Product name
Eaton XIOC Communication module
Product Length/Depth
100 millimetre
Product height
95 millimetre
Product width
30 millimetre
Product weight
0.145 kilogram
Certifications
UL508
CSA Class No.: 2252-01
CSA-C22.2 No. 0-M
CSA File No.: 012528
UL Category Control No.: NRAQ
UL
UL File No.: E135462
CSA-C22.2 No. 142-M
CSA
CE
EN 50178
IEC/EN 61131-2
Product Type
Communication module
Fitted with:
Potential separation
Functions
Master (Class 1)
PROFIBUS-DP interface
Current consumption
300 mA, Interfaces
300 mA (Ie), Interfaces
Resistance
500 g/⌀ 50 mm ±25 g (impact resistance)
Type
Communication module
PROFIBUS-DP master module
Used with
XC100/200 (expandable with up to 15 XI/OC modules)
Ambient conditions, mechanical
Shock resistance
15 g, Mechanical, Shock duration 11 ms
Vibration resistance
10 - 57 Hz, ± 0.075 mm
57 - 150 Hz ± 1.0 mm
Climatic environmental conditions
Ambient operating temperature - min
0 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-20 °C
Ambient storage temperature - max
70 °C
Electro magnetic compatibility
Emitted interference
Class A (according to DIN/EN 55011/22)
Terminals
Optionally, screw terminals or spring-loaded terminals for digital/analog modules
Rated operational voltage
24 (12) V DC
Supply voltage
20.4 – 28.8 (11.8 – 14.4) V DC, Admissible range, Power supply
Supply voltage at DC - max
5 V
Bus termination
Switchable
Data transfer rate
93.75 kBit/s with 1200 m
9.6 - 12000 kBit/s
500 kBit/s with 400 m
1500 kBit/s with 200 m
Transmit data: 3500 Byte
9.6 kBit/s with 1200 m
3000 kBit/s with 100 m
19.2 kBit/s with 1200 m
12000 kBit/s with 100 m
187.5 kBit/s with 1000 m
6000 kBit/s with 100 m
Receive data: 3500 Bytes
Interfaces
PROFIBUS DP, RS485, EN 50170 (built-in)
Max. 244 Bytes per slave (Inputs/outputs)
LED indicator
Status indication of Bus diagnostics: LED
Number of modules
3 (XC200)
124 (slaves)
1 (XC100)
Plug type
9-pole SUB-D socket
Explosion safety category for dust
None
Explosion safety category for gas
None
Potential isolation
Interfaces: yes
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
7.2 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Meets the product standard's requirements.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.