LM-S-A/C-3S-ETH 2800618 PHOENIX CONTACT Lightning current measuring system View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

LM-S-A/C-3S-ETH 2800618 PHOENIX CONTACT Lightning current measuring system

LM-S-A/C-3S-ETH

2800618

PHOENIX_CONTACT

Lightning current measuring system

Evaluation unit for live monitoring system for the permanent recording and evaluation of lightning discharges. Up to three optical beam sensors can be connected.

Evaluation unit for the instantaneous monitoring system for continuous acquisition and evaluation of lightning strikes. Up to three optical lightning detectors can be connected.

More details


Earthing, lightning and surge protection > Lightning current measuring system

Monitoring

Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

Related products

Best sellers

More info



Key Commercial Data

Orderkey2800618
Packing unit1 pc
Catalog pagePage 191 (C-4-2017)
GTIN4046356615297
Weight per Piece (excluding packing)1,370.000 g
Custom tariff number85437090
Country of originDE (Germany)

Dimensions

Height185 mm
Width77.6 mm
Depth181.5 mm

Ambient conditions

Ambient temperature (operation)-30 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)30 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)30 % ... 95 % (non-condensing)
Altitude≤ 4000 m (amsl (above mean sea level))

General

Housing materialStainless steel 1.4016
Mounting typeDIN rail: 35 mm
TypeDIN rail module, one-piece

Typical characteristics

InterfaceEthernet
Number1
Connection methodRJ45
Transmission speed10/100 Mbps
InterfaceO/E module
Number of ports3
Connection methodRack for plug-in I/O module
Basic functionsEvaluation and communication of sensor data
OperationVia web interface, Modbus, OPC-UA
Maximum storable data records500
Operating voltage24 V DC ±4 V
Operating currentmax. 500 mA
Detectable values (current strength)5 kA ... 400 kA
InterfaceFiber optic interface
Connection methodB-FOC (ST®)
Number of ports3

Remote indication contact

Switching functionN/C contact, 1-pos.
Connection methodM12 D-coded
Maximum operating voltage UmaxDC60 V DC

Standards and Regulations

Standards/specificationsEN 61326-1 2013

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


ETIM for 2800618 Earthing, lightning and surge protection (EC002965)
Feature Name Feature Value
Model (EF000010) Complete
Degree of protection (IP) (EF005474) IP20
Ambient temperature during operating (EF007515) 30 °C
Max. mounting height (EF006338) 4000 m

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.