ANUNCIAR
ILC 131 ETH/XC 2701034 PHOENIX CONTACT Controller View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

ILC 131 ETH/XC 2701034 PHOENIX CONTACT Controller

ILC 131 ETH/XC

2701034

PHOENIX_CONTACT

Controller

Inline controller for use in severe environmental conditions, with Ethernet interface for coupling to other controls or systems, and possibility of programming according to IEC 61131-3, complete with connector and marking surface.

Inline controller for use under harsh ambient conditions, with Ethernet interface for coupling to other controllers and systems, with programming options according to IEC 61131-3, complete with connector and labeling field.

More details


PLC's > PLC CPU-module

Control Systems (CST)

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Total: $878.45
Unit price: $878.45
This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Technical data

Notes
Utilization restriction
CCCex noteUse in potentially explosive areas is not permitted in China.

Product properties
Product typeController
Product familyInline-Controller
Typemodular
Data management status
Article revision13
Display
Diagnostics displayno

System properties
ProcessorAlteraNios® II 64 MHz
Clock frequency64 MHz
Retentive data storage8 kByte (NVRAM)
IEC 61131 runtime system
Program memory192 kByte
Data storage system192 kByte
Number of control tasks8
INTERBUS-Master
Amount of process datamax. 4096 bit (INTERBUS)
Number of supported devicesmax. 63
Number of local bus devices that can be connectedmax. 63 (observe current consumption)
Number of devices with parameter channelmax. 8
Modbus/TCP-Client
Amount of process datamax. 8192 bit (internal Modbus /TCP client)
Number of Modbus/TCP clientsmax. 4 later than FW 4.42
PROFINET
Device functionPROFINET device
Specification2.2
Device ID007Dhex/ 125dez
Vendor ID00B0hex/ 176dez
Function
Diagnostics displayno
Controller redundancyno
Safety functionno
Functionality
Programming languages supportedInstruction list (IL)
Symbolic flowchart (SFC)
Ladder diagram (LD)
Function block diagram (FBD)
Structured text (ST)
System requirements
Engineering toolPC Worx
PC Worx Express
Configuration toolConfig+ Version 1.01 or later
Diagnostics toolDIAG+
Runtime systemeCLR
Application interfaceOPC

Electrical properties
Transmission mediumCopper
Real-time clock
Realtime clockyes
Description realtime clocknot integrated
Potentials: 24 V supply UILC
Supply voltage24 V DC -15 % / +20 % (in accordance with EN 61131-2)
Supply voltage range19.2 V DC ... 30 V DC
Current draw80 mA (without connected I/O terminal blocks)
Potentials: 7.5 V communications power UL(potential jumper)
Supply voltage7.5 V DC ±5 %
Potentials: 24 V analog supply UANA(potential jumper)
Supply voltage24 V DC -15 % / +20 %
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Potentials: 24 V main supply UM
Supply voltage24 V DC -15 % / +20 % (in accordance with EN 61131-2)
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 8 A DC
6 mA (without sensors)
Potentials: 24 V segment supply US
Supply voltage24 V DC -15 % / +20 % (in accordance with EN 61131-2)
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 8 A DC
10 mA (without actuators)

Input data
Digital:
Input nameDigital inputs
Description of the inputEN 61131-2 type 1 NPN/PNP
Number of inputs8
Cable lengthmax. 30 m
Connection methodInline potential distributor
Connection technology2-, 3-, 4-conductor
Input voltage range-0.5 V ... 30 V
Input voltage range "0" signal-0.5 V ... 5 V
Input voltage range "1" signal15 V ... 30 V
Nominal input current at UINtyp. 7 mA
max. 15 mA
Input filter timetyp. 5 ms (Signal change 01)
typ. 5 ms ()

Output data
Digital:
Output nameDigital outputs
Connection methodSpring-cage connection
Connection technology2-, 3-, 4-conductor
Number of outputs4
Maximum output current per channel500 mA
Maximum output current per module / terminal block2 A
Nominal load, lamp12 W
Nominal load, ohmic12 W
Behavior with inductive overloadOutput can be destroyed

Connection data
Inline connector
Connection methodSpring-cage connection
Conductor cross section, rigid0.08 mm² ... 1.5 mm²
Conductor cross section, flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16

Interfaces
Web serveryes
Ethernet 10Base-T/100Base-TX
Bus systemRJ45
Number of interfaces1
Connection methodRJ45 jack
Transmission speed10/100 Mbps
No. of channels1
INTERBUS local bus (master)
Number of interfaces1
Connection methodInline data jumper
Transmission speed500 kBaud / 2 MBaud (can be switched)
Parameterization/operation/diagnostics
Bus systemRS-232
Number of interfaces1
Connection method6-pos. MINI DIN socket (PS/2)
Transmission speedmax. 115.2 kbps
Transmission physicsCopper
No. of channels1

Dimensions
Width80 mm
Height119.8 mm
Depth71.5 mm

Material specifications
Colorgreen (RAL 6021)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)10 % ... 95 % (according to DIN EN 61131-2)
Shock25g, Criterion 1, according to IEC 60068-2-27
Vibration (operation)5g
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37Sulfur dioxide (SO2) 10 ±0.3 ppm (test duration: 10 days), hydrogen sulfide (H2S) 1 ±0.3 ppm (test duration: 4 days), both at 25°C and with 75% humidity

EMC data
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU
Conformance with EMC directivesImmunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD)EN 61000-4-2/IEC 61000-4-2 Criterion B, ±6 kV contact discharge, ±8 kV air discharge
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electromagnetic fieldsEN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Fast transients (burst)EN 61000-4-4/IEC 61000-4-4 Criterion A, all interfaces ±1 kVCriterion B, all interfaces ±2 kV
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Transient overvoltage (surge)EN 61000-4-5/IEC 61000-4-5 Criterion B, supply lines DC: 0.5 kV/0.5 kV (symmetrical/asymmetrical), fieldbus cable shield 1 kV
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Conducted interferenceEN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
Noise emission test in accordance with EN 61000-6-4/IEC 61000-6-4 EN 55011 Class A

Mounting
Mounting typeDIN rail mounting

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.