Product successfully added to your shopping cart
PSR-SCP- 24DC/URD3/4X1/2X2/3
2981732
PHOENIX_CONTACT
1
Extension module
Safety
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Orderkey | 2981732 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 265 (C-6-2017) |
GTIN | 4046356103695 |
Weight per Piece (excluding packing) | 234.850 g |
Custom tariff number | 85371098 |
Country of origin | DE (Germany) |
Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
---|
Ambient temperature (operation) | -20 °C ... 55 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 70 °C |
Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
Maximum altitude | max. 2000 m (Above sea level) |
Rated control circuit supply voltage US | |
---|---|
Nominal input voltage UN | 24 V DC |
Input voltage range in reference to UN | 0.85 ... 1.1 |
Typical input current at UN | 84 mA |
Typical response time | 20 ms |
Typical release time range | 0.3 s ... 3 s +50 % (adjustable) |
Recovery time | 1 s |
Operating voltage display | Green LED |
Status display | Green LED |
Protective circuit | Fuse PTC resistor |
Surge protection Suppressor diode |
Contact type | 4 delayed enabling current paths |
---|---|
1 delayed signaling current path | |
1 delayed confirmation current path | |
Contact material | AgSnO2 |
Maximum switching voltage | 250 V AC/DC |
Minimum switching voltage | 15 V AC/DC |
Limiting continuous current | 6 A (N/O contact) |
3 A (N/C contact) | |
Maximum inrush current | 6 A (N/O contact) |
3 A (N/C contact) | |
Inrush current, minimum | 25 mA |
Sq. Total current | 50 A2(ITH2= I12+ I22+ I32+ I42) |
Interrupting rating (ohmic load) max. | 144 W (24 V DC, τ = 0 ms, N/C contact 65/66: 72 W) |
288 W (48 V DC, τ = 0 ms, N/C contact 65/66: 144 W) | |
77 W (110 V DC, τ = 0 ms) | |
88 W (220 V DC, τ = 0 ms) | |
1500 VA (250 V AC, τ = 0 ms, N/C contact 65/66: 750 VA) | |
Maximum interrupting rating (inductive load) | 48 W (24 V DC, τ = 40 ms) |
40 W (48 V DC, τ = 40 ms) | |
35 W (110 V DC, τ = 40 ms) | |
33 W (220 V DC, τ = 40 ms) | |
Switching capacity min. | 0.4 W |
Mechanical service life | approx. 107cycles |
Switching capacity (360/h cycles) | 6 A (24 V DC) |
5 A (230 V AC) | |
Output fuse | 10 A gL/gG NEOZED (N/O contact) |
4 A gL/gG NEOZED (N/C contact) |
Relay type | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
---|---|
Nominal operating mode | 100% operating factor |
Net weight | 234.85 g |
Mounting position | any |
Mounting type | DIN rail mounting |
Degree of protection | IP20 |
IP54 | |
Min. degree of protection of inst. location | IP54 |
Housing color | yellow |
Connection method | Screw connection |
---|---|
pluggable | Yes |
Conductor cross section solid min. | 0.2 mm² |
Conductor cross section solid max. | 2.5 mm² |
Conductor cross section flexible min. | 0.2 mm² |
Conductor cross section flexible max. | 2.5 mm² |
Conductor cross section AWG min. | 24 |
Conductor cross section AWG max. | 12 |
Stripping length | 7 mm |
Screw thread | M3 |
Stop category | 1 |
---|---|
Designation | IEC 61508 - High demand |
Safety Integrity Level (SIL) | 3 |
Designation | IEC 61508 - Low demand |
Safety Integrity Level (SIL) | 3 |
Designation | EN ISO 13849 |
Performance level (PL) | d |
Category | 3 |
Designation | EN 62061 |
Safety Integrity Level Claim Limit (SIL CL) | 3 |
Designation | Air clearances and creepage distances between the power circuits |
---|---|
Standards/regulations | DIN EN 50178/VDE 0160 |
Rated insulation voltage | 250 V |
Rated surge voltage/insulation | 4 kV / basic isolation (safe isolation, reinforced insulation and 6 kV between input circuit/N/C contacts and enabling current paths). |
Degree of pollution | 2 |
Overvoltage category | III |
China RoHS | Environmentally Friendly Use Period = 50 |
---|---|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Title: | Size: | Type: |
---|---|---|
PHOENIX CONTACT-2981732-PSR-SCP- 24DC/URD3/4X1/2X2/3 | 142 Kbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.