Fail-safe digital module DM-F PROFIsafe, for fail-safe shutdown via bus/PROFIsafe, Us: 24 V DC, 2 relay enabling circuits, 2 relay outputs, 3 inputs, maximum achievable SIL IEC 61508: 3, maximum achievable PL ISO 13849-1: E |
product brand name | SIRIUS |
product designation | Fail-safe digital module |
design of the product | for fail-safe shutdown |
product type designation | DM-FP |
General technical data |
product function | |
● EMERGENCY OFF function | No |
● automatic start | No |
● light barrier monitoring | No |
● light array monitoring | No |
● protective door monitoring | No |
● magnetically operated switch monitoring NC-NO | No |
● magnetically operated switch monitoring NC-NC | No |
● pressure-sensitive mat monitoring | No |
● monitored start-up | No |
product feature cross-circuit-proof | Yes |
product component | |
● input for thermistor connection | No |
● digital input | Yes |
● input for analog temperature sensors | No |
● input for ground fault detection | No |
● relay output | Yes |
consumed active power | 4 W |
insulation voltage with degree of pollution 3 at AC rated value | 300 V |
surge voltage resistance rated value | 4 000 V |
protection class IP | IP20 |
shock resistance according to IEC 60068-2-27 | 15g / 11 ms |
vibration resistance according to IEC 60068-2-6 | 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g |
operating frequency maximum | 360 1/h |
switching capacity current of the NO contacts of the relay outputs at AC-15 | |
● at 24 V | 3 A |
● at 120 V | 3 A |
● at 240 V | 1.5 A |
switching capacity current of the NO contacts of the relay outputs at DC-13 | |
● at 24 V | 4 A |
● at 60 V | 0.55 A |
● at 125 V | 0.22 A |
● at 250 V | 0.11 A |
switching capacity current of relay enabling circuits at AC-15 | |
● at 24 V | 3 A |
● at 120 V | 3 A |
● at 240 V | 1.5 A |
switching capacity current of relay enabling circuits at DC-13 | |
● at 24 V | 4 A |
● at 60 V | 0.55 A |
● at 125 V | 0.22 A |
● at 250 V | 0.11 A |
mechanical service life (switching cycles) typical | 10 000 000 |
electrical endurance (switching cycles) typical | 100 000 |
buffering time in the event of power failure | 60 ms |
backslide delay time in the event of power failure | |
● typical | 40 ms |
● maximum | 80 ms |
reference code according to IEC 81346-2 | F |
type of input characteristic | Type 2 in accordance with EN 61131-2 |
Substance Prohibitance (Date) | 05/01/2012 |
certificate of suitability according to ATEX directive 2014/34/EU | BVS 06 ATEX F001 |
explosion device group and category according to ATEX directive 2014/34/EU | II (2) G, II (2 ) D, I (M2) |
Electromagnetic compatibility |
EMC emitted interference according to IEC 60947-1 | class A |
EMC immunity according to IEC 60947-1 | corresponds to degree of severity 3 |
conducted interference | |
● due to burst according to IEC 61000-4-4 | 2 kV network connection / 1 kV control connection |
● due to conductor-earth surge according to IEC 61000-4-5 | 1 kV |
● due to conductor-conductor surge according to IEC 61000-4-5 | 0.5 kV |
● due to high-frequency radiation according to IEC 61000-4-6 | 10 V |
field-based interference according to IEC 61000-4-3 | 10 V/m |
electrostatic discharge according to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge |
conducted HF interference emissions according to CISPR11 | corresponds to degree of severity A |
field-bound HF interference emission according to CISPR11 | corresponds to degree of severity A |
Inputs/ Outputs |
product function | |
● parameterizable inputs | Yes |
● parameterizable outputs | Yes |
number of inputs | 4 |
input version with safety-related function | 3 sensor inputs 24 V DC, 1 feedback circuit input |
design of input | |
● feedback input | Yes |
number of digital inputs | 3 |
● with a common reference potential | 4 |
digital input version | |
● type 1 acc. to IEC 61131 | No |
● type 2 acc. to IEC 61131 | Yes |
number of analog inputs | 0 |
number of outputs | 2 |
number of semiconductor outputs | 0 |
number of outputs | |
● as contact-affected switching element | 2 |
● as contact-affected switching element as NO contact safety-related instantaneous contact | 2 |
number of analog outputs | 0 |
switching behavior | monostable |
property of contacts of the relay outputs | Fail-safe NO contacts |
wire length for digital signals maximum | 300 m |
Product Function |
suitability for use | |
● position switch monitoring | No |
● EMERGENCY-OFF circuit monitoring | No |
● valve monitoring | No |
● opto-electronic protection device monitoring | No |
● tactile sensor monitoring | No |
● magnetically operated switch monitoring | No |
● proximity switch monitoring | No |
● safety switch | No |
● safety-related circuits | No |
Communication/ Protocol |
protocol is supported PROFIsafe protocol | Yes |
Installation/ mounting/ dimensions |
mounting position | any |
fastening method | screw and snap-on mounting |
height | 106 mm |
width | 45 mm |
depth | 124 mm |
required spacing | |
● top | 40 mm |
● bottom | 40 mm |
● left | 0 mm |
● right | 0 mm |
Connections/ Terminals |
product component removable terminal for auxiliary and control circuit | Yes |
type of connectable conductor cross-sections | |
● solid | 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²) |
● finely stranded with core end processing | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
● at AWG cables solid | 1x (20 ... 12), 2x (20 ... 14) |
● at AWG cables stranded | 1x (20 ... 14), 2x (20 ... 16) |
tightening torque with screw-type terminals | 0.8 ... 1.2 N·m |
tightening torque [lbf·in] with screw-type terminals | 7 ... 10.3 lbf·in |
Ambient conditions |
installation altitude at height above sea level | |
● 1 maximum | 2 000 m |
● 2 maximum | 3 000 m; max. +50 °C (no protective separation) |
● 3 maximum | 4 000 m; max. +40 °C (no protective separation) |
ambient temperature | |
● during operation | -25 ... +60 °C |
● during storage | -40 ... +80 °C |
● during transport | -40 ... +80 °C |
environmental category | |
● during operation according to IEC 60721 | 3K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
● during storage according to IEC 60721 | 1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4 |
● during transport according to IEC 60721 | 2K2, 2C1, 2S1, 2M2 |
relative humidity during operation | 5 ... 95 % |
contact rating of auxiliary contacts according to UL | B300 / R300 |
Short-circuit protection |
design of the fuse link for short-circuit protection of relay enabling circuits required | gL/gG: 4 A |
Safety related data |
safety device type according to IEC 61508-2 | Type B |
Safety Integrity Level (SIL) | |
● according to IEC 61508 | 3 |
SIL Claim Limit (subsystem) | |
● according to EN 62061 | 3 |
performance level (PL) | |
● according to EN ISO 13849-1 | e |
category | |
● according to EN ISO 13849-1 | 4 |
stop category according to EN 60204-1 | 0 |
average diagnostic coverage level (DCavg) | 99 % |
failure rate [FIT] | |
● at rate of recognizable hazardous failures (λdd) | 897.34 FIT |
● at rate of non-recognizable hazardous failures (λdu) | 7.37 FIT |
safe state | Safety outputs switched off |
touch protection against electrical shock | finger-safe |
contact reliability | 0.1 million operating cycles (AC15, 230 V, 2 A) |
Response times/ Monitoring times |
PROFIsafe monitoring time F-WD-Time | 250 ms |
response time | |
● in case of failure OFDT | 200 ms |
● in faultless state WCDT | 150 ms |
Galvanic isolation |
(electrically) protective separation according to IEC 60947-1 | All circuits in SIMOCODE pro are with protective separation, i.e. they are designed with doubled creepage paths and clearances. NOTICE: The information in the "Protective Separation" test report, No. 2668, must be observed. |
design of the electrical isolation | Protective separation in accordance with IEC 60947-1 for all circuits, up to installation altitude of 2000 m |
Control circuit/ Control |
type of voltage of the control supply voltage | DC |
control supply voltage at DC | |
● rated value | 24 V |
operating range factor control supply voltage rated value at DC | |
● initial value | 0.8 |
● full-scale value | 1.2 |
inrush current peak | |
● at 24 V | 8.3 A |
duration of inrush current peak | |
● at 24 V | 1 ms |
Certificates/ approvals |
Downloads and manuals |
|
Further information |
Information- and Downloadcenter (Catalogs, Brochures,…) |
Industry Mall (Online ordering system) |
Cax online generator |
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) |
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) |
Test report No. A0258, protective separation |
|
|
|
last modified: | 4/8/2022 |
Date 5/7/2022 | Subject to change without notice © Copyright Siemens 2022 |