PT-IQ-3-PB+F-PT 2801287 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PT-IQ-3-PB+F-PT 2801287 PHOENIX CONTACT Surge protection device

PT-IQ-3-PB+F-PT

2801287

PHOENIX_CONTACT

Surge protection device

Surge protection, consisting of plug-in protection and base element, with multi-level status indication integrated into the module for three signal conductors with joint reference potential. Indirect grounding with gas discharger. For high-frequency applications and telecommunication interfaces without supply voltage (up to 90 MBit/s).

More details


Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Key Commercial Data

Orderkey2801287
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 79 (C-6-2015)
GTIN4046356766685
Weight per Piece (excluding packing)111.000 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height109.3 mm
Width17.7 mm
Depth77.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl (above mean sea level))
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorjet black RAL 9005
Mounting typeDIN rail: 35 mm
TypeDIN rail module, two-section, divisible
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN5 V DC
Maximum continuous voltage UC6 V DC
4 V AC
Rated current600 mA (40 °C)
Operating effective current ICat UC≤ 800 µA (per path)
Residual current IPE≤ 10 µA
Nominal discharge current In(8/20) µs (line-line)10 kA
Nominal discharge current In(8/20) µs (line-earth)10 kA
Pulse discharge current Iimp(10/350) µs (line-earth)2.5 kA
Pulse discharge current Iimp(10/350) µs (line-signalground)2.5 kA
Total discharge current Itotal(8/20) µs20 kA
Voltage protection level Up(line-line)≤ 90 V (C1 - 1 kV/500 A)
≤ 140 V (C2 - 10 kV / 5 kA)
≤ 30 V (C3 - 25 A)
≤ 30 V (C3 - 50 A)
Voltage protection level Up(line-earth)≤ 730 V (C1 - 1 kV/500 A)
≤ 900 V (C2 - 10 kV / 5 kA)
≤ 900 V (C3 - 25 A)
≤ 900 V (C3 - 50 A)
Voltage protection level Up(line-signalground)≤ 90 V (C1 - 1 kV/500 A)
≤ 140 V (C2 - 10 kV / 5 kA)
≤ 30 V (C3 - 25 A)
≤ 30 V (C3 - 50 A)
Voltage protection level Upstatic (line-line)≤ 45 V (C1 - 1 kV/500 A)
Voltage protection level Upstatic (line-signalground)≤ 45 V (C1 - 1 kV/500 A)
Response time tA(line-line)≤ 1 ns
Response time tA (line-signalground)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 10 MHz/150 Ω)
Input attenuation aE, asym.typ. 0.3 dB (≤ 10 MHz/150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ohm systemtyp. 60 MHz
Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm systemtyp. 60 MHz
Capacity (line-line)typ. 30 pF
Capacity (line-signalground)typ. 30 pF
Resistance in series1.2 Ω ±5 %
Surge protection fault messageOptical, multi-stage
Max. required back-up fuse600 mA (FF)
Impulse durability (line-line)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 50 A
Impulse durability (line-earth)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 50 A
D1 - 2.5 kA
Impulse durability (line-signalground)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C3 - 50 A
D1 - 2,5 kA
Pulse reset time (line-line)≤ 10 ms
Pulse reset time (line-earth)≤ 10 ms
Pulse reset time (line-signalground)≤ 10 ms

Connection data

Connection methodPush-in connection
Stripping length10 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Connection, equipotential bonding

Connection methodDIN rail NS35

Standards and Regulations

Standards/specificationsIEC 61643-21 2000 + A1:2008 + A2:2012
EN 61643-21 2001 + A1:2009
EN 61000-6-2 2007 + A1:2011
EN 61000-6-3 2005

Classifications


Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.