DCM-63/1-SK (NVP16) 1314003 EATON ELECTRIC Switch-disconnector, 3 pole + N, 63 A, Without rotary handle and .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

DCM-63/1-SK (NVP16) 1314003 EATON ELECTRIC Switch-disconnector, 3 pole + N, 63 A, Without rotary handle and ..

DCM-63/1-SK (NVP16)

1314003

EATON-MOELLER

Switch-disconnector, 3 pole + N, 63 A, Without rotary handle and drive shaft, surface mounting, Vertical connection

DCM-63/1-SK (NVP16)

DCM-63/1-SK (NVP16) - Switch-disconnector, DCM, 63 A, 3P + N (solid), Stop Function optional, Without rotary handle and drive shaft, Vertical connection

More details


Low-voltage industrial components > Switch disconnector

DUMECO Switch-Disconnectors

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

Total price: $110.71
Unit price: $110.71

Quantity Price
1+$110.71
2+$94.20
3+$87.48
4+$85.79
*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Circuit breaker, DCM, 63 A, 3 P + N (fixed), stop Function optional without handle, rotary axis drive, vertical connection
Circuit breaker Selection: circuit breaker, power Switches, maintenance Switches, Detector type: DCM, Function of stop: optional, without handle and rotary drive axis, 3-pole + N (direct), Degree of protection: IP20, mounting: housing, rated Power of use AC-23A, 50 - 60 Hz 400 V: P = 30 kW, rated uninterrupted Current: Iu = 63 A, connection: vertical connection, in Conformity with standards: IEC/EN 60947, VDE 0660, IEC/EN 60204, Disconnectors, power according to IEC/EN 60947-3

Delivery program

Assortment
circuit breaker
General switches
Maintenance switches
Detector type
DCM
Stop function
optional
without the handle and rotary drive axis
Number of poles
3 P + N (fixed)
Auxiliary contacts
0 no Contact
0 NC Contact
Degree of protection
IP20
Design
in case
000Z428
Circuit symbol
1150SWI-39
Rated power of use AC-23A, 50 - 60 Hz [P]
400 V [P]
30 kW
Rated uninterrupted current [Iu]
63 A
Note on rated uninterrupted current Iu
The rated uninterrupted current Iu is supplied with max. the cross-section.
Connection types
vertical connection

Technical data

General
Compliance with the standards
IEC/EN 60947, VDE 0660, IEC/EN 60204
Disconnectors, power according to IEC/EN 60947-3
Certifications
CE, RoHs, KEMA, EAC, Lloyds
Ambient temperatureOperation [ϑ]
-25 - +55 °C
Ambient temperatureStorage [ϑ]
-30 - +80 °C
Overvoltage category/pollution degree
III/3
Rated voltage impulse withstand [Uimp]
6 kV
Rated insulation voltage [Uthe]
690 V
Mounting position
optional
Relay contacts
Mechanical valuesNumber of poles
3 P + N (fixed)
Mechanical valuesAuxiliary contacts
0 no Contact
Mechanical valuesAuxiliary contacts
0 NC Contact
Electrical parametersRated voltage [Uand]
415 V AC
Electrical parametersRated uninterrupted current [Iu]
63 A
Electrical parametersNote on rated uninterrupted current Iu
The rated uninterrupted current Iu is supplied with max. the cross-section.
Resistance to short circuitfuse
Fifty
Resistance to short circuitShort-circuit current [Iq]
50 kA
Resistance to short circuitthe current switch-off
7 kA
Resistance to short circuitmax. let-through energy
12 kA2s
Resistance to short-time current (Current 1-s) [Icw]
One thousand five hundredeff
Note on the current permissible rated short-time current Icw
The current 1 second
Nominal power of closing under short-circuit [Thecm]
1.4 kAeff
Dissipation per pole, as a function of the current [Pvid]
3.9 W
Power
Interrupting rating cos ϕ to IEC 60947-3400/415 V
504 To
Slicer safe according to EN 61140Losses for the joule effect by contact with Theand
3.9 W
Mechanical durability [Cycles]
Ten thousand
The ac voltageAC-21AThe nominal current of use power switches400 V 415 V [Iand]
63 A
The ac voltageAC-22AThe nominal current of use power switches400 V 415 V [Iand]
63 A
The ac voltageAC-23AThe nominal current of use power switches400 V 415 V [Iand]
63 A
The ac voltageAC-23ARated power of use AC-23A, 50 - 60 Hz [P]400 V 415 V [P]
30 kW
Connection cross-sections
Hard
2,5 - 16 mmTwo
Flexible with ferrule according to DIN 46228flexible
1,5 - 25 mmTwo
Stripping length
14 mm
Tightening torque connection screw
2 Nm
Technical parameters of safety
Notes
B10dValues according to EN ISO 13849-1, table C1

Design checks according to IEC/EN 61439

Technical data for design checks
The nominal current of use for the data related to dissipation [Then]
63 A
Dissipation per pole, as a function of the current [Pvid]
3.9 W
Dissipation of the device, as a function of the current [Pvid]
0 W
Static dissipation, independent from the current [Pvs]
0 W
Power dissipation [Pve]
0 W
Temperature service environment min.
-25 °C
Ambient temperature max service.
+55 °C
Design checks per IEC/EN 61439
10.2 the Suitability of materials and components10.2.2 Resistance to corrosion
The requirements of the product standard are met.
10.2 the Suitability of materials and components10.2.3.1 Resistance of the housing to the heat
The requirements of the product standard are met.
10.2 the Suitability of materials and components10.2.3.2 Resistance of insulating materials to heat levels normal
The requirements of the product standard are met.
10.2 the Suitability of materials and components10.2.3.3 Resistance of insulating materials to heat levels extraordinary
The requirements of the product standard are met.
10.2 the Suitability of materials and components10.2.4 Resistance to UV irradiation
The requirements of the product standard are met.
10.2 the Suitability of materials and components10.2.5 Lifting
Not applicable since the entire electrical panel should be evaluated.
10.2 the Suitability of materials and components10.2.6 Proof
Not applicable since the entire electrical panel should be evaluated.
10.2 the Suitability of materials and components10.2.7 Labeling
The requirements of the product standard are met.
10.3 Degree of protection provided by enclosures
Not applicable since the entire electrical panel should be evaluated.
10.4 Pathways of dispersion-air and surface
The requirements of the product standard are met.
10.5 Protection against electric shock
Not applicable since the entire electrical panel should be evaluated.
10.6 flush Mounting of appliances
Not applicable since the entire electrical panel should be evaluated.
10.7 internal Circuits and connections
Is the responsibility of the manufacturer of the electrical panel.
10.8 Connections for conductors introduced from the outside
Is the responsibility of the manufacturer of the electrical panel.
10.9 insulation properties10.9.2 dielectric strength at network frequency
Is the responsibility of the manufacturer of the electrical panel.
10.9 insulation properties10.9.3 Voltage impulse
Is the responsibility of the manufacturer of the electrical panel.
10.9 insulation properties10.9.4 Testing of enclosures of insulating material
Is the responsibility of the manufacturer of the electrical panel.
10.10 Heating
The calculation of the overheating is the responsibility of the manufacturer of the electrical panel. Eaton provides data on the dissipation of the equipment.
10.11 Resistance to short circuit
Is the responsibility of the manufacturer of the electrical panel. Respect the default values of the equipment.
10.12 EMC
Is the responsibility of the manufacturer of the electrical panel. Respect the default values of the equipment.
10.13 mechanical Function
For the unit requirements are met while respecting the directions of the assembly instructions (THE).

Technical data according to ETIM 7.0

electrical equipment in low-voltage (EG000017) / load break switch (EC000216)
The Technique Of Ar., Elem., Energy, Tech. Comm., Network And Proc. Pipeline / Technology, Low Voltage Switch / Load Switch, Disconnect switch, Control Switch / switch Disconnector compact ([email protected] [AKF060013])
execution as the main switch
yes
running as a switch maintenance/repair
yes
running as a safety switch
no
run as the emergency stop device
no
running as an inverter
no
number of switches
One
max. operating voltage nominal Ue to AC
415 V
operating voltage nominal
415 - 415 V
nominal continuous current Iu
63 A
nominal continuous current at AC-23, 400V
40 To
nominal continuous current for AC-21, 400 V
63 A
operating power rated for AC-3, 400 V
0 kW
resistance to short-time current Icw
1.5 kA
operating power rated for AC-23, 400V
63 kW
power at 400 V
0 kW
short-circuit current the rated conditional Iq
0 kA
number of poles
Three
number of auxiliary contacts, the contacts of the rest
Zero
number of auxiliary contacts, closing contacts
Zero
number of auxiliary contacts, power inverters
Zero
motor drive optional
no
motor drive integrated
no
auxiliary voltage optional
no
the type of construction of the device
recessed luminaire, a technique for fixed installation
suitable for fixing to the ground
yes
suitable for mounting front 4 holes
no
suitable for fixing to front center
no
suitable for mounting on the distributor
yes
suitable for building intermediate
no
the color of the drive element
other
the execution of the drive element
other
lockable
no
type of connection circuit in the main electrical
screw fitting
degree of protection (IP), front side
IP20
type of protection (NEMA)
other

Size

1150DIM-42

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.