FLT-CP-2C-350 2859770 PHOENIX CONTACT Type 1+2 protective device combination View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

FLT-CP-2C-350 2859770 PHOENIX CONTACT Type 1+2 protective device combination

FLT-CP-2C-350

2859770

PHOENIX_CONTACT

Type 1+2 protective device combination

Pluggable lightning current and surge arrester combination, in acc. with typ 1+2 / Class I+II / B+C arresters. Arresters coordinated following the AEC principle, for 2-phase power supply networks with PE and N (L1, L2, PEN) installed in one cable.

More details


Trabtech (TT)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete.

Go to successor article: FLT-SEC-T1+T2-2C-350/25-FM 2905467

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Technical data

Product properties
Product typeArrester combination
IEC test classificationI + II
T1 + T2
IEC power supply systemTN-C
TypeDIN rail module, two-section, divisible
Number of positions2
Surge protection fault messageOptical, remote indicator contact
Insulation characteristics
Overvoltage categoryIII
Pollution degree2

Electrical properties
Nominal frequency fN50 Hz (60 Hz)
Indicator/remote signaling
Connection nameRemote fault indicator contact
Switching functionChangeover contact
Operating voltage12 V AC ... 250 V AC
125 V DC (200 mA DC)
Operating current10 mA AC ... 1 A AC
1 A DC (30 V DC)

Connection data
Connection methodScrew terminal blocks
Screw threadM5
Tightening torque4.5 Nm
Stripping length18 mm
Conductor cross section flexible2.5 mm² ... 25 mm²
Conductor cross section rigid2.5 mm² ... 35 mm²
Conductor cross section AWG13 ... 2
Remote fault indicator contact
Connection methodPlug-in/screw connection via COMBICON
Screw threadM2
Tightening torque0.25 Nm
Stripping length7 mm
Conductor cross section flexible0.14 mm² ... 1.5 mm²
Conductor cross section rigid0.14 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Dimensions
Dimensional drawingtmcaywsefu.jpg
Width71.2 mm
Height95 mm
Depth71.5 mm
Horizontal pitch4 Div.

Material specifications
Flammability rating according to UL 94V - 0
CTI value of material600
Insulating materialPA 6.6/PBT
Material groupI
Housing materialPBT

Mechanical properties
Mechanical data
Open side panelNo

Protective circuit
Mode of protectionL-PEN
Direction of action2L-N/PE
Nominal voltage UN240/415 V AC (TN-C)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC350 V AC
Rated load current IL125 A (< 55 °C)
Nominal discharge current In(8/20) µs25 kA
Impulse discharge current (10/350) µs, charge12.5 As
Impulse discharge current (10/350) µs, specific energy160 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp25 kA
Follow current interrupt rating Ifi25 kA (264 V AC)
3 kA (350 V AC)
Short-circuit current rating ISCCR25 kA (264 V AC)
3 kA (350 V AC)
Voltage protection level Up≤ 1.5 kV
Residual voltage Ures≤ 1.5 kV (at In)
≤ 1.2 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 1.5 kV
TOV behavior at UT415 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with V-type through wiring125 A (gG)
Max. backup fuse with branch wiring315 A (gG)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl)
Permissible humidity (operation)5 % ... 95 %
Shock (operation)25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (5 - 500 Hz/2.5 h/X, Y, Z)

Approvals
UL specifications
Maximum continuous operating voltage MCOV (L-L)528 V AC
Maximum continuous operating voltage MCOV (L-G)264 V AC
Nominal discharge current In(L-L)20 kA
Nominal discharge current In(L-G)20 kA
Mode of protectionL-L
L-G
Nominal voltage240/415 V AC
Power distribution systemDelta
Nominal frequency50/60 Hz
Measured limiting voltage MLV (L-L)2450 V
Measured limiting voltage MLV (L-G)1340 V
Follow current (N-G)10 kA (264 V AC)
SPD Type4CA
UL indicator/remote signaling
Operating voltage125 V AC
AC operating current1 A AC
UL connection data
Tightening torque40 lbf-in.
Conductor cross section AWG12 ... 2

Standards and regulations
Air clearances and creepage distances
Standards/regulationsDIN VDE 0110-1 / IEC 60664-1 / IEC 61643-1
Standards/specificationsIEC 61643-11
Note2011
Standards/specificationsEN 61643-11
Note2012

Mounting
Mounting typeDIN rail: 35 mm

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.