SIPLUS ET 200SP CPU 1512SP-1 PN -40...+60°C with conformal coating based on 6ES7512-1DK01-0AB0 . CPU 1512SP-1 PN for ET 200SP, Central processing unit with Work memory 200 KB for program and 1 MB for data, first interface: PROFINET IRT with 3-port switch, 48 ns bit performance, SIMATIC Memory Card required, BusAdapter required for port 1 and 2
SIPLUS ET 200SP -40...+60 ° C temp. boot: -25 ° C with coating formed based on 6ES7512-1DK01-0AB0 . CPU 1512SP-1 PN for ET 200SP, CPU with working memory 200 KB for program and 1 MB for data, 1. INTERFACE: PROFINET IRT with 3 port-switch, 48 ns execution instrucc. binary, necessary SIMATIC Memory Card, bus adapter required to port1 and 2
AUTOMATION SYSTEMS > SIPLUS Extreme (LOGO, S7-1200, S7-1500, etc)
Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Value | Unit | |
|---|---|---|
| Type of electric connection (EF003961) | - | |
| Number of HW-interfaces USB (EF003025) | - | |
| Category according to EN 954-1 (EF006782) | - | |
| Max. input current DC (EF007362) | - | A |
| Number of slots (EF003077) | - | |
| Supporting protocol for TCP/IP (EF003050) | - | |
| With potential separation (EF003272) | - | |
| With integrated power supply (EF003338) | - | |
| Input voltage at AC 50 Hz (EF007118) | ['-', '-'] | V |
| Input voltage at AC 60 Hz (EF007119) | ['-', '-'] | V |
| Input voltage at DC (EF007120) | ['19.2', '28.8'] | V |
| Type of voltage (input voltage) (EF003033) | DC | |
| Max. input current AC 50 Hz (EF007360) | - | A |
| Max. input current AC 60 Hz (EF007361) | - | A |
| Output voltage at AC 50 Hz (EF006999) | ['-', '-'] | V |
| Output voltage at AC 60 Hz (EF007000) | ['-', '-'] | V |
| Output voltage at DC (EF007001) | ['-', '-'] | V |
| Type of output voltage (EF008222) | - | |
| Max. output current AC 50 Hz (EF007351) | - | A |
| Max. output current AC 60 Hz (EF007352) | - | A |
| Max. output current DC (EF007353) | - | A |
| Number of HW-interfaces industrial Ethernet (EF003020) | 1 | |
| Number of interfaces PROFINET (EF006932) | 1 | |
| Number of HW-interfaces RS-232 (EF003021) | 0 | |
| Number of HW-interfaces RS-422 (EF003022) | 0 | |
| Number of HW-interfaces RS-485 (EF003023) | 1 | |
| Number of HW-interfaces serial TTY (EF003024) | 0 | |
| Number of HW-interfaces parallel (EF003026) | 0 | |
| Number of HW-interfaces Wireless (EF006933) | 0 | |
| Number of HW-interfaces other (EF003027) | 0 | |
| With optical interface (EF003028) | true | |
| Supporting protocol for PROFIBUS (EF003052) | true | |
| Supporting protocol for CAN (EF003053) | false | |
| Supporting protocol for INTERBUS (EF003054) | false | |
| Supporting protocol for ASI (EF003051) | false | |
| Supporting protocol for KNX (EF003055) | false | |
| Supporting protocol for Modbus (EF003057) | true | |
| Supporting protocol for Data-Highway (EF003058) | false | |
| Supporting protocol for DeviceNet (EF003059) | false | |
| Supporting protocol for SUCONET (EF003060) | false | |
| Supporting protocol for LON (EF003017) | false | |
| Supporting protocol for SERCOS (EF006657) | false | |
| Supporting protocol for PROFINET IO (EF007525) | true | |
| Supporting protocol for PROFINET CBA (EF007524) | false | |
| Supporting protocol for Foundation Fieldbus (EF007522) | false | |
| Supporting protocol for EtherNet/IP (EF007521) | false | |
| Supporting protocol for AS-Interface Safety at Work (EF007519) | false | |
| Supporting protocol for DeviceNet Safety (EF007520) | false | |
| Supporting protocol for INTERBUS-Safety (EF006662) | false | |
| Supporting protocol for PROFIsafe (EF007526) | false | |
| Supporting protocol for SafetyBUS p (EF007527) | false | |
| Supporting protocol for other bus systems (EF003062) | false | |
| Radio standard Bluetooth (EF007178) | false | |
| Radio standard WLAN 802.11 (EF007179) | false | |
| Radio standard GPRS (EF008523) | false | |
| Radio standard GSM (EF008524) | false | |
| Radio standard UMTS (EF008525) | false | |
| IO link master (EF007298) | false | |
| System accessory (EF004118) | true | |
| Degree of protection (IP) (EF005474) | IP20 | |
| With pluggable modules, digital I/O (EF003078) | true | |
| With pluggable modules, analogue I/O (EF003079) | true | |
| With pluggable modules, communication modules (EF003080) | true | |
| With pluggable modules, function and technology modules (EF003081) | true | |
| With pluggable modules, central modules (EF003082) | true | |
| With pluggable modules, others (EF003083) | true | |
| Fieldbus connection over separate bus coupler possible (EF004002) | true | |
| With bus coupler for modular station connection (EF003990) | true | |
| Rail mounting possible (EF003972) | true | |
| Wall mounting/direct mounting (EF007020) | true | |
| Front build in possible (EF007016) | - | |
| Rack-assembly possible (EF007018) | - | |
| Suitable for safety functions (EF001597) | false | |
| SIL according to IEC 61508 (EF009889) | None | |
| Performance level according to EN ISO 13849-1 (EF007399) | None | |
| Appendant operation agent (Ex ia) (EF004141) | false | |
| Appendant operation agent (Ex ib) (EF004142) | false | |
| Explosion safety category for gas (EF003997) | ATEX gas-ex-protection, Cat. 3G | |
| Explosion safety category for dust (EF003998) | None | |
| Width (EF000008) | 100.0 | mm |
| Height (EF000040) | 117.0 | mm |
| Depth (EF000049) | 75.0 | mm |
| SIPLUS ET 200SP CPU 1512SP-1 PN -40...+60°C with conformal coating based on 6ES7512-1DK01-0AB0 . CPU 1512SP-1 PN for ET 200SP, Central processing unit with Work memory 200 KB for program and 1 MB for data, first interface: PROFINET IRT with 3-port switch, 48 ns bit performance, SIMATIC Memory Card required, BusAdapter required for port 1 and 2 | ||
| General information | ||
| Product type designation | CPU 1512SP-1 PN | |
| Product function | ||
| ● Isochronous mode | Yes; Only with PROFINET; with minimum OB 6x cycle of 625 µs | |
| Configuration control | ||
| via dataset | Yes | |
| Control elements | ||
| Mode selector switch | 1 | |
| Supply voltage | ||
| Type of supply voltage | 24 V DC | |
| permissible range, lower limit (DC) | 19.2 V | |
| permissible range, upper limit (DC) | 28.8 V | |
| Reverse polarity protection | Yes | |
| Mains buffering | ||
| ● Mains/voltage failure stored energy time | 5 ms | |
| Input current | ||
| Current consumption (rated value) | 0.6 A | |
| Inrush current, max. | 4.7 A; Rated value | |
| I²t | 0.14 A²·s | |
| Power | ||
| Infeed power to the backplane bus | 8.75 W | |
| Power loss | ||
| Power loss, typ. | 5.6 W | |
| Memory | ||
| Number of slots for SIMATIC memory card | 1 | |
| SIMATIC memory card required | Yes | |
| Work memory | ||
| ● integrated (for program) | 200 kbyte | |
| ● integrated (for data) | 1 Mbyte | |
| Load memory | ||
| ● Plug-in (SIMATIC Memory Card), max. | 32 Gbyte | |
| Backup | ||
| ● maintenance-free | Yes | |
| CPU processing times | ||
| for bit operations, typ. | 48 ns | |
| for word operations, typ. | 58 ns | |
| for fixed point arithmetic, typ. | 77 ns | |
| for floating point arithmetic, typ. | 307 ns | |
| CPU-blocks | ||
| Number of elements (total) | 2 000; In addition to blocks such as DBs, FBs and FCs, UDTs, global constants, etc. are also regarded as elements | |
| DB | ||
| ● Number range | 1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999 | |
| ● Size, max. | 1 Mbyte; For DBs with absolute addressing, the max. size is 64 KB | |
| FB | ||
| ● Number range | 0 ... 65 535 | |
| ● Size, max. | 200 kbyte | |
| FC | ||
| ● Number range | 0 ... 65 535 | |
| ● Size, max. | 200 kbyte | |
| OB | ||
| ● Size, max. | 200 kbyte | |
| ● Number of free cycle OBs | 100 | |
| ● Number of time alarm OBs | 20 | |
| ● Number of delay alarm OBs | 20 | |
| ● Number of cyclic interrupt OBs | 20 | |
| ● Number of process alarm OBs | 50 | |
| ● Number of DPV1 alarm OBs | 3 | |
| ● Number of isochronous mode OBs | 1 | |
| ● Number of technology synchronous alarm OBs | 2 | |
| ● Number of startup OBs | 100 | |
| ● Number of asynchronous error OBs | 4 | |
| ● Number of synchronous error OBs | 2 | |
| ● Number of diagnostic alarm OBs | 1 | |
| Nesting depth | ||
| ● per priority class | 24 | |
| Counters, timers and their retentivity | ||
| S7 counter | ||
| ● Number | 2 048 | |
| Retentivity | ||
| — adjustable | Yes | |
| IEC counter | ||
| ● Number | Any (only limited by the main memory) | |
| Retentivity | ||
| — adjustable | Yes | |
| S7 times | ||
| ● Number | 2 048 | |
| Retentivity | ||
| — adjustable | Yes | |
| IEC timer | ||
| ● Number | Any (only limited by the main memory) | |
| Retentivity | ||
| — adjustable | Yes | |
| Data areas and their retentivity | ||
| Retentive data area (incl. timers, counters, flags), max. | 128 kbyte; Available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 88 KB | |
| Flag | ||
| ● Number, max. | 16 kbyte | |
| ● Number of clock memories | 8; 8 clock memory bit, grouped into one clock memory byte | |
| Data blocks | ||
| ● Retentivity adjustable | Yes | |
| ● Retentivity preset | No | |
| Local data | ||
| ● per priority class, max. | 64 kbyte; max. 16 KB per block | |
| Address area | ||
| Number of IO modules | 2 048; max. number of modules / submodules | |
| I/O address area | ||
| ● Inputs | 32 kbyte; All inputs are in the process image | |
| ● Outputs | 32 kbyte; All outputs are in the process image | |
| per integrated IO subsystem | ||
| — Inputs (volume) | 8 kbyte | |
| — Outputs (volume) | 8 kbyte | |
| per CM/CP | ||
| — Inputs (volume) | 8 kbyte | |
| — Outputs (volume) | 8 kbyte | |
| Subprocess images | ||
| ● Number of subprocess images, max. | 32 | |
| Address space per module | ||
| ● Address space per module, max. | 32 byte; For input and output data respectively | |
| Address space per station | ||
| ● Address space per station, max. | 1 280 byte; for central inputs and outputs; depending on configuration | |
| Hardware configuration | ||
| Number of distributed IO systems | 20 | |
| Number of DP masters | ||
| ● Via CM | 1 | |
| Number of IO Controllers | ||
| ● integrated | 1 | |
| ● Via CM | 0 | |
| Rack | ||
| ● Modules per rack, max. | 64; CPU + 64 modules + server module (mounting width max. 1 m) | |
| ● Number of lines, max. | 1 | |
| PtP CM | ||
| ● Number of PtP CMs | the number of connectable PtP CMs is only limited by the number of available slots | |
| Time of day | ||
| Clock | ||
| ● Type | Hardware clock | |
| ● Backup time | 6 wk; At 40 °C ambient temperature, typically | |
| ● Deviation per day, max. | 10 s; Typ.: 2 s | |
| Operating hours counter | ||
| ● Number | 16 | |
| Clock synchronization | ||
| ● supported | Yes | |
| ● to DP, master | Yes; Via CM DP module | |
| ● to DP, slave | Yes; Via CM DP module | |
| ● in AS, master | Yes | |
| ● in AS, slave | Yes | |
| ● on Ethernet via NTP | Yes | |
| Interfaces | ||
| Number of PROFINET interfaces | 1 | |
| Number of PROFIBUS interfaces | 1; Via CM DP module | |
| Optical interface | Yes; Via BusAdapter BA 2x SCRJ | |
| 1. Interface | ||
| Interface types | ||
| ● Number of ports | 3; 1. integr. + 2. via BusAdapter | |
| ● integrated switch | Yes | |
| ● RJ 45 (Ethernet) | Yes; X1 | |
| ● BusAdapter (PROFINET) | Yes; Applicable BusAdapter: BA 2x RJ45, BA 2x FC, BA 2x SCRJ, BA SCRJ / RJ45, BA SCRJ / FC | |
| Protocols | ||
| ● PROFINET IO Controller | Yes | |
| ● PROFINET IO Device | Yes | |
| ● SIMATIC communication | Yes | |
| ● Open IE communication | Yes | |
| ● Web server | Yes | |
| ● Media redundancy | Yes | |
| PROFINET IO Controller | ||
| Services | ||
| — PG/OP communication | Yes | |
| — S7 routing | Yes | |
| — Isochronous mode | Yes | |
| — Direct data exchange | Yes; Requirement: IRT and isochronous mode (MRPD optional) | |
| — IRT | Yes | |
| — MRP | Yes; as MRP redundancy manager and/or MRP client; max. number of devices in the ring: 50 | |
| — MRPD | Yes; Requirement: IRT | |
| — PROFIenergy | Yes | |
| — Prioritized startup | Yes; Max. 32 PROFINET devices | |
| — Number of connectable IO Devices, max. | 128; In total, up to 253 distributed I/O devices can be connected via PROFIBUS or PROFINET | |
| — Of which IO devices with IRT, max. | 64 | |
| — Number of connectable IO Devices for RT, max. | 128 | |
| — of which in line, max. | 128 | |
| — Number of IO Devices that can be simultaneously activated/deactivated, max. | 8; in total across all interfaces | |
| — Number of IO Devices per tool, max. | 8 | |
| — Updating times | The minimum value of the update time also depends on communication share set for PROFINET IO, on the number of IO devices, and on the quantity of configured user data | |
| Update time for IRT | ||
| — for send cycle of 250 µs | 250 μs to 4 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 500 µs of the isochronous OB is decisive | |
| — for send cycle of 500 µs | 500 μs to 8 ms; Note: In the case of IRT with isochronous mode, the minimum update time of 625 µs of the isochronous OB is decisive | |
| — for send cycle of 1 ms | 1 ms to 16 ms | |
| — for send cycle of 2 ms | 2 ms to 32 ms | |
| — for send cycle of 4 ms | 4 ms to 64 ms | |
| — With IRT and parameterization of "odd" send cycles | Update time = set "odd" send clock (any multiple of 125 µs: 375 µs, 625 µs ... 3 875 µs) | |
| Update time for RT | ||
| — for send cycle of 250 µs | 250 µs to 128 ms | |
| — for send cycle of 500 µs | 500 µs to 256 ms | |
| — for send cycle of 1 ms | 1 ms to 512 ms | |
| — for send cycle of 2 ms | 2 ms to 512 ms | |
| — for send cycle of 4 ms | 4 ms to 512 ms | |
| PROFINET IO Device | ||
| Services | ||
| — PG/OP communication | Yes | |
| — S7 routing | Yes | |
| — Isochronous mode | No | |
| — IRT | Yes | |
| — MRP | Yes | |
| — MRPD | Yes | |
| — PROFIenergy | Yes | |
| — Shared device | Yes | |
| — Number of IO Controllers with shared device, max. | 4 | |
| 2. Interface | ||
| Interface types | ||
| ● Number of ports | 1 | |
| ● RS 485 | Yes; Via CM DP module | |
| Protocols | ||
| ● PROFIBUS DP master | Yes | |
| ● PROFIBUS DP slave | Yes | |
| ● SIMATIC communication | Yes | |
| Interface types | ||
| RJ 45 (Ethernet) | ||
| ● 100 Mbps | Yes | |
| ● Autonegotiation | Yes | |
| ● Autocrossing | Yes | |
| ● Industrial Ethernet status LED | Yes | |
| RS 485 | ||
| ● Transmission rate, max. | 12 Mbit/s | |
| Protocols | ||
| Number of connections | ||
| ● Number of connections, max. | 88 | |
| ● Number of connections reserved for ES/HMI/web | 10 | |
| ● Number of connections via integrated interfaces | 88 | |
| ● Number of S7 routing paths | 16 | |
| Redundancy mode | ||
| Media redundancy | ||
| — MRP | Yes; as MRP redundancy manager and/or MRP client; max. number of devices in the ring: 50 | |
| — Switchover time on line break, typ. | 200 ms | |
| — Number of stations in the ring, max. | 50 | |
| SIMATIC communication | ||
| ● S7 communication, as server | Yes | |
| ● S7 communication, as client | Yes | |
| ● User data per job, max. | See online help (S7 communication, user data size) | |
| Open IE communication | ||
| ● TCP/IP | Yes | |
| — Data length, max. | 64 kbyte | |
| — several passive connections per port, supported | Yes | |
| ● ISO-on-TCP (RFC1006) | Yes | |
| — Data length, max. | 64 kbyte | |
| ● UDP | Yes | |
| — Data length, max. | 1 472 byte | |
| ● DHCP | No | |
| ● SNMP | Yes | |
| ● DCP | Yes | |
| ● LLDP | Yes | |
| Web server | ||
| ● HTTP | Yes; Standard and user-defined pages | |
| ● HTTPS | Yes; Standard and user-defined pages | |
| PROFIBUS DP master | ||
| ● Number of connections, max. | 48 | |
| Services | ||
| — PG/OP communication | Yes | |
| — S7 routing | Yes | |
| — Data record routing | Yes | |
| — Isochronous mode | No | |
| — Equidistance | No | |
| — Number of DP slaves | 125 | |
| — Activation/deactivation of DP slaves | Yes | |
| Further protocols | ||
| ● MODBUS | Yes; MODBUS TCP | |
| S7 message functions | ||
| Number of login stations for message functions, max. | 32 | |
| Program alarms | Yes | |
| Number of configurable program messages, max. | 5 000 | |
| Number of simultaneously active program alarms | ||
| ● Number of program alarms | 300 | |
| ● Number of alarms for system diagnostics | 100 | |
| ● Number of alarms for motion technology objects | 80 | |
| Test commissioning functions | ||
| Joint commission (Team Engineering) | Yes; Parallel online access possible for up to 3 engineering systems | |
| Status block | Yes; up to 8 simultaneously | |
| Single step | No | |
| Status/control | ||
| ● Status/control variable | Yes | |
| ● Variables | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | |
| ● Number of variables, max. | ||
| — of which status variables, max. | 200; per job | |
| — of which control variables, max. | 200; per job | |
| Forcing | ||
| ● Forcing | Yes | |
| ● Forcing, variables | Peripheral inputs/outputs | |
| ● Number of variables, max. | 200 | |
| Diagnostic buffer | ||
| ● present | Yes | |
| ● Number of entries, max. | 1 000 | |
| — of which powerfail-proof | 500 | |
| Traces | ||
| ● Number of configurable Traces | 4; Up to 512 KB of data per trace are possible | |
| Interrupts/diagnostics/status information | ||
| Diagnostics indication LED | ||
| ● RUN/STOP LED | Yes | |
| ● ERROR LED | Yes | |
| ● MAINT LED | Yes | |
| ● Monitoring of the supply voltage (PWR-LED) | Yes | |
| ● Connection display LINK TX/RX | Yes | |
| Supported technology objects | ||
| Motion Control | Yes | |
| ● Speed-controlled axis | ||
| — Number of speed-controlled axes, max. | 6; Requirement: There must be no other motion technology objects created; note: The number of axes affects the cycle time of the PLC program; selection guide via the TIA Selection Tool | |
| ● Positioning axis | ||
| — Number of positioning axes, max. | 6; Requirement: There must be no other motion technology objects created; note: The number of axes affects the cycle time of the PLC program; selection guide via the TIA Selection Tool | |
| ● Synchronized axes (relative gear synchronization) | ||
| — Number of axes, max. | 3; Requirement: There must be no other motion technology objects created; note: The number of axes affects the cycle time of the PLC program; selection guide via the TIA Selection Tool | |
| ● External encoders | ||
| — Number of external encoders, max. | 6; Requirement: There must be no other motion technology objects created; note: The number of axes affects the cycle time of the PLC program; selection guide via the TIA Selection Tool | |
| Controller | ||
| ● PID_Compact | Yes; Universal PID controller with integrated optimization | |
| ● PID_3Step | Yes; PID controller with integrated optimization for valves | |
| ● PID-Temp | Yes; PID controller with integrated optimization for temperature | |
| Counting and measuring | ||
| ● High-speed counter | Yes | |
| Ambient conditions | ||
| Ambient temperature during operation | ||
| ● horizontal installation, min. | -40 °C; = Tmin (incl. condensation/frost) | |
| ● horizontal installation, max. | 60 °C; = Tmax | |
| ● vertical installation, min. | -40 °C; = Tmin | |
| ● vertical installation, max. | 50 °C; = Tmax | |
| Altitude during operation relating to sea level | ||
| ● Installation altitude above sea level, max. | 5 000 m | |
| ● Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) | |
| Relative humidity | ||
| ● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation | |
| Resistance | ||
| Coolants and lubricants | ||
| — Resistant to commercially available coolants and lubricants | Yes; Incl. diesel and oil droplets in the air | |
| Use in stationary industrial systems | ||
| — to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | |
| — to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | |
| — to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | |
| — Against mechanical environmental conditions acc. to EN 60721-3-3 | Yes; Class 3M8 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | |
| Use on ships/at sea | ||
| — to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request | |
| — to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | |
| — to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * | |
| — Against mechanical environmental conditions acc. to EN 60721-3-6 | Yes; Class 6M4 using the SIPLUS Mounting Kit ET 200SP (6AG1193-6AA00-0AA0) | |
| Usage in industrial process technology | ||
| — Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) | |
| — Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) | |
| Remark | ||
| — Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! | |
| Conformal coating | ||
| ● Coatings for printed circuit board assemblies acc. to EN 61086 | Yes; Class 2 for high reliability | |
| ● Protection against fouling acc. to EN 60664-3 | Yes; Type 1 protection | |
| ● Military testing according to MIL-I-46058C, Amendment 7 | Yes; Discoloration of coating possible during service life | |
| ● Qualification and Performance of Electrical Insulating Compound for Printed Board Assemblies according to IPC-CC-830A | Yes; Conformal coating, Class A | |
| Configuration | ||
| Programming | ||
| Programming language | ||
| — LAD | Yes | |
| — FBD | Yes | |
| — STL | Yes | |
| — SCL | Yes | |
| — GRAPH | Yes | |
| Know-how protection | ||
| ● User program protection/password protection | Yes | |
| ● Copy protection | Yes | |
| ● Block protection | Yes | |
| Access protection | ||
| ● Protection level: Write protection | Yes | |
| ● Protection level: Read/write protection | Yes | |
| ● Protection level: Complete protection | Yes | |
| Cycle time monitoring | ||
| ● lower limit | adjustable minimum cycle time | |
| ● upper limit | adjustable maximum cycle time | |
| Dimensions | ||
| Width | 100 mm | |
| Height | 117 mm | |
| Depth | 75 mm | |
| Weights | ||
| Weight, approx. | 310 g | |
| last modified: | 08/29/2020 | |
| Product | ||||||||||||||||||||||||||||||||||
| Article Number (Market Facing Number) | 6AG1512-1DK01-2AB0 | |||||||||||||||||||||||||||||||||
| Product Description | SIPLUS ET 200SP CPU 1512SP-1 PN -40...+60°C with conformal coating based on 6ES7512-1DK01-0AB0 . CPU 1512SP-1 PN for ET 200SP, Central processing unit with Work memory 200 KB for program and 1 MB for data, first interface: PROFINET IRT with 3-port switch, 48 ns bit performance, SIMATIC Memory Card required, BusAdapter required for port 1 and 2 | |||||||||||||||||||||||||||||||||
| Product family | SIPLUS CPU 1512SP-1 PN | |||||||||||||||||||||||||||||||||
| Product Lifecycle (PLM) | PM300:Active Product | |||||||||||||||||||||||||||||||||
| Price data | ||||||||||||||||||||||||||||||||||
| Price Group | 473 | |||||||||||||||||||||||||||||||||
| Surcharge for Raw Materials | None | |||||||||||||||||||||||||||||||||
| Metal Factor | None | |||||||||||||||||||||||||||||||||
| Delivery information | ||||||||||||||||||||||||||||||||||
| Export Control Regulations | AL : N / ECCN : EAR99H | |||||||||||||||||||||||||||||||||
| Standard lead time ex-works | 42 Day/Days | |||||||||||||||||||||||||||||||||
| Net Weight (kg) | 0,500 Kg | |||||||||||||||||||||||||||||||||
| Product Dimensions (W x L x H) | Not available | |||||||||||||||||||||||||||||||||
| Packaging Dimension | 10,00 x 12,20 x 6,30 | |||||||||||||||||||||||||||||||||
| Package size unit of measure | CM | |||||||||||||||||||||||||||||||||
| Quantity Unit | 1 Piece | |||||||||||||||||||||||||||||||||
| Packaging Quantity | 1 | |||||||||||||||||||||||||||||||||
| Additional Product Information | ||||||||||||||||||||||||||||||||||
| EAN | 4047618072322 | |||||||||||||||||||||||||||||||||
| UPC | 804766386046 | |||||||||||||||||||||||||||||||||
| Commodity Code | 85371091 | |||||||||||||||||||||||||||||||||
| LKZ_FDB/ CatalogID | A&DSE/SIP ADD | |||||||||||||||||||||||||||||||||
| Product Group | 4257 | |||||||||||||||||||||||||||||||||
| Group Code | R740 | |||||||||||||||||||||||||||||||||
| Country of origin | Germany | |||||||||||||||||||||||||||||||||
| Compliance with the substance restrictions according to RoHS directive | Since: 21.07.2014 | |||||||||||||||||||||||||||||||||
| Product class | B: return restricted, please contact your Siemens partner/contact | |||||||||||||||||||||||||||||||||
| WEEE (2012/19/EU) Take-Back Obligation | Yes | |||||||||||||||||||||||||||||||||
| REACH Art. 33 Duty to inform according to the current list of candidates |
| |||||||||||||||||||||||||||||||||
| Classifications | ||||||||||||||||||||||||||||||||||
| ||||||||||||||||||||||||||||||||||
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE SIEMENS EN.pdf | 120 Mbytes |
|
| PDF CATALOGUE SIEMENS EN.pdf | 104 Mbytes |
|
| 6AG1512-1DK01-2AB0 EN_6AG1512-1DK01-2AB0.pdf | 144 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.