 A (High demand) |
| 4 A (Low demand) | |
| Sq. Total current | 60 A2(observe derating) |
| Switching frequency | max. 0.5 Hz |
| Mechanical service life | 10x 106cycles |
| Output fuse | 6 A gL/gG |
| 4 A gL/gG (for low-demand applications) | |
| Signal: M1 | |
| Output description | PNP |
| Number of outputs | 1 (non-safety-related) |
| Voltage | approx. 22 V DC (Us- 2 V) |
| Current | max. 100 mA |
| Maximum inrush current | 500 mA (Δt = 1 ms at Us) |
| Short-circuit protection | no |
| Output fuse | 150 mA fast blow |
| Connection technology | |
| pluggable | yes |
| Conductor connection | |
| Connection method | Screw connection |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section AWG | 24 ... 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Status display | 2 x LED (green) |
| Operating voltage display | 1 x yellow LED |
| Error indication | 1 x LED (red) |
| Width | 12.5 mm |
| Height | 112.2 mm |
| Depth | 114.5 mm |
| Color (Housing) | yellow (RAL 1018) |
| Housing material | Polyamide |
| Safety data | |
| Stop category | 0 |
| Safety data: EN 50156 | |
| Safety Integrity Level (SIL) | 3 |
| Safety data: IEC 61508 - High demand | |
| Safety Integrity Level (SIL) | 3 |
| Safety data: IEC 61508 - Low demand | |
| Safety Integrity Level (SIL) | 3 |
| Ambient conditions | |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Ambient temperature (operation) | -40 °C ... 70 °C (observe derating) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Shock | 15g |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g |
| ATEX | |
| Identification | II 3G Ex ec nC IIC T4 Gc |
| Certificate | UL 22 ATEX 2912X |
| IECEx | |
| Identification | Ex ec nC IIC T4 Gc |
| Certificate | IECEx UL 22.0037X |
| UL, USA/Canada | |
| Identification | cULus |
| Certificate | E140324 |
| UL Ex, USA / Canada | |
| Identification | Class I, Zone 2, AEx nA nC IIC T4 / Ex nA nC IIC Gc T4 X |
| Class I, Div. 2, Groups A, B, C, D, T4 | |
| Certificate | E360692 |
| CE | |
| Identification | CE-compliant |
| Environmental simulation test | |
| Identification | G3 |
| Certificate | ISA-S71.04 |
| CCC / China-Ex | |
| Identification | Ex ec nC IIC T4 Gc |
| Certificate | 2022122304115695 |
| DNV | |
| Identification | C, EMC2 |
| Certificate | 11253-14 HH |
| Air clearances and creepage distances between the power circuits | |
| Standards/regulations | EN 60664-1, EN 60079-7, EN 60079-15 |
| Mounting type | DIN rail mounting |
| Assembly note | See derating curve |
| Mounting position | vertical, horizontal, with front of module upward |
| Feature Name | Feature Value |
|---|---|
| Model (EF000010) | Basic device |
| Suitable for rail mounting (EF003972) | Yes |
| With detachable clamps (EF003340) | Yes |
| Type of electric connection (EF003961) | Screw connection |
| Suitable for monitoring of emergency-stop circuits (EF007268) | No |
| Suitable for monitoring of valves (EF007272) | No |
| Suitable for monitoring of optoelectronic protection equipment (EF007269) | No |
| Suitable for monitoring of tactile sensors (EF007271) | No |
| Suitable for monitoring of magnetic switches (EF007266) | No |
| Suitable for monitoring of proximity switches (EF007267) | No |
| Evaluation inputs (EF008245) | Other |
| With start input (EF003342) | No |
| With muting function (EF004057) | No |
| With feedback circuit (EF003343) | No |
| Release-delay (EF001129) | 0.2 s |
| Number of outputs, safety related, undelayed, with contact (EF003344) | 0 |
| Number of outputs, safety related, delayed, with contact (EF003345) | 0 |
| Number of outputs, safety related, undelayed, semiconductors (EF003346) | 0 |
| Number of outputs, safety related, delayed, semiconductors (EF003347) | 0 |
| Number of outputs, signalling function, undelayed, with contact (EF003348) | 0 |
| Number of outputs, signalling function, delayed, with contact (EF003349) | 0 |
| Number of outputs, signalling function, undelayed, semiconductors (EF003350) | 0 |
| Number of outputs, signalling function, delayed, semiconductors (EF003351) | 0 |
| Stop category according to IEC 60204 (EF007498) | Other |
| With approval for BG BIA (EF004145) | No |
| With approval according to UL (EF001783) | No |
| Width (EF000008) | 12.5 mm |
| Height (EF000040) | 112.2 mm |
| Depth (EF000049) | 114.5 mm |
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE AUTOMATION PHOENIX EN.pdf | 35 Mbytes |
|
| PHOENIX CONTACT-2700588-PSR-PC40-2NO-1DO-24DC-SC | 123 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.