EU1E-SWD-1CX 174721 EATON ELECTRIC SWD T-Connector counter module IP69K, one counter input with power supply.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

EU1E-SWD-1CX 174721 EATON ELECTRIC SWD T-Connector counter module IP69K, one counter input with power supply..

EU1E-SWD-1CX

174721

EATON-MOELLER

SWD T-Connector counter module IP69K, one counter input with power supply, M12 I/O socket

EU1E-SWD-1CX

More details


PLC's > PLC function/technology module

Smartwire Darwin

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $208.59
Unit price: $208.59

Quantity Price
1+$208.59
2+$180.84
3+$173.80
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



EL-Nummer (Norway)
4560906
SWD T-Connector counter module IP69K, one counter input with power supply, M12 I/O socket
SmartWire-DT module with IP67 degree of protection for connecting one digital meter; 24 VDC, 70 mA short-circuit proof power supply for counter; automatic address setting; 24 VDC simple counter, incremental encoder (A, B, R) with X1, X2, X4 encoding; Up/Down Counter up to 30 kHz; counter connection with M12 socket

Delivery program

Product range
SmartWire-DT slave
Basic function
Counter module
Function
For connecting a counter
Short Description
Counter/incremental encoder 24 V DC, max. 30 kHz
Inputs
meter
1
Connection to SmartWire-DT
yes

Technical data

General
Standards
IEC/EN 61131-2
ApprovalsApprovals
UL
CSA
Dimensions (W x H x D)
85.6 x 56.9 x 20.1 mm
Weight
0.07 kg
Mounting
DIN-rail, screw fixing (M4), mounting section (Clip M20)
Mounting position
As required
24 V DC supply for output supply
Power supplyPower loss [P]
1.4 W
Climatic environmental conditions
Climatic proofing
Dry heat to IEC 60068-2-2
Damp heat as per EN 60068-2-3
Air pressure (operation)
795 - 1080 hPa
Ambient temperatureOperation [ϑ]
-25 - +70 °C
Ambient temperatureStorage / Transport [ϑ]
-40 - +70 °C
Relative humidityCondensation
permissible
Relative humidityRelative humidity, non-condensing (IEC/EN 60068-2-30)
5 - 95 %
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP69K
Vibrations (IEC/EN 61131-2:2008)Constant amplitude 3,5 mm
5 - 8.4 Hz
Vibrations (IEC/EN 61131-2:2008)Constant acceleration 1 g
8.4 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 30 g/11 ms
9 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
0.3 m
Electromagnetic compatibility (EMC)
Overvoltage category
II
Pollution degree
3
Electrostatic discharge (IEC/EN 61131-2:2008)Air discharge (Level 3)
8 kV
Electrostatic discharge (IEC/EN 61131-2:2008)Contact discharge (Level 2)
4 kV
Electromagnetic fields (IEC/EN 61131-2:2008)80 - 1000 MHz
10 V/m
Electromagnetic fields (IEC/EN 61131-2:2008)1.4 - 2 GHz
3 V/m
Electromagnetic fields (IEC/EN 61131-2:2008)2 - 2.7 GHz
1 V/m
Radio interference suppression (SmartWire-DT)
EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)Supply cable
2 kV
Burst (IEC/EN 61131-2:2008, Level 3)Signal lines
1 kV
Burst (IEC/EN 61131-2:2008, Level 3)SmartWire-DT cables
1 kV
Surge (IEC/EN 61131-2:2008, Level 1)Surge power cables
0.5 kV
Surge (IEC/EN 61131-2:2008, Level 1)Surge I/O cables
1 kV
Radiated RFI (IEC/EN 61131-2:2008, Level 3)
10 V
SmartWire-DT network
Station type
SmartWire-DT slave
Setting the baud rate
automatic
Baud rate (data transfer speed)
maximum2000 kbps
Status SmartWire-DT
Green LED
SWD-IN
M12 plug (A-keyed), 5 pole
SWD-OUT
M12 socket (A-keyed), 5 pole
Current consumption (24V, without sensor and without I/O supply)Current consumption (24 V SWD supply)
57 mA
Sensor supplyMax. current consumption per M12 I/O plug
70 mA
Sensor supplyOverload and short-circuit proof
yes, with diagnostics
Connection supply and I/O
Terminal for I/O sensorConnection type
5-pin M12 socket (A-keyed)
Counter inputs
Quantity
1
Input rated voltage
24 V DC
Counter input frequency
Max.30 kHz
Counter value
32 Bit
Incremental encoder functionEncoder inputs
A,B,reference
Incremental encoder functionEncoding
X1, X2, X4
Incremental encoder functionFrequency measurement
0-65535 Hz
Simple counter functionCounter inputs
Counter pulse, direction, reference mark
Simple counter functionEncoding
1.2-way
Simple counter functionFrequency measurement
0-65535 Hz
Counter status indicator
yellow LED
Potential isolation
Inputs for SmartWire-DT
No

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
0 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
1.4 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+70 °C
Degree of Protection
IP69K
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

PLC's (EG000024) / PLC function/technology module (EC001422)
Electric engineering, automation, process control engineering / Control / Programmable logic control (SPS) / SPS functional/technological module ([email protected] [AKE528014])
Number of functions
3
Redundancy
No
Suitable for counting
Yes
Suitable for weighting
No
Suitable for temperature control
No
Suitable for welding control
No
Suitable for pressure control
No
Suitable for NC
No
Function electronic positioning available
Yes
Suitable for CNC
No
Suitable for SSI
No
Suitable for incremental data detection
Yes
Suitable for detection absolute value
No
Flux controller possible
Yes
Suitable for flux measurement
No
Suitable for path controller
Yes
Suitable for cam controller
No
Suitable for flying saw
No
Suitable for multi-axis control
No
Single-axis controller possible
Yes
Suitable for multi-axis positioning
No
Single-axis positioning possible
Yes
Suitable for safety functions
No
Category according to EN 954-1
SIL according to IEC 61508
None
Performance level acc. EN ISO 13849-1
None
Appendant operation agent (Ex ia)
No
Appendant operation agent (Ex ib)
No
Explosion safety category for gas
None
Explosion safety category for dust
None
Width
85.6 mm
Height
56.9 mm
Depth
20.1 mm

Approvals

UL File No.
E170645
North America Certification
UL listed, CSA certified
Specially designed for North America
No

Dimensions

2723DIM-37
SmartWire-DT I/O modules (IP67) EU1E-SWD-…
2723DRW-112
① SmartWire-DT connection SWD IN
② SmartWire-DT connection SWD OUT
③ SmartWire-DT diagnostics LED
④ I/O connection X1
⑤ status display

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.