MNT-1 S/WH 2880862 PHOENIX CONTACT Type 3 surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

MNT-1 S/WH 2880862 PHOENIX CONTACT Type 3 surge protection device

MNT-1 S/WH

2880862

PHOENIX_CONTACT

10

Type 3 surge protection device

More details


Home > PHOENIX CONTACT

* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

Go to successor article: MNT-1 D/WH 2882213

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Key Commercial Data

Orderkey2880862
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 60 (C-6-2013)
GTIN4046356013093
Weight per Piece (excluding packing)68.970 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height79 mm
Width63 mm
Depth75.5 mm

Ambient conditions

Degree of protectionIP20 (child-proof)
Ambient temperature (operation)-25 °C ... 75 °C

General

Housing materialPA
Flammability rating according to UL 94V0
Colorwhite
Standards for cearances and creepage distancesEN 60664-1
IEC 60664-1
IEC 61643-1
EN 61643-11
TypeAttachment plug
Mounting typePlugging into the mains socket
For country-specific use inS, FIN, N
Direction of actionL(N)-PE

Protective circuit

EN typeT3
Nominal voltage UN230 V AC
Arrester rated voltage UC(L-N)275 V AC
Arrester rated voltage UC(L-PE)360 V AC
Arrester rated voltage UC(N-PE)360 V AC
Nominal frequency fN50 Hz
60 Hz
Nominal current IN16 A (30 °C)
Residual current IPE≤ 1 µA
Nominal discharge current In(8/20) µs3 kA
Nominal discharge current In(8/20) µs (L-N)3 kA
Nominal discharge current In(8/20) µs (L-PE)3 kA
Nominal discharge current In(8/20) µs (N-PE)3 kA
Max. discharge current Imax(8/20) µs8 kA (> 100x 1 kA)
Combination wave UOC4 kV
Energy absorption symmetrical140 J (L-N (L))
Enery absorption, asymmetrical220 J (L(N)-PE)
Voltage protection level Up(L-N)≤ 1.2 kV
≤ 1 kV (at 1 kA (8/20 μs))
Voltage protection level Up(L-PE)≤ 1.5 kV
Voltage protection level Up(N-PE)≤ 1.5 kV
Response time tA(L-N)≤ 25 ns (L-N)
Response time tA(L-PE)≤ 100 ns (L, N-PE)
Max. required back-up fuse16 A (gL/C)
Short-circuit withstand capability IPwith max. backup fuse (r.m.s.)3 kA
Surge protection fault messageoptical

Non-heating apparatus connection, power supply

Connection method INGrounding plug
Connection method OUTGrounding socket

Standards and Regulations

Standards/specificationsEN 61643-11/A11 2007
IEC 61643-1 2005
VDE 0620-1 2005
SEK SS 428 08 34 2004
IEC 60884-1

Classifications

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.