N2-4-160-S1-DC 127732 0004356070 EATON ELECTRIC Switch-disconnector 4p 160A 1000VDC View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

N2-4-160-S1-DC 127732 0004356070 EATON ELECTRIC Switch-disconnector 4p 160A 1000VDC

N2-4-160-S1-DC

127732

0004356070

EATON-MOELLER

Switch-disconnector 4p 160A 1000VDC

N2-4-160-S1-DC

More details


Low-voltage industrial components > Switch disconnector

Circuit Breakers NZM

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $549.20
Unit price: $549.20

Quantity Price
1+$549.20
2+$549.21
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



EL-Nummer (Norway)
0004356070
Switch-disconnector 4p 160A 1000VDC
Switch-disconnectors N..DC in the special version for up to 1500 V DC can be used on 1- or 2 poles. The comply with the isolation properties even for earthed IT networks. Accessories, such as bridge kits, connection terminals and door coupling rotary handles enable individual installation in the most varied of distribution systems. Auxiliary switches, voltage releases and remote operators facilitate signaling and automation. Notes: main switch characteristics including positive drive according to IEC/EN 60204 und VDE 0113. Isolating characteristics according to IEC/EN 60947-3 and VDE 0660. Terminal type: a series connection is required for 2 pole switching according to the specified connecting possibilities. See accessories bridge kits. Switch can not be combined with plug-in / withdrawable units and / or connection on rear.

Delivery program

Product range
Switch-disconnectors
Protective function
Disconnectors/main switches
Photovoltaic applications
Product range
DC switch-disconnectors
Application field
Utility buildings
Open areas
Part no.
N...DC
Standard/Approval
IEC
Rated operational voltage
1000
Installation type
Fixed
Construction size
N2
Description
IEC/EN 60947-3
CCC China Compulsory Certificate
Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
Isolating characteristics to IEC/EN 60947-3 and VDE 0660.
N switch-disconnectors can, in addition, be combined with NZM...-XU, NZM...-XA shunt releases and auxiliary contacts as well as with NZM...-XR... remote operator.
For DC switching, all 4 contacts must be connected in series. Refer to the information on jumper kit accessories.
Supplied as standard: Screw connection; box terminal optional.
When working with ungrounded systems (e.g., IT), the installation must ensure that a double ground fault will be impossible.
Switch can not be combined with plug-in/withdrawable units and/or connection on rear.
N4-4-...-S15-DC feeder unit and outgoer from the bottom only.
Connection options
1230DRW-12061230DRW-12071230DRW-13351230DRW-13361230DRW-13341230DRW-1209
Number of poles
4-pole basic device, usable in a 1-pole or 2-pole configuration depending on the type of connection
Standard equipment
Screw connection
Switch positions
I, +, 0
Rated current = rated uninterrupted current [In= Iu]
160 A
Short-circuit protective device max. fuse gR-characteristic
200 A gR
Remotely control / trip
Remote operation with shunt releases / remote operator
Rated operating frequency
DC

Technical data

Switch-disconnectors
Rated operational voltage, max. [Ue]
1000 V DC
Rated uninterrupted current with terminal jumpersat 40°
160
Rated uninterrupted current with terminal jumpersat 65°
160
Rated uninterrupted current with terminal jumpers
Values for rated uninterrupted current at 65 °C include jumpers.
Utilization category
DC-22A
Rated operational current [Ie]DC 22-A [Ie]
160 A
Overvoltage category/pollution degree
III/3
Rated insulation voltage [Ui]
1250 V
Ambient temperatureAmbient temperature, storage
- 40 - + 70 °C
Ambient temperatureOperation
-25 - +70 °C
Rated short-time withstand current
t = 1 s [Icw]
3.6 kA
Rated conditional short-circuit current [kA]
1000 V
15 kA
With back-up fuse
200 A gR
Lifespan, mechanical
Max. operating frequency
120 Ops/h
Lifespan, mechanical [Operations]
20000
Lifespan, mechanical: of which max. 50 % trip by shunt/undervoltage release
Terminal capacity
Standard equipment
Screw connection
Round copper conductorBox terminalSolid
1 x (4 - 16)
2 x (4 - 16) mm2
Round copper conductorBox terminalStranded
1 x (25 - 185)
2 x (25 - 70) mm2
Round copper conductorTunnel terminalSolid
1 x 16 mm2
Round copper conductorTunnel terminalStrandedStranded
1 x (25 - 185) mm2
Round copper conductorBolt terminalsDirect on the switchSolid
1 x (10 - 16)
2 x (4 - 16) mm2
Round copper conductorBolt terminalsDirect on the switchStranded
1 x (25 - 185)
2 x (25 - 70) mm2
Al conductors, Cu cableTunnel terminalSolid
1 x 16 mm2
Al conductors, Cu cableTunnel terminalStrandedStranded
1 x (25 - 185) mm2
Al conductors, Cu cableBolt terminal and rear-side connectionFlat copper strip, with holes [min.]
2 x 16 x 0.8 mm
Al conductors, Cu cableBolt terminal and rear-side connectionFlat copper strip, with holes [max.]
10 x 24 x 0.8 mm
Cu strip (number of segments x width x segment thickness)Box terminal [min.]
2 x 9 x 0,8 mm
Cu strip (number of segments x width x segment thickness)Box terminal [max.]
10 x 16 x 0,8
(2x) 8 x 15,5 x 0,8 mm
Cu strip (number of segments x width x segment thickness)Bolt terminal and rear-side connectionFlat copper strip, with holes [min.]
2 x 16 x 0.8 mm
Cu strip (number of segments x width x segment thickness)Bolt terminal and rear-side connectionFlat copper strip, with holes [max.]
10 x 24 x 0.8 mm
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionScrew connection
M8
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionDirect on the switch [min.]
16 x 5 mm
Copper busbar (width x thickness) [mm]Bolt terminal and rear-side connectionDirect on the switch [max.]
24 x 8 mm

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
160 A
Equipment heat dissipation, current-dependent [Pvid]
27 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+70 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Switch disconnector (EC000216)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Switch disconnector ([email protected] [AKF060013])
Version as main switch
Yes
Version as maintenance-/service switch
Yes
Version as safety switch
No
Version as emergency stop installation
Yes
Version as reversing switch
No
Number of switches
1
Max. rated operation voltage Ue AC
0 V
Rated operating voltage
1000 - 1000 V
Rated permanent current Iu
160 A
Rated permanent current at AC-23, 400 V
0 A
Rated permanent current at AC-21, 400 V
0 A
Rated operation power at AC-3, 400 V
0 kW
Rated short-time withstand current lcw
3.6 kA
Rated operation power at AC-23, 400 V
0 kW
Switching power at 400 V
0 kW
Conditioned rated short-circuit current Iq
0 kA
Number of poles
4
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
Motor drive optional
Yes
Motor drive integrated
No
Voltage release optional
Yes
Device construction
Built-in device fixed built-in technique
Suitable for ground mounting
Yes
Suitable for front mounting 4-hole
No
Suitable for front mounting centre
No
Suitable for distribution board installation
Yes
Suitable for intermediate mounting
Yes
Colour control element
Black
Type of control element
Rocker lever
Interlockable
Yes
Type of electrical connection of main circuit
Screw connection
Degree of protection (IP), front side
IP20
Degree of protection (NEMA)

Dimensions

123X508
① Blow out area, minimum clearance to other parts ≧ 90 mm
② Minimum clearance to adjacent parts ≧ 5 mm
③ Does not apply to DC applications
123X341

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.