ANUNCIAR
C 25-B+C 0 5095603 OBO BETTERMANN Lightning current conductor choose N against PE, View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

C 25-B+C 0 5095603 OBO BETTERMANN Lightning current conductor choose N against PE,

C 25-B+C 0

5095603

OBO BETTERMANN

Lightning current conductor choose N against PE,

Plug-in arrester, total spark gap between N and PE 255 V. Plug-in total discharge gap for use between neutral lines (N) and protector (PE) Suitable for use in combination with: • CombiController, type V 25-B+C• SurgeController, type V 20-C• SurgeController, type V 10-C* Complete = Plug-in arrester and base

More details


Earthing, lightning and surge protection > Combined arrester for power supply systems

TBS Transient and lightning protection systems - OBO BETTERMANN > Surge protection, arrestor, type 1+2 (office and housing) - OBO BETTERMANN

Brand new product in its original packaging covered by the warranties and certifications provided by OBO BETTERMANN

Total: $49.51
Unit price: $49.51
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Often bought together

Best sellers

More info



Arrester surge current (8/20 µs) [total]30 kA
Blow-outno
CO2 Footprint (GWP) Cradle-to-Gate0,35 kg CO2e / 1 Piece
Conductor cross-section, rigid (single-wire/multiwire), max.35 mm²
Conductor cross-section, rigid (single-wire/multiwire), min.2,5 mm²
Dimension255V
Follow current quenching capacity (eff) [N-PE]0,1 kA
Installation typeOn basic element
Lightning protection zone LPZ0→2
Lightning surge current (10/350 μs)25 kA
Max. mains-side overcurrent protection160
Maximum back-up fuse160 A
Maximum continuous voltage AC255 V
Maximum discharge current (8/20 μs)50 kA
Network formOther
Nominal discharge current (8/20 µs)30 kA
Nominal discharge current (8/20 µs) [N-PE]30 kA
Nominal voltage AC (50/60 Hz)230 V
Operating temperature, max.80 °C
Operating temperature, min.-40 °C
Permitted temperature range, max.80 °C
Permitted temperature range, min.-40 °C
Pole versionN/PE
Protection ratingIP20
Remote signallingno
Response time<100 ns
Signalling on deviceNone
SPD to EN 61643-11Type 1+2
SPD to IEC 61643-1Class I+II
Version for1-pole cover; 255 V

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.