Basic unit SIMOCODE pro V MR, MODBUS RTU interface 57.6 Kbps, RS 485, 4I/3O freely parameterizable, Us: 110...240 V AC/DC, input for thermistor connection Monostable relay outputs, expandable by extension modules |
product brand name | SIRIUS |
product designation | Motor management system |
design of the product | basic unit 2 |
product type designation | SIMOCODE pro V MR |
General technical data |
product function | |
● bus communication | Yes |
● data acquisition function | Yes |
● diagnostics function | Yes |
● password protection | Yes |
● test function | Yes |
● maintenance function | Yes |
product component | |
● input for thermistor connection | Yes |
● digital input | Yes |
● input for analog temperature sensors | No |
● input for ground fault detection | No |
● relay output | Yes |
product extension | |
● temperature monitoring module | Yes |
● current measuring module | Yes |
● current/voltage measuring module | Yes |
● fail-safe digital I/O module | Yes |
● ground-fault monitoring module | Yes |
● control unit with display | Yes |
● control unit | Yes |
● analog I/O module | Yes |
apparent power consumption | 8.3 VA |
consumed active power | 3.6 W |
insulation voltage with degree of pollution 3 at AC rated value | 300 V |
surge voltage resistance rated value | 4 000 V |
protection class IP | IP20 |
shock resistance | |
● according to IEC 60068-2-27 | 15g / 11 ms |
| |
● vibration resistance | 1-6 Hz / 15 mm; 6-500 Hz / 2 g |
switching capacity current of the NO contacts of the relay outputs at AC-15 | |
● at 24 V | 6 A |
● at 120 V | 6 A |
● at 230 V | 3 A |
switching capacity current of the NO contacts of the relay outputs at DC-13 | |
● at 24 V | 2 A |
● at 60 V | 0.55 A |
● at 125 V | 0.25 A |
mechanical service life (switching cycles) typical | 10 000 000 |
electrical endurance (switching cycles) typical | 100 000 |
buffering time in the event of power failure | 0.2 s |
reference code according to IEC 81346-2 | F |
continuous current of the NO contacts of the relay outputs | |
● at 50 °C | 6 A |
● at 60 °C | 5 A |
type of input characteristic | Type 1 in accordance with EN 61131-2 |
Substance Prohibitance (Date) | 05/01/2012 |
certificate of suitability | |
● according to ATEX directive 2014/34/EU | BVS 06 ATEX F001 |
explosion device group and category according to ATEX directive 2014/34/EU | II (2) G, II (2 ) D, I (M2) |
Electromagnetic compatibility |
EMC emitted interference according to IEC 60947-1 | class A |
EMC immunity according to IEC 60947-1 | corresponds to degree of severity 3 |
conducted interference | |
● due to burst according to IEC 61000-4-4 | 2 kV (power ports) / 1 kV (signal ports) |
● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV |
● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV |
● due to high-frequency radiation according to IEC 61000-4-6 | 10 V |
field-based interference according to IEC 61000-4-3 | 10 V/m |
electrostatic discharge according to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge |
conducted HF interference emissions according to CISPR11 | corresponds to degree of severity A |
field-bound HF interference emission according to CISPR11 | corresponds to degree of severity A |
Inputs/ Outputs |
product function | |
● parameterizable inputs | Yes |
● parameterizable outputs | Yes |
number of inputs | 4 |
● for thermistor connection | 1 |
number of digital inputs with a common reference potential | 4 |
digital input version type 1 acc. to IEC 61131 | Yes |
input voltage at digital input at DC rated value | 24 V |
number of outputs | 3 |
number of semiconductor outputs | 0 |
number of outputs as contact-affected switching element | 3 |
switching behavior | monostable |
type of relay outputs | Monostable |
wire length for digital signals maximum | 300 m |
wire length for thermistor connection | |
● with conductor cross-section = 0.5 mm² maximum | 50 m |
● with conductor cross-section = 1.5 mm² maximum | 150 m |
● with conductor cross-section = 2.5 mm² maximum | 250 m |
Protective and monitoring functions |
product function | |
● asymmetry detection | Yes |
● blocking current evaluation | Yes |
● power factor monitoring | Yes |
● ground fault detection | Yes |
● phase failure detection | Yes |
● phase sequence recognition | Yes |
● voltage detection | Yes |
● monitoring of number of start operations | Yes |
● overvoltage detection | Yes |
● overcurrent detection 1 phase | Yes |
● undervoltage detection | Yes |
● undercurrent detection 1 phase | Yes |
● active power monitoring | Yes |
product function | |
● current detection | Yes |
● overload protection | Yes |
● evaluation of thermistor motor protection | Yes |
total cold resistance number of sensors in series maximum | 1.5 kΩ |
response value of thermoresistor | 3 400 ... 3 800 Ω |
● of the short-circuit control | 9 Ω |
release value of thermoresistor | 1 500 ... 1 650 Ω |
Motor control functions |
product function | |
● parameterizable overload relay | Yes |
● circuit breaker control | Yes |
● direct start | Yes |
● reverse starting | Yes |
● star-delta circuit | Yes |
● star-delta reversing circuit | Yes |
● Dahlander circuit | Yes |
● Dahlander reversing circuit | Yes |
● pole-changing switch circuit | Yes |
● pole-changing switch reversing circuit | Yes |
● slide control | Yes |
● valve control | Yes |
Communication/ Protocol |
| |
● protocol is supported PROFIBUS DP protocol | No |
● protocol is supported PROFINET IO protocol | No |
● protocol is supported PROFIsafe protocol | No |
● protocol is supported Modbus RTU | Yes |
● protocol is supported EtherNet/IP | No |
● protocol is supported OPC UA Server | No |
● protocol is supported LLDP | No |
● protocol is supported Address Resolution Protocol (ARP) | No |
● protocol is supported SNMP | No |
● protocol is supported HTTPS | No |
● protocol is supported NTP | No |
● protocol is supported Media Redundancy Protocol (MRP) | No |
● product function is supported Device Level Ring (DLR) | No |
number of interfaces | |
● according to PROFINET | 0 |
● according to PROFIBUS | 0 |
● according to Ethernet/IP | 0 |
● according to Modbus RTU | 1 |
product function | |
● web server | No |
● shared device | No |
● at the Ethernet interface Autocrossover | No |
● at the Ethernet interface Autonegotiation | No |
● at the Ethernet interface Autosensing | No |
● is supported PROFINET system redundancy | No |
● supports PROFIenergy measured values | No |
● supports PROFIenergy shutdown | No |
transfer rate maximum | 0.057 Mbit/s |
identification & maintenance function | |
● I&M0 - device-specific information | Yes |
● I&M1 – higher level designation/location designation | Yes |
● I&M2 - installation date | Yes |
● I&M3 - comment | Yes |
type of electrical connection of the communication interface | 9-pin D-sub socket (57.6 Kbit) / screw terminal (57.6 Kbit) |
Installation/ mounting/ dimensions |
mounting position | any |
fastening method | screw and snap-on mounting |
height | 111 mm |
width | 45 mm |
depth | 124 mm |
required spacing | |
● top | 40 mm |
● bottom | 40 mm |
● left | 0 mm |
● right | 0 mm |
Connections/ Terminals |
product component removable terminal for auxiliary and control circuit | Yes |
type of connectable conductor cross-sections | |
● solid | 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²) |
● finely stranded with core end processing | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
● at AWG cables solid | 1x (20 ... 12), 2x (20 ... 14) |
● at AWG cables stranded | 1x (20 ... 14), 2x (20 ... 16) |
tightening torque with screw-type terminals | 0.8 ... 1.2 N·m |
tightening torque [lbf·in] with screw-type terminals | 7 ... 10.3 lbf·in |
type of connectable conductor cross-sections for PROFIBUS wire | 2x 0.34 mm², AWG 22 |
Ambient conditions |
installation altitude at height above sea level | |
● 1 maximum | 2 000 m |
● 2 maximum | 3 000 m; max. +50 °C (no protective separation) |
● 3 maximum | 4 000 m; max. +40 °C (no protective separation) |
ambient temperature | |
● during operation | -25 ... +60 °C |
● during storage | -40 ... +80 °C |
● during transport | -40 ... +80 °C |
environmental category | |
● during operation according to IEC 60721 | 3K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
● during storage according to IEC 60721 | 1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4 |
● during transport according to IEC 60721 | 2K2, 2C1, 2S1, 2M2 |
relative humidity | |
● during operation | 5 ... 95 % |
contact rating of auxiliary contacts according to UL | B300 / R300 |
Short-circuit protection |
design of short-circuit protection per output | Fuse links: gG 6 A, quick-response 10 A (IEC 60947-5-1), miniature circuit-breaker C char.: 1.6 A (IEC 60947-5-1) or 6 A (I_K < 500 A) |
Safety related data |
touch protection against electrical shock | finger-safe |
Galvanic isolation |
(electrically) protective separation according to IEC 60947-1 | All circuits with protective separation (double creepage paths and clearances), the information in the "Protective Separation" test report, No. A0258, must be observed (link see further information) |
Control circuit/ Control |
product function soft starter control | Yes |
type of voltage of the control supply voltage | AC/DC |
control supply voltage at AC | |
● at 50 Hz rated value | 110 ... 240 V |
● at 60 Hz rated value | 110 ... 240 V |
control supply voltage frequency | |
● 1 rated value | 50 Hz |
● 2 rated value | 60 Hz |
relative symmetrical tolerance of the control supply voltage frequency | 5 % |
control supply voltage at DC | |
● rated value | 110 ... 240 V |
operating range factor control supply voltage rated value at DC | |
● initial value | 0.85 |
● full-scale value | 1.1 |
operating range factor control supply voltage rated value at AC at 50 Hz | |
● initial value | 0.85 |
● full-scale value | 1.1 |
operating range factor control supply voltage rated value at AC at 60 Hz | |
● initial value | 0.85 |
● full-scale value | 1.1 |
inrush current peak | |
● at 240 V | 15 A |
duration of inrush current peak | |
● at 240 V | 1 ms |
Certificates/ approvals |
Downloads and manuals |
|
Further information |
Information- and Downloadcenter (Catalogs, Brochures,…) |
Industry Mall (Online ordering system) |
Cax online generator |
Service&Support (Manuals, Certificates, Characteristics, FAQs,...) |
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...) |
Test report No. A0258, protective separation |
|
|
|
last modified: | 4/8/2022 |
Date 5/5/2022 | Subject to change without notice © Copyright Siemens 2022 |