CB E1 24DC/8A SI-R P 2905804 PHOENIX CONTACT Electronic device circuit breaker, 1-pos., active current limit.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

CB E1 24DC/8A SI-R P 2905804 PHOENIX CONTACT Electronic device circuit breaker, 1-pos., active current limit..

CB E1 24DC/8A SI-R P

2905804

PHOENIX_CONTACT

Electronic device circuit breaker, 1-pos., active current limitation, inverted status output and control input, plug for base element.

More details


Over Current Protection

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey 2905804
Packing unit 1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 257 (C-6-2015)
GTIN4046356998079
Weight per Piece (excluding packing)36.900 g
Custom tariff number85362010
Country of originDE (Germany)

Dimensions

Height45 mm
Width12.3 mm
Depth52 mm
Complete module height90 mm
Complete module width12.3 mm
Complete module depth77.3 mm

Ambient conditions

Ambient temperature (operation)-25 °C ... 50 °C (non-condensing)
Ambient temperature (storage/transport)-40 °C ... 70 °C
Humidity test96 h, 95 % RH, 40 °C
Vibration (operation)3g (In accordance with IEC 60068-2-6, Test Fc)
Degree of protectionIP30 (Actuation area)

General

Flammability rating according to UL 94V0
Mounting typeon base element
Colorgray
Number of positions1
Degree of pollution2
TypeMale

Electrical data

Fuse typeelectronic
Rated surge voltage0.5 kV
Operating voltage24 V DC
18 V DC ... 30 V DC
Nominal current IN8 A
Rated insulation voltage Ui30 V (Load circuit)
Active current limitationtyp. 1.25 x IN
Closed circuit current I0typ. 8 mA (When switched on)
typ. 11 mA (With status output)
Power dissipation1.06 W (Nominal operation)
Temperature derating7.2 A (at 50 °C)
Tripping methodE (electronic)
Required backup fusenot required, integrated failsafe element
Dielectric strengthmax. 30 V DC (Load circuit)
Voltage drop100 mV (at IN)
Shutdown time load circuit100 ms (see time/current characteristic curve)
Undervoltage shutdown load circuit< 14 V (typ. OFF)
> 17 V (typ. ON)
Max. capacitive load load circuit20000 µF
Output voltage status output24 V DC
Output current status outputmax. 0.2 A (Short-circuit-proof)
Input voltage reset input7 V DC ... 30 V DC (Reset with falling edge)
Current consumption reset inputtyp. 2.6 mA (at 24 V DC)
Auxiliary type of contactPositive-switching signal output

Standards and Regulations

Standards/specificationsUL 2367 UL recognized
UL 508 UL/C-UL listed
EMV EN 61000-6-3 Interference emission
EMV EN 61000-6-2 Noise immunity

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.