MSC-DM-0,4-M7(24VDC)/MSFA 191103 XTSCP40B007BMTDNL-FS EATON ELECTRIC DOL starter no alimentador placa de sis.. Ver maior
As imagens são só a título ilustrativo. Por favor, consulte a ficha técnica.

MSC-DM-0,4-M7(24VDC)/MSFA 191103 XTSCP40B007BMTDNL-FS EATON ELECTRIC DOL starter no alimentador placa de sis..

MSC-DM-0,4-M7(24VDC)/MSFA

191103

Y7-191103

EATON-MOELLER

DOL starter no alimentador placa de sistema, de 3 pólos, 0,09 kW/400 V/AC-3, 100 kA, operado DC

Acionador de partida de motor direto no sistema de alimentação; 3 pólos; 0.09 kW / 400 V / AC-3; 100 kA; 24 V DC

Eaton Moeller® series MSC-DM DOL starter, 380 V 400 V 415 V: 0.09 kW, Ir= 0.25 - 0.4 A, 24 V DC, DC voltage MSC-DM-0,4-M7(24VDC)/MSFA

Mais detalhes


Disjuntores de baixa tensão > Combinação de acionador de partida de motor/motor de arranque

Chaves de proteção do motor

* Produto novo em sua embalagem original com todas as garantias e certificações de EATON-MOELLER

Preço total: $148.61
Preço unitário: $148.61

Quantidade Preço
1+$148.61
2+$142.91
*Este preço é por unidade e mostra o valor líquido (excluindo impostos indirectos se aplicável).

Se o nosso preço não é o melhor, peça-nos uma cotação Solicitar uma cotação

Best sellers

Mais informação



General specifications

Product Name
Eaton Moeller® series MSC-DM DOL starter
Catalog Number
191103
EAN
4015081916016
Product Length/Depth
115 mm
Product Height
180 mm
Product Width
45 mm
Product Weight
0.724 kg
Certifications
UL 508 (on request)
CSA-C22.2 No. 14 (on request)
Model Code
MSC-DM-0,4-M7(24VDC)/MSFA

Funcionalidades e Funções

Fitted with:
Short-circuit release
Functions
Temperature compensated overload protection

Geral

Class
CLASS 10 A
Connection
Screw terminals
Connection to SmartWire-DT
No
Coordination type
2
Degree of protection
IP20
NEMA Other
Model
IEC starter
Mounting method
Motor starter Feeder System
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
1
Overload release current setting - min
0.25 A
Overload release current setting - max
0.4 A
Overvoltage category
III
Pollution degree
3
Rated impulse withstand voltage (Uimp)
6000 V AC
Suitable for
Also motors with efficiency class IE3
Type
Starter with Bi-Metal release
Voltage type
DC

Condições meteorológicas

Altitude
Max. 2000 m
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C

Classificação elétrica

Rated operational current (Ie)
0.31 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
0.4 A
Rated operational power at AC-3, 220/230 V, 50 Hz
0.06 kW
Rated operational power at AC-3, 380/400 V, 50 Hz
0.09 kW
Rated operational voltage
230 - 415 V AC

Classificação de curto-circuito

Rated conditional short-circuit current (Iq), type 2, 380 V, 400 V, 415 V
50000 A
Short-circuit release (Irm) - max
6.2 A

Sistema magnético

Power consumption (sealing) at DC
2.6 W
Rated control supply voltage (Us) at AC, 50 Hz - min
0 V
Rated control supply voltage (Us) at AC, 50 Hz - max
0 V
Rated control supply voltage (Us) at AC, 60 Hz - min
0 V
Rated control supply voltage (Us) at AC, 60 Hz - max
0 V
Rated control supply voltage (Us) at DC - min
24 V
Rated control supply voltage (Us) at DC - max
24 V

Verificação do design

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Datasheet - PDF

Avaliações: (0)

Não há comentários do produto ainda.

Adicionar avaliação
ocultar formulário
Avaliação:
Nome:
Email:
Título:
Opinión:
  Captcha
  Adicionar avaliação

Todas as classificações que recebemos a partir dos itens que oferecemos são reais e verificadas. Um pequeno gesto, mas muito valioso. Então, obrigado por esse minuto você gasta em deixar-nos a sua opinião e classificação de produtos, porque nos ajuda a continuar a melhorar e oferecer maior qualidade de serviço.