VAL-CP-1S-175 2859479 PHOENIX CONTACT Type 2 surge arrester View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

VAL-CP-1S-175 2859479 PHOENIX CONTACT Type 2 surge arrester

VAL-CP-1S-175

2859479

PHOENIX_CONTACT

Type 2 surge arrester

More details


Trabtech (TT)

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

Go to successor article: VAL-SEC-T2-1S-175-FM 2905348

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2859479
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 41 (C-6-2013)
GTIN4046356045476
Weight per Piece (excluding packing)205.300 g
Custom tariff number85369010
Country of originDE (Germany)

Dimensions

Height98 mm
Width25.3 mm
Depth71.5 mm
Horizontal pitch1.4 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemTN-S
TT
Mode of protectionL-N
L-PE
N-PE
Mounting typeDIN rail: 35 mm
Colorgray/blue
black
Housing materialPBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Number of positions2
Surge protection fault messageOptical, remote indicator contact

Protective circuit

Nominal voltage UN120 V AC (TN-S)
120 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous operating voltage UC(L-N)175 V AC
Maximum continuous operating voltage UC(L-PE)175 V AC
Maximum continuous voltage UC(N-PE)150 V AC
Rated load current IL40 A (Biconnect M4 fork-type cable lug 6​ mm²)
63 A (TWIN ferrule 2 x 10 mm²)
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs (L-N)20 kA
Nominal discharge current In(8/20) µs (N-PE)20 kA
Maximum discharge current Imax(8/20) µs (L-N)40 kA
Maximum discharge current Imax(8/20) µs (N-PE)40 kA
Follow current interrupt rating Ifi(N-PE)100 A (150 V AC)
Short-circuit current rating ISCCR25 kA
Voltage protection level Up(L-N)≤ 0.85 kV
Voltage protection level Up(L-PE)≤ 1.3 kV
Voltage protection level Up(N-PE)≤ 0.95 kV
Residual voltage Ures(L-N)≤ 0.85 kV (at In)
≤ 0.75 kV (at 10 kA)
≤ 0.65 kV (at 5 kA)
≤ 0.63 kV (at 4 kA)
≤ 0.57 kV (at 2 kA)
Residual voltage Ures(N-PE)≤ 0.4 kV (at In)
≤ 0.4 kV (at 10 kA)
≤ 0.4 kV (at 5 kA)
≤ 0.4 kV (at 4 kA)
≤ 0.4 kV (at 2 kA)
TOV behavior at UT(L-N)240 V AC (5 s / withstand mode)
240 V AC (120 min / safe failure mode)
TOV behavior at UT(N-PE)1200 V AC (200 ms / withstand mode)
Response time tA(L-N)≤ 25 ns
Response time tA(N-PE)≤ 100 ns
Max. backup fuse with V-type through wiring40 A (gG / Biconnect M4 fork-type cable lug, 6​ mm²)
63 A (gG / TWIN ferrule 2x 10mm²)
Max. backup fuse with branch wiring315 A (gG)

Indicator/remote signaling

Switching functionPDT contact
Operating voltage5 V AC ... 250 V AC
125 V DC (200 mA DC)
Operating current5 mA AC ... 1 A AC
1 A DC (30 V DC)
Connection methodPluggable screw connection
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section solid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Connection data

Connection methodScrew connection
Screw threadM5
Tightening torque4.5 Nm
Stripping length16 mm
Conductor cross section flexible2.5 mm² ... 16 mm²
Conductor cross section solid2.5 mm² ... 25 mm²
Conductor cross section AWG12 ... 4

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV (L-N)175 V AC
Maximum continuous operating voltage MCOV (L-G)175 V AC
Maximum continuous operating voltage MCOV (N-G)150 V AC
Nom. voltage120 V AC
Mode of protectionL-N
L-G
N-G
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-N)1510 V
Measured limiting voltage MLV (L-G)1630 V
Measured limiting voltage MLV (N-G)560 V
Nominal discharge current In(L-N)20 kA
Nominal discharge current In(L-G)20 kA
Nominal discharge current In(N-G)20 kA

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.