ANUNCIAR
PSR-MC73-5NO-1DO-24DC-SP 1015526 PHOENIX CONTACT Safety relay for emergency stop, safety doors, light grid u.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

PSR-MC73-5NO-1DO-24DC-SP 1015526 PHOENIX CONTACT Safety relay for emergency stop, safety doors, light grid u..

PSR-MC73-5NO-1DO-24DC-SP

1015526

PHOENIX_CONTACT

Safety relay for emergency stop, safety doors, light grid up to SILCL 3, Cat. 4, PL e, 1- or 2-channel operation, cross-circuit detection, can be retriggered, fall back/on delay 0.2 s to 300 s, 5 enabling current paths, U

Safety relay for emergency stop, safety doors, light curtains up to SIL 3, category 4, PL e, 1 or 2 channel operation, transverse short circuit detection, reactivatable, return/excitation delay 0.2 s to 300 s, 5 trip circuits, US = 24 V DC, plug-in push-in terminal block

More details


Relays > Device for monitoring of safety-related circuits

Safety

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total: $727.96
Unit price: $727.96
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Key Commercial Data

Orderkey1015526
Packing unit1 pc
Catalog pagePage 227 (C-6-2019)
GTIN4055626496566
Weight per Piece (excluding packing)0.000 g
Custom tariff number85371098
Country of originDE (Germany)

Drawings



Block diagram

Block diagram

Circuit diagram

Circuit diagram



Back to top

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area
Back to top

Dimensions

Width22.5 mm
Height117.5 mm
Depth114.5 mm
Back to top

Ambient conditions

Ambient temperature (operation)-35 °C ... 60 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Maximum altitude≤ 2000 m (Above sea level)
Back to top

Power supply

DesignationA1/A2
Rated control circuit supply voltage US24 V DC -20 % / +25 %
Rated control supply current IStyp. 80 mA
Power consumption at UStyp. 1.92 W
Inrush currenttyp. 28 A (Δt = 30 µs at Us)
Filter time10 ms (For the logic. At A1 in the event of voltage dips at Us)
Protective circuitSerial protection against polarity reversal Suppressor diode
Back to top

Digital inputs

Input nameSensor circuit
S12, S22
Description of the inputsafety-related sensor inputs
NPN
Number of inputs2
Input voltage range "0" signal0 V DC ... 5 V DC
Input voltage range "1" signal11 V DC ... 30 V DC
Input current range "0" signal0 mA ... 2 mA
Inrush current< 11 mA (typically with US)
Current consumption< 4.5 mA (typically with US)
Filter timemax. 3 ms (Test pulse width of low test pulses)
min. 21 ms (Test pulse rate for low test pulse)
Max. permissible overall conductor resistance150 Ω
Concurrence input 1/2
Limit frequencymin. 0 Hz
max. 1 Hz
Protective circuit/componentVaristor
Input nameStart circuit
S34
Description of the inputnon-safety-related
NPN
Number of inputs1
Input voltage range "0" signal0 V DC ... 5 V DC
Input voltage range "1" signal11 V DC ... 30 V DC
Input current range "0" signal0 mA ... 2 mA
Inrush current< 8.6 mA (typically with US)
Current consumption< 3.2 mA (typically with US)
Filter timemax. 3 ms (Test pulse width of low test pulses)
min. 21 ms (Test pulse rate for low test pulse)
Max. permissible overall conductor resistance150 Ω
Limit frequencymin. 0 Hz
max. 1 Hz
Protective circuit/componentVaristor
Back to top

Relay outputs: enabling current path

Output nameEnabling current paths
13/14, 23/24/34, 47/48/58
Output description2 N/O contacts each in series, safety-related, floating
Number of outputs3 (undelayed: 13/14, 23/24/34)
2 (delayed: 47/48/58)
Contact type5 enabling current paths
Contact materialAgSnO2
Switching voltagemin. 12 V AC/DC
max. 250 V AC (Observe the load curve)
Limiting continuous current6 A
Inrush currentmin. 3 mA
max. 6 A
Sq. Total current108 A2(observe derating)
Switching capacitymin. 60 mW
Switching frequency0.5 Hz (depending on the set delay time)
Mechanical service life10x 106cycles
Switching capacity according to IEC 60947-5-14 A (24 V (DC13))
5 A (250 V (AC15))
Output fuse6 A gL/gG
4 A gL/gG (for low-demand applications)
Back to top

Alarm outputs

DesignationM1
Output descriptionPNP
non-safety-related
Number of outputs1
Voltageapprox. 23 V DC (US- 1 V)
Currentmax. 100 mA
Maximum inrush current500 mA (Δt = 10 ms at Us)
Protective circuit/componentSuppressor diode
Short-circuit protectionYes
Back to top

Clock outputs

DesignationS11, S21
Output descriptionPNP
non-safety-related
Number of outputs2
Voltagecorresponds to US
Currentmax. 100 mA
Maximum inrush current500 mA (Δt = 10 ms at Us)
Cable lengthmax. 150 m
Protective circuit/componentSuppressor diode
Short-circuit protectionYes
Back to top

Times

Typical pickup time at US500 ms (with Uswhen controlled via A1)
Typical response time at US< 40 ms (automatic start)
< 30 ms (manual, monitored start)
Typical release time at US< 25 ms (when controlled via S12 and S22 (only for undelayed contacts))
< 5 ms (when controlled via A1; applicative deactivation via A1/A2 is not permitted)
Delay time range0.2 s ... 300 s ±5 % (can be set for 47/48/58)
Restart time< 1 s (Boot time)
Recovery time500 ms (following demand of the safety function)
Back to top

General

Relay typeElectromechanical relay with forcibly guided contacts in accordance with IEC/EN 61810-3 (EN 50205)
Nominal operating mode100% operating factor
Net weight155.43 g
Mounting positionvertical or horizontal
Mounting typeDIN rail mounting
Assembly instructionsSee derating curve
Degree of protectionIP20
Min. degree of protection of inst. locationIP54
Housing materialPBT
Housing coloryellow
Status display5 x bi-color LED
Back to top

Connection capacity

Connection methodPush-in spring connection
pluggableYes
Conductor cross section solid0.2 mm² ... 1.5 mm²
Conductor cross section flexible0.2 mm² ... 1.5 mm²
Conductor cross section AWG / kcmil24 ... 16
Conductor cross section flexible, with ferrule without plastic sleeve0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Conductor cross section, flexible, with ferrule, with plastic sleeve0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6)
Stripping length8 mm
Back to top

Safety-related characteristic data

Stop category0
1
DesignationIEC 61508 - High demand
Safety Integrity Level (SIL)3
DesignationIEC 61508 - Low demand
Safety Integrity Level (SIL)3
DesignationEN ISO 13849
Performance level (PL)e (4 A DC13; 5 A AC15; 8760 switching cycles/year)
Category4
DesignationEN 62061
Safety Integrity Level Claim Limit (SIL CL)3
Back to top

Standards and Regulations

DesignationAir clearances and creepage distances between the power circuits
Standards/regulationsDIN EN 50178
Rated insulation voltage250 V AC
Rated surge voltage/insulationBasic insulation 4 kV between all current paths and housing
Safe isolation, reinforced insulation 6 kV between (A1, A2, S11, S12, S21, S22, S34, M1) and enabling current path (13/14) and enabling current path (23/24/34) and enabling current path (47/48/58)
Degree of pollution2
Overvoltage categoryIII
Shock10g (operation), 15g (transport)
Vibration (operation)10 Hz ... 150 Hz, 2g
ConformanceCE-compliant
Back to top

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
Back to top

Classifications

eCl@ss

eCl@ss 8.027371819
eCl@ss 9.027371819
Back to top

ETIM

ETIM 5.0EC001449
ETIM 6.0EC001449
ETIM 7.0EC001449
Back to top

ETIM for 1015526 Relays (EC001449)
Feature Name Feature Value
Model (EF000010) Basic device
Suitable for rail mounting (EF003972) Yes
With detachable clamps (EF003340) Yes
Type of electric connection (EF003961) Spring clamp connection
Suitable for monitoring of position switches (EF007270) Yes
Suitable for monitoring of emergency-stop circuits (EF007268) Yes
Suitable for monitoring of valves (EF007272) No
Suitable for monitoring of optoelectronic protection equipment (EF007269) Yes
Suitable for monitoring of tactile sensors (EF007271) No
Suitable for monitoring of magnetic switches (EF007266) Yes
Suitable for monitoring of proximity switches (EF007267) No
Evaluation inputs (EF008245) Other
With start input (EF003342) No
With muting function (EF004057) No
With feedback circuit (EF003343) Yes
Release-delay (EF001129) 0.05 s
Number of outputs, safety related, undelayed, with contact (EF003344) 0
Number of outputs, safety related, delayed, with contact (EF003345) 0
Number of outputs, safety related, undelayed, semiconductors (EF003346) 0
Number of outputs, safety related, delayed, semiconductors (EF003347) 0
Number of outputs, signalling function, undelayed, with contact (EF003348) 0
Number of outputs, signalling function, delayed, with contact (EF003349) 0
Number of outputs, signalling function, undelayed, semiconductors (EF003350) 0
Number of outputs, signalling function, delayed, semiconductors (EF003351) 0
Stop category according to IEC 60204 (EF007498) Other
With approval for BG BIA (EF004145) No
With approval according to UL (EF001783) No
Width (EF000008) 22.5 mm
Height (EF000040) 117.5 mm
Depth (EF000049) 114.5 mm

Datasheet - PDF

Title: Size: Type:
PDF CATALOGUE AUTOMATION PHOENIX EN.pdf 35 Mbytes

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.