Key Commercial Data

Orderkey2316145
Packing unit1 pc
Catalog pagePage 517 (C-6-2017)
GTIN4046356619974
Weight per Piece (excluding packing)329.100 g
Custom tariff number85389099
Country of originUS (United States)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width36 mm
Height202.5 mm
Depth61.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)95 % (non-condensing)
Degree of protectionIP20 (when D-FB-PS is installed)

General

Mounting positionOn horizontal DIN rail NS 35 in acc. with EN 60715
Net weight329.1 g
ConformanceCE-compliant
Fieldbus FoundationFF-831

Power supply

Conductor cross section flexible max.2.50 mm²
Conductor cross section flexible min.0.20 mm²
Conductor cross section solid max.2.50 mm²
Conductor cross section solid min.0.20 mm²
Conductor cross section AWG max.12
Conductor cross section AWG min.30

Serial interface

Interface 1Discrete wiring
InterfaceHost system
Number of connections4
Connection methodTerminal block
Torque0.4 Nm ... 0.6 Nm
Inductance Li17.6 mH (trunk and host)
Max. output voltage Uo30 V DC (trunk and host)

Digital outputs

Output nameAlarm

Standards and Regulations

Type of testCorrosive resistance in acc. to ANSI-ISA 71.04-1985 - Severity level G3
DesignationStandards/regulations
Standards/regulationsRing wave noise immunidty in acc. with IEC 61000-4-12
DesignationStandards/regulations
Standards/regulationsDry heat in acc. with IEC 61131-2
DesignationStandards/regulations
Standards/regulationsDamp heat in acc. with IEC 61131-2
DesignationStandards/regulations
Standards/regulationsShock and vibration in acc. with EN 61131-2 and EN 50178
IEC 61158-2
NE21
EN 61326
ConformanceCE-compliant
Fieldbus FoundationFF-831
ATEXSira 11ATEX4216X; II 3 G Ex nA nC IIC T4 Gc
IECExIECEx SIR 11.0097X; Ex nA nC IIC T4 Gc
CSA, USA/CanadaClass I, Div. 2, Groups A, B, C, D; Ex nA nC IIC T4
Class I, Zone 2, AEx nA nC IIC T4

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.