Product successfully added to your shopping cart
FLT-CP-2S-350
2859767
PHOENIX_CONTACT
1
Type 1+2 protective device combination
Trabtech (TT)
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Orderkey | 2859767 |
---|---|
Packing unit | 1 pc |
Note | Made to Order (non-returnable) |
Catalog page | Page 37 (C-6-2013) |
GTIN | 4017918956486 |
Weight per Piece (excluding packing) | 1,110.820 g |
Custom tariff number | 85363030 |
Country of origin | DE (Germany) |
Degree of protection | IP20 (only when all terminal points are used) |
---|---|
Ambient temperature (operation) | -40 °C ... 80 °C |
Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Altitude | ≤ 2000 m (amsl (above mean sea level)) |
Permissible humidity (operation) | 5 % ... 95 % |
Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
Vibration (operation) | 5g (5 - 500 Hz/2.5 h/X, Y, Z) |
IEC test classification | I + II |
---|---|
T1 + T2 | |
EN type | T1 + T2 |
IEC power supply system | TN-S |
TT | |
Mode of protection | L-N |
L-PE | |
N-PE | |
Mounting type | DIN rail: 35 mm |
Color | gray/blue |
black | |
Housing material | PBT |
Degree of pollution | 2 |
Flammability rating according to UL 94 | V-0 |
Type | DIN rail module, two-section, divisible |
Number of positions | 3 |
Arrester can be tested with CHECKMASTER from software version: | From SW rev. 3.00 |
Surge protection fault message | Optical, remote indicator contact |
Nominal voltage UN | 240/415 V AC (TN-S) |
---|---|
240/415 V AC (TT) | |
Nominal frequency fN | 50 Hz (60 Hz) |
Maximum continuous operating voltage UC(L-N) | 350 V AC |
Maximum continuous voltage UC(N-PE) | 350 V AC |
Rated load current IL | 125 A (< 55 °C) |
Residual current IPE | ≤ 0.01 mA |
Nominal discharge current In(8/20) µs (L-N) | 25 kA |
Nominal discharge current In(8/20) µs (L-PE) | 25 kA |
Nominal discharge current In(8/20) µs (N-PE) | 100 kA |
Impulse discharge current (10/350) µs (L-N), charge | 12.5 As |
Impulse discharge current (10/350) µs (L-N), specific energy | 160 kJ/Ω |
Impulse discharge current (10/350) µs (L-N), peak current value Iimp | 25 kA |
Impulse discharge current (10/350) µs (L-PE), charge | 12.5 As |
Impulse discharge current (10/350) µs (L-PE), specific energy | 160 kJ/Ω |
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp | 25 kA |
Impulse discharge current (10/350) µs (N-PE), charge | 50 As |
Impulse discharge current (10/350) µs (N-PE), specific energy | 2500 kJ/Ω |
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp | 100 kA |
Follow current interrupt rating Ifi(L-N) | 25 kA (264 V AC) |
3 kA (350 V AC) | |
Follow current interrupt rating Ifi(N-PE) | 100 A (350 V AC) |
Short-circuit current rating ISCCR | 25 kA (264 V AC) |
3 kA (350 V AC) | |
Voltage protection level Up(L-N) | ≤ 1.5 kV |
Voltage protection level Up(L-PE) | ≤ 2.2 kV |
Voltage protection level Up(N-PE) | ≤ 1.5 kV |
Residual voltage Ures(L-N) | ≤ 1.5 kV (at In) |
≤ 1.2 kV (at 10 kA) | |
≤ 1 kV (at 5 kA) | |
≤ 0.9 kV (at 3 kA) | |
Residual voltage Ures(L-PE) | ≤ 2.2 kV (at In) |
≤ 2 kV (at 10 kA) | |
≤ 1.8 kV (at 5 kA) | |
≤ 1.6 kV (at 3 kA) | |
Residual voltage Ures(N-PE) | ≤ 1.5 kV (at In) |
≤ 1 kV (at 10 kA) | |
≤ 0.9 kV (at 5 kA) | |
≤ 0.8 kV (at 3 kA) | |
TOV behavior at UT(L-N) | 415 V AC (5 s / withstand mode) |
457 V AC (120 min / safe failure mode) | |
TOV behavior at UT(N-PE) | 1200 V AC (200 ms / withstand mode) |
Response time tA(L-N) | ≤ 25 ns |
Response time tA(N-PE) | ≤ 100 ns |
Max. backup fuse with V-type through wiring | 125 A (gG) |
Max. backup fuse with branch wiring | 315 A (gG) |
Switching function | PDT contact |
---|---|
Operating voltage | 12 V AC ... 250 V AC |
125 V DC (200 mA DC) | |
Operating current | 10 mA AC ... 1 A AC |
1 A DC (30 V DC) | |
Connection method | Plug-in/screw connection via COMBICON |
Screw thread | M2 |
Tightening torque | 0.25 Nm |
Stripping length | 7 mm |
Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
Conductor cross section AWG | 28 ... 16 |
Connection method | Screw terminal blocks |
---|---|
Screw thread | M5 |
Tightening torque | 4.5 Nm |
Stripping length | 18 mm |
Conductor cross section flexible | 2.5 mm² ... 25 mm² |
Conductor cross section solid | 2.5 mm² ... 35 mm² |
Conductor cross section AWG | 13 ... 2 |
SPD Type | 4CA |
---|---|
Maximum continuous operating voltage MCOV (L-L) | 528 V AC |
Maximum continuous operating voltage MCOV (L-N) | 264 V AC |
Maximum continuous operating voltage MCOV (L-G) | 528 V AC |
Maximum continuous operating voltage MCOV (N-G) | 264 V AC |
Nom. voltage | 240/415 V AC |
Mode of protection | L-L |
L-N | |
L-G | |
N-G | |
Power distribution system | Wye |
Nominal frequency | 50/60 Hz |
Measured limiting voltage MLV (L-L) | 2470 V |
Measured limiting voltage MLV (L-N) | 1340 V |
Measured limiting voltage MLV (L-G) | 1550 V |
Measured limiting voltage MLV (N-G) | 1080 V |
Nominal discharge current In(L-L) | 20 kA |
Nominal discharge current In(L-N) | 20 kA |
Nominal discharge current In(L-G) | 20 kA |
Nominal discharge current In(N-G) | 20 kA |
China RoHS | Environmentally Friendly Use Period = 50 |
---|---|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX PROTECTION EN.pdf | 27 Mbytes | |
Datasheet 1: 2859767 - FLT-CP-2S-350 | 207 Kbytes | |
Datasheet 2: 2859767 - FLT-CP-2S-350 | 182 Kbytes | |
Complete catalogue 1: 2859767 - FLT-CP-2S-350 | 12 Mbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.