Key Commercial Data

Orderkey2920735
Packing unit10 pc
Catalog pagePage 97 (C-6-2015)
GTIN4046356168373
Weight per Piece (excluding packing)25.000 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height100 mm
Width6.2 mm
Depth63.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 85 °C
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorblack
Standards for cearances and creepage distancesEN 60664-1
Mounting typeDIN rail: 35 mm
TypeDouble-level terminal block
Number of positions2
Direction of actionLine-Earth Ground

Protective circuit

IEC test classificationC1
C3
VDE requirement classC1
C3
Nominal voltage UN24 V DC
Maximum continuous voltage UC30 V DC
21 V AC
Rated current10 A (50 °C)
Operating effective current ICat UC≤ 5 µA (DC)
≤ 20 µA (60 Hz)
Residual current IPE≤ 10 µA (DC)
≤ 40 µA (60 Hz)
Nominal discharge current In(8/20) µs (line-earth)310 A (per path)
Total discharge current Itotal(8/20) µs620 A
Nominal pulse current Ian (10/1000) µs (line-earth)62 A (per path)
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 45 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 45 V
Residual voltage at In(line-earth)≤ 48 V
Residual voltage with Ian (10/1000) µs (line-earth)≤ 48 V
Voltage protection level Up(line-earth)≤ 45 V (C1 - 250 A)
Response time tA(line-earth)≤ 1 ns
Input attenuation aE, asym.typ. 0.3 dB (≤ 1 MHz / 50 Ω)
typ. 0.1 dB (≤ 150 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (GND) in 50 Ohm systemtyp. 3 MHz
Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm systemtyp. 500 kHz
Capacity (line-earth)≤ 2 nF
Surge protection fault messagenone
Max. required back-up fuse10 A (T)
Impulse durability (line-earth)C1 - 500 V / 250 A
C3 - 25 A
Alternating current carrying capacity (line-earth)2 A (5x 1 s)

Connection data

Connection methodSpring-cage connection
Connection method INSpring-cage
Connection method OUTSpring-cage
Stripping length8 mm
Conductor cross section flexible0.5 mm² ... 2.5 mm²
Conductor cross section solid0.5 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Standards and Regulations

Standards/regulationsIEC 61643-21
EN 61643-21
Standards/specificationsIEC 61643-21/A1 2008
EN 61643-21/A1 2009

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications

Datasheet - PDF

Title: Size: Type:
PDF CATALOG PHOENIX PROTECTION EN.pdf 27 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.