SIPLUS ET 200S EM 2AI HF -25...+60°C with conformal coating based on 6ES7134-4LB02-0AB0 . 2 AI U High Feature for ET 200S, 15 mm width, Cycle time per module: "0.5 ms, ""+/-10 V; 15 bit+sign,""" "+/-5 V; 15 bit+sign, 1..5V;" "15"" bit, Operational limit" +/-0.1% with SF LED (group fault)
SIPLUS ET 200, 1 electronic module for ET 200S EM 2AI HF, working temperature from - 25 to + 70 ° C with a layer of special protection, based on 6ES7134-4LB02-0AB0 . 2 AI U HIGH FEATURE, width 15 mm, cycle time per module: 0.5 ms, +/-10V; 15 bit + sign, +/-5V; 15bit + sign,1..5V; 15bit, error limit practical +/ - 0.1% and with LED failure clustered SF
AUTOMATION SYSTEMS > SIPLUS Extreme (LOGO, S7-1200, S7-1500, etc)
Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
| Value | Unit | |
|---|---|---|
| Performance level according to EN ISO 13849-1 (EF007399) | - | |
| Supply voltage AC 60 Hz (EF007533) | - | V |
| SIL according to IEC 61508 (EF009889) | - | |
| Supply voltage AC 50 Hz (EF007532) | - | V |
| Category according to EN 954-1 (EF006782) | - | |
| Degree of protection (NEMA) (EF011959) | - | |
| Supply voltage DC (EF007534) | ['20.4', '28.8'] | V |
| Voltage type of supply voltage (EF002991) | DC | |
| Input, current (EF003204) | false | |
| Input, voltage (EF003205) | true | |
| Input, resistor (EF003206) | false | |
| Input, resistance thermometer (EF003207) | false | |
| Input, thermocouple (EF003208) | false | |
| Input signal, configurable (EF003209) | true | |
| Resolution of the analogue inputs (EF003575) | 16 | Bit |
| Output, current (EF003212) | - | |
| Output, voltage (EF003213) | - | |
| Output signal configurable (EF003214) | - | |
| Resolution of the analogue outputs (EF003577) | - | Bit |
| Number of analogue inputs (EF001994) | 2 | |
| Number of analogue outputs (EF001995) | 0 | |
| Analogue inputs configurable (EF008518) | true | |
| Analogue outputs configurable (EF008519) | - | |
| Number of HW-interfaces industrial Ethernet (EF003020) | 0 | |
| Number of interfaces PROFINET (EF006932) | 0 | |
| Number of HW-interfaces RS-232 (EF003021) | 0 | |
| Number of HW-interfaces RS-422 (EF003022) | 0 | |
| Number of HW-interfaces RS-485 (EF003023) | 0 | |
| Number of HW-interfaces serial TTY (EF003024) | 0 | |
| Number of HW-interfaces parallel (EF003026) | 0 | |
| Number of HW-interfaces Wireless (EF006933) | 0 | |
| Number of HW-interfaces USB (EF003025) | 0 | |
| Number of HW-interfaces other (EF003027) | 0 | |
| Supporting protocol for TCP/IP (EF003050) | false | |
| Supporting protocol for PROFIBUS (EF003052) | false | |
| Supporting protocol for CAN (EF003053) | false | |
| Supporting protocol for INTERBUS (EF003054) | false | |
| Supporting protocol for ASI (EF003051) | false | |
| Supporting protocol for KNX (EF003055) | false | |
| Supporting protocol for Modbus (EF003057) | false | |
| Supporting protocol for Data-Highway (EF003058) | false | |
| Supporting protocol for DeviceNet (EF003059) | false | |
| Supporting protocol for SUCONET (EF003060) | false | |
| Supporting protocol for LON (EF003017) | false | |
| Supporting protocol for PROFINET IO (EF007525) | false | |
| Supporting protocol for PROFINET CBA (EF007524) | false | |
| Supporting protocol for SERCOS (EF006657) | false | |
| Supporting protocol for Foundation Fieldbus (EF007522) | false | |
| Supporting protocol for EtherNet/IP (EF007521) | false | |
| Supporting protocol for AS-Interface Safety at Work (EF007519) | false | |
| Supporting protocol for DeviceNet Safety (EF007520) | false | |
| Supporting protocol for INTERBUS-Safety (EF006662) | false | |
| Supporting protocol for PROFIsafe (EF007526) | false | |
| Supporting protocol for SafetyBUS p (EF007527) | false | |
| Supporting protocol for other bus systems (EF003062) | false | |
| Radio standard Bluetooth (EF007178) | false | |
| Radio standard WLAN 802.11 (EF007179) | false | |
| Radio standard GPRS (EF008523) | false | |
| Radio standard GSM (EF008524) | false | |
| Radio standard UMTS (EF008525) | false | |
| IO link master (EF007298) | false | |
| System accessory (EF004118) | true | |
| Degree of protection (IP) (EF005474) | IP20 | |
| Type of electric connection (EF003961) | Screw-/spring clamp connection | |
| Fieldbus connection over separate bus coupler possible (EF004002) | true | |
| Rail mounting possible (EF003972) | true | |
| Wall mounting/direct mounting (EF007020) | true | |
| Front build in possible (EF007016) | true | |
| Rack-assembly possible (EF007018) | false | |
| Suitable for safety functions (EF001597) | false | |
| Appendant operation agent (Ex ia) (EF004141) | false | |
| Appendant operation agent (Ex ib) (EF004142) | false | |
| Explosion safety category for gas (EF003997) | ATEX gas-ex-protection, Cat. 3G | |
| Explosion safety category for dust (EF003998) | None | |
| Width (EF000008) | 15.0 | mm |
| Height (EF000040) | 81.0 | mm |
| Depth (EF000049) | 52.0 | mm |
| SIPLUS ET 200S EM 2AI HF -25...+60°C with conformal coating based on 6ES7134-4LB02-0AB0 . 2 AI U High Feature for ET 200S, 15 mm width, Cycle time per module: "0.5 ms, ""+/-10 V; 15 bit+sign,""" "+/-5 V; 15 bit+sign, 1..5V;" "15"" bit, Operational limit" +/-0.1% with SF LED (group fault) | ||
| Supply voltage | ||
| Load voltage L+ | ||
| ● Rated value (DC) | 24 V | |
| ● Reverse polarity protection | Yes | |
| Input current | ||
| from load voltage L+ (without load), max. | 55 mA | |
| from backplane bus 3.3 V DC, max. | 10 mA | |
| Output voltage | ||
| Power supply to the transmitters | ||
| ● present | No | |
| Power loss | ||
| Power loss, typ. | 0.85 W | |
| Address area | ||
| Address space per module | ||
| ● Address space per module, max. | 4 byte | |
| Analog inputs | ||
| Number of analog inputs | 2 | |
| permissible input voltage for voltage input (destruction limit), max. | 35 V; 35 V continuous; 75 V for max. 1 ms | |
| Cycle time (all channels) max. | 0.5 ms; 0.5 ms for 2 channels without noise suppression, 18 / 21 ms per channel with noise suppression | |
| Input ranges (rated values), voltages | ||
| ● 1 V to 5 V | Yes | |
| — Input resistance (1 V to 5 V) | 800 kΩ | |
| ● -10 V to +10 V | Yes | |
| — Input resistance (-10 V to +10 V) | 800 kΩ | |
| ● -5 V to +5 V | Yes | |
| — Input resistance (-5 V to +5 V) | 800 kΩ | |
| Cable length | ||
| ● shielded, max. | 200 m | |
| Analog value generation for the inputs | ||
| Integration and conversion time/resolution per channel | ||
| ● Resolution with overrange (bit including sign), max. | 16 bit; 0 to 5 V: 15 bit, ±10 V: 16 bit, ±5 V: 16 bit | |
| ● Integration time, parameterizable | Yes | |
| ● Interference voltage suppression for interference frequency f1 in Hz | 60 / 50 Hz / no | |
| ● Conversion time (per channel) | 0.04 ms; Without noise suppression 17/20 ms per channel with error | |
| Encoder | ||
| Connection of signal encoders | ||
| ● for voltage measurement | Yes | |
| Errors/accuracies | ||
| Operational error limit in overall temperature range | ||
| ● Voltage, relative to input range, (+/-) | 0.15 %; 0,25 % without interference frequency suppression | |
| Basic error limit (operational limit at 25 °C) | ||
| ● Voltage, relative to input range, (+/-) | 0.05 %; 0.1% without interference frequency suppression | |
| Interrupts/diagnostics/status information | ||
| Alarms | ||
| ● Hardware interrupt | Yes | |
| Diagnoses | ||
| ● Wire-break | Yes; Measuring range 1 to 5 V only | |
| ● Group error | Yes | |
| ● Overflow/underflow | Yes | |
| Diagnostics indication LED | ||
| ● Group error SF (red) | Yes | |
| Parameter | ||
| Remark | 12 bytes, 4 bytes in compatibility mode | |
| Measurement type/range | deactivated / ±5 V / 1 to 5 V / ±10 V | |
| Group diagnostics | Disable / enable | |
| Overflow/underflow | Disable / enable | |
| Potential separation | ||
| Potential separation analog inputs | ||
| ● between the channels | No; however, increased permissible potential difference between the inputs. | |
| ● between the channels and backplane bus | Yes | |
| ● Between the channels and load voltage L+ | Yes | |
| Isolation | ||
| Isolation tested with | 500 V DC | |
| Standards, approvals, certificates | ||
| CE mark | Yes | |
| Ambient conditions | ||
| Ambient temperature during operation | ||
| ● min. | -25 °C; = Tmin | |
| ● max. | 60 °C; = Tmax | |
| Altitude during operation relating to sea level | ||
| ● Installation altitude above sea level, max. | 5 000 m | |
| ● Ambient air temperature-barometric pressure-altitude | Tmin ... Tmax at 1 140 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax -20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) | |
| Relative humidity | ||
| ● With condensation, tested in accordance with IEC 60068-2-38, max. | 100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state) | |
| Resistance | ||
| Use in stationary industrial systems | ||
| — to biologically active substances according to EN 60721-3-3 | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request | |
| — to chemically active substances according to EN 60721-3-3 | Yes; Class 3C4 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | |
| — to mechanically active substances according to EN 60721-3-3 | Yes; Class 3S4 incl. sand, dust, * | |
| Use on ships/at sea | ||
| — to biologically active substances according to EN 60721-3-6 | Yes; Class 6B2 mold and fungal spores (excluding fauna); Class 6B3 on request | |
| — to chemically active substances according to EN 60721-3-6 | Yes; Class 6C3 (RH < 75 %) incl. salt spray acc. to EN 60068-2-52 (severity degree 3); * | |
| — to mechanically active substances according to EN 60721-3-6 | Yes; Class 6S3 incl. sand, dust; * | |
| Usage in industrial process technology | ||
| — Against chemically active substances acc. to EN 60654-4 | Yes; Class 3 (excluding trichlorethylene) | |
| — Environmental conditions for process, measuring and control systems acc. to ANSI/ISA-71.04 | Yes; Level GX group A/B (excluding trichlorethylene; harmful gas concentrations up to the limits of EN 60721-3-3 class 3C4 permissible); level LC3 (salt spray) and level LB3 (oil) | |
| Remark | ||
| — Note regarding classification of environmental conditions acc. to EN 60721, EN 60654-4 and ANSI/ISA-71.04 | * The supplied plug covers must remain in place over the unused interfaces during operation! | |
| Dimensions | ||
| Width | 15 mm | |
| Height | 81 mm | |
| Depth | 52 mm | |
| Weights | ||
| Weight, approx. | 45 g | |
| last modified: | 08/29/2020 | |
| Product | ||||||||||||||||||||||||||||||||||||||||
| Article Number (Market Facing Number) | 6AG1134-4LB02-2AB0 | |||||||||||||||||||||||||||||||||||||||
| Product Description | SIPLUS ET 200S EM 2AI HF -25...+60°C with conformal coating based on 6ES7134-4LB02-0AB0 . 2 AI U High Feature for ET 200S, 15 mm width, Cycle time per module: "0.5 ms, ""+/-10 V; 15 bit+sign,""" "+/-5 V; 15 bit+sign, 1..5V;" "15"" bit, Operational limit" +/-0.1% with SF LED (group fault) | |||||||||||||||||||||||||||||||||||||||
| Product family | Ordering Data Overview | |||||||||||||||||||||||||||||||||||||||
| Product Lifecycle (PLM) | PM300:Active Product | |||||||||||||||||||||||||||||||||||||||
| Price data | ||||||||||||||||||||||||||||||||||||||||
| Price Group | 473 | |||||||||||||||||||||||||||||||||||||||
| Surcharge for Raw Materials | None | |||||||||||||||||||||||||||||||||||||||
| Metal Factor | None | |||||||||||||||||||||||||||||||||||||||
| Delivery information | ||||||||||||||||||||||||||||||||||||||||
| Export Control Regulations | AL : N / ECCN : EAR99H | |||||||||||||||||||||||||||||||||||||||
| Standard lead time ex-works | 23 Day/Days | |||||||||||||||||||||||||||||||||||||||
| Net Weight (kg) | 0,056 Kg | |||||||||||||||||||||||||||||||||||||||
| Product Dimensions (W x L x H) | Not available | |||||||||||||||||||||||||||||||||||||||
| Packaging Dimension | 6,30 x 9,30 x 2,30 | |||||||||||||||||||||||||||||||||||||||
| Package size unit of measure | CM | |||||||||||||||||||||||||||||||||||||||
| Quantity Unit | 1 Piece | |||||||||||||||||||||||||||||||||||||||
| Packaging Quantity | 1 | |||||||||||||||||||||||||||||||||||||||
| Additional Product Information | ||||||||||||||||||||||||||||||||||||||||
| EAN | 4042948623008 | |||||||||||||||||||||||||||||||||||||||
| UPC | 887621021108 | |||||||||||||||||||||||||||||||||||||||
| Commodity Code | 85389091 | |||||||||||||||||||||||||||||||||||||||
| LKZ_FDB/ CatalogID | A&DSE/SIP ADD | |||||||||||||||||||||||||||||||||||||||
| Product Group | 4572 | |||||||||||||||||||||||||||||||||||||||
| Group Code | R740 | |||||||||||||||||||||||||||||||||||||||
| Country of origin | Germany | |||||||||||||||||||||||||||||||||||||||
| Compliance with the substance restrictions according to RoHS directive | Since: 22.08.2011 | |||||||||||||||||||||||||||||||||||||||
| Product class | A: Standard product which is a stock item could be returned within the returns guidelines/period. | |||||||||||||||||||||||||||||||||||||||
| WEEE (2012/19/EU) Take-Back Obligation | Yes | |||||||||||||||||||||||||||||||||||||||
| REACH Art. 33 Duty to inform according to the current list of candidates |
| |||||||||||||||||||||||||||||||||||||||
| Classifications | ||||||||||||||||||||||||||||||||||||||||
| ||||||||||||||||||||||||||||||||||||||||
| Title: | Size: | Type: |
|---|---|---|
| PDF CATALOGUE SIEMENS EN.pdf | 120 Mbytes |
|
| PDF CATALOGUE SIEMENS EN.pdf | 104 Mbytes |
|
| 6AG1134-4LB02-2AB0 EN_6AG1134-4LB02-2AB0.pdf | 107 Kbytes |
![]() |
No customer reviews for the moment.
| Rating: |
|
| Name: | |
| Email: | |
| Subject: | |
| Text: | |
| Do you recommend this product to buy? | |
|
|
|
| Add review | |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.