Standards
EN 61204, 2006/95/EC, 2004/108/EC, EN 50178, EN 60950, UL 60950, UL 508, SELV (EN 60950)
Degree of protectionEnclosures
IP20
Degree of protectionTerminals
IP20
Protection class
according to EN 61140, Class 1
Mounting
DIN rail (IEC/EN 60715), snap fixing
Mounting position
Horizontal
Heat dissipation
part no. ≦ 29 W
Minimum distance to adjacent devices
horizontal 10, vertical 80 mm
Only operate plug-in terminals off load.
Input circuitFlexible with ferrule
0.2…2.5 (22…14 AWG) mm2
Input circuitFlexible without ferrule
0.2…2.5 (22…14 AWG) mm2
Input circuitMassive
0.2…2.5 (22…14 AWG) mm2
Output circuitFlexible with ferrule
0.12…2.5 (26…14 AWG) mm2
Output circuitFlexible without ferrule
0.12…2.5 (26…14 AWG) mm2
Output circuitMassive
0.12…2.5 (26…14 AWG) mm2
Environmental compatibility
Ambient temperature, operation
-25 - +70 °C
Ambient temperature, full load
0 - +60 (without derating) °C
Ambient temperature, storage
- 40 - + 85 °C
Climatic proofing
to IEC 60068-2-3, 93% at +40 °C, no condensation
Overvoltage category/pollution degree
according to EN 50178; 2
Climatic class (IEC)
according EN 60721; 3K3
Vibrations (IEC/EN 60068-2-6)
1…57 Hz, amplitude ±0.075 mm; 57…100 Hz, 5 g
Mechanical shock resistance (IEC 60068-2-27)
30 g all directions
Inputs/outputs
3 kV AC (type test), 1.2 kV AC (routine test)
Input
1.5 kV AC (type test), 1.2 kV AC (routine test)
Output
350 V AC (routine test)
Electromagnetic compatibility (EMC)
Interference immunity
EN 61000-6-2
ESD [Air/contact discharge]
according to EN 61000-4-2, level 4-8KV/15KV kV
RFI
according to EN 61000-4-3, level 3-10 V/m
Burst
according to EN 61000-4-4, level 4-4 KV
Surge
according to EN 61000-4-5, level 4-2KV symmetrical, Level 3-3KV asymmetrical
cable-born HF
according to EN 61000-4-6, level 3-10 V
Emitted interference
EN 61000-6-3
Electromagnetic fields [(0.08…1) / (1,4…2) / (2…2,7) GHz ]
according to EN 55022, Class B V/m
Cable-born HF
according to EN 55022, Class B
Supply frequencyRated value
50/60 Hz
Supply frequencyRange
47 - 63 Hz
Current consumptionAt 110 … 240 V AC
Approx. 3.5…1.6 A
Power consumption
Normally 269 W
Inrush current limiter/i2t (cold start)
≦ 33 A / ca. 0.2 A2s
Mains failure bridging
typ. ≧ 40 ms
Run-up time after mains voltage applied
Normally ≧ 5 ms
Transient overvoltage protection
Varistors
Internal input fuse (device protection, not accessible)
6.3 AT
Discharge current to PE
< 3.5 mA mA
L+, L+, L-, L-
Proof against short-circuit, no-load and overload
Rated output current Tu≦ 60 °C
10 A
Peak output current (power reserves) Tu ≦ 40 °C
Normally ≦ 12.25 A
Derating 60 °C ≦ Tu≦ 70 °C
2.5 % per Kelvin temperature increase
Control deviation atLoad change 10…90 %, static
±0.05 % Normally
Control deviation atLoad change 10…90 %, dynamic
±3 % Normally
Control deviation atController acting time
Normally 1 ms
Control deviation atInput voltage deviation ±10 %
Normally ±0.05 %
Control deviation atRise time 10…90 %
Normally ≦ 4 ms
Residual ripple and switching peaks
20 MHz typically < 50 mVss
Can be switched in parallel
yes, up to 5 devices for redundancy and for power increase, non symetrical current
Series connection capability
yes, for voltage increase (max. 2 off)
Resistance to reverse feed
yes, limited to approx. 35 V AC
Power factor correction (PFC)
Yes
Status indication
OUTPUT OK: LED green
Overload characteristics
→ AWA2727-2318 (www.moeller.net/support)
Behaviour on short-circuit
continuously with current limitation
Current limitation at short-circuit
Approx. 19 A
Short-circuit protection
Proof against sustained short circuit
Overload protection
thermal protection
Capacitive load starting
Not restricted
At U ≧ 264 V DC additionally suitable, use external fuse.