Freely programmable temperature transducer with analog output and 3 limit value relays, standard configuration, resistance thermometer with 2, 3 or 4-conductor technology, thermocouples, electrical isolation, wide-range power supply, screw connection, PLd

More details


INTERFACE Signal converters, switching devices, and power supply units - PHOENIX CONTACT

Modular Converter MCR technique. Analog - PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

Quantity Price
1+$435.39
2+$424.65
*This price is per unit and is the net value (not including taxes if applicable).

Related products

More info



Dimensions

Width35 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 65 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude≤ 2000 m
Permissible humidity (operation)typ. 5 % ... 95 % (non-condensing)
Noise immunityEN 61000-6-2 When being exposed to interference, there may be minimal deviations.

Input data

Sensor types (RTD) that can be usedPt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC)B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG
Temperature measuring range-200 °C ... 850 °C
Input signal range0 Ω ... 50 kΩ
Potentiometer resistance range0 Ω ... 50 kΩ
Input signal range-1000 mV ... 1000 mV

Output data

Current output signal4 mA ... 20 mA
Max. current output signal22 mA
Load/output load current output≤ 600 Ω (at 20 mA)
Behavior in the event of a sensor erroraccording to NE 43 or freely configurable
Output nameRelay output
Output description1 SIL/PL
Contact type2 PDT
Contact materialAgSnO2, hard gold-plated
Maximum switching voltage250 V AC (250 V DC)
Maximum inrush current2 A (250 V AC)
2 A (28 V DC)
0.2 A (120 V DC)

Power supply

Supply voltage range24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Power consumption< 2.4 W

Connection data

Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.14
Screw threadM3
Connection methodScrew connection

General

Maximum transmission error0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA)
Maximum temperature coefficient0.01 %/K
Flammability rating according to UL 94V0
Pollution degree2
Overvoltage categoryII
Housing materialPA 66-FR
Coloryellow
DesignationInput/output/power supply
Electrical isolation300 Vrms (Rated insulation voltage (overvoltage category II; pollution degree 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
DesignationInput/output
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
DesignationInput/power supply
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
DesignationInput/switching output
Electrical isolation375 V (Peak value in accordance with EN 60079-11)
ConformanceCE-compliant
ATEXEx II 3 G Ex nA nC ic IIC T4 Gc X
IECExEx nA nC ic IIC T4 Gc X
UL, USA / CanadaUL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Functional Safety (SIL)SIL 2

Datasheet - PDF

Title: Language: Size: Type:
PHOENIX CONTACT-2904901-MACX PL-T-UIREL-UP English 129 Kbytes PHOENIX CONTACT-2904901-MACX PL-T-UIREL-UP

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

Latest Customer Reviews

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.