Standards
EN 61000-6-1/-2/-3/-4, IEC 60068-2-6, IEC 60068-2-27
Dimensions (W x H x D)
75 x 58 x 36.2 mm
Mounting
Fitted onto the fixing shaft of the display
Power supplySolid
0.5 - 2.5 (AWG 20 - 14) mm2
Power supplyflexible with ferrules
0.5 - 1.5 (AWG 20 - 16) mm2
Power supplyStandard screwdriver
3.5 x 0.6 mm
Data cableSolid
0.2 - 0.5 (AWG 24 - 20) mm2
Climatic environmental conditions
Operating ambient temperature
-25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation
Take appropriate measures to prevent condensation
Relative humidity, non-condensing (IEC/EN 60068-2-30)
5 - 95 %
Air pressure (operation)
795 - 1080 hPa
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
Vibrations (IEC/EN 60068-2-6)Constant amplitude 0.15 mm
10 - 57 Hz
Vibrations (IEC/EN 60068-2-6)Constant acceleration 2 g
150 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms
18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height]
50 mm
Free fall, packaged (IEC/EN 60068-2-32)
1 m
Mounting position
Vertical or horizontal
Electromagnetic compatibility (EMC)
Overvoltage category/pollution degree
II/2
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)Air discharge
8 kV
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3
10 V/m
Radio interference suppression
EN 55011 Class B, EN 55022 Class B
Burst Impulse (IEC/EN 61000-4-4, Level 3)Supply cable
2 kV
Burst Impulse (IEC/EN 61000-4-4, Level 3)Signal lines
2 kV
Power pulses (surge) (IEC/EN 61000-4-5)
2 (supply cables, symmetrical) kV
power pulses (surge) (IEC/EN 61000-4-5, level 2)
1 (supply cables, symmetrical) kV
Immunity to line-conducted interference to (IEC/EN 61000-4-6)
10 V
Clearance in air and creepage distances
EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance
EN 50178
Rated operational voltage [Ue]
24 DC (-15⁄+20 %) V
Admissible rangeMin. admissible range
20.4 V DC
Admissible rangeMax. addmissible range
28.8 V DC
Input currentat 24 V DC
Normally 185 mA
Power loss [P]
Normally 1.5 W
Note on heat dissipation
Current consumption at 24 V DC
CANopen®Control contact rated current
to DS301V4
CANopen®PDO type
asynchronous (event controlled)
CANopen®Addresses
1 to 63, can be set through display
CANopen®Baud rate/length
10 kByte up to 1 MByte,
Automatic detection
Manual setting via display possible. kBd
CANopen®Connection technique
6-pole cage clamp terminal
CANopen®Terminating resistor
external 120 Ω