BPM-O-600/4.5-IVS 111366 EATON ELECTRIC Surface mounted service distribution board View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

BPM-O-600/4.5-IVS 111366 EATON ELECTRIC Surface mounted service distribution board

BPM-O-600/4.5-IVS

111366

EATON-MOELLER

Surface mounted service distribution board

More details


Home > EATON - MOELLER

* Brand new product in its original packaging covered by the warranties and certifications provided by EATON-MOELLER

* This article may be obsolete. Ask for a quotation and we will check if there are any units available. If not, one of our technicians will look for an alternative solution.

If our price is not the best, please ask us for a quote. Ask for a quotation

More info



Delivery programme
Product range
  Service distribution board IVS
Basic function
  Wall-mounting distribution system
Single unit/Complete unit
  Complete housing
Degree of Protection
  IP54
Description
  Profi Plus basic enclosures
Monoblock enclosure with door and double ward key lock
The enclosure can be turned through 180° for cable entry from below.
Material
  Sheet steel
Surface finish
  Polyester powder coating
Phosphated
RAL 7035, light grey
Colour
  RAL 7035, light grey
Information about equipment supplied
  Including mounting system for the IVS mounting units
including insulating surround and mounted insulated support bracket
including open cable entry at top, prepared for F3A flanges, closed at bottom
Width
 mm600
Height
 mm510
Depth
 mm270
Technical data
General
Standards
  EN 60439-1/3
IEC 62208
Protection class
  1
Degree of Protection
  IP54
Power loss
   
Max. admissible heat dissipation, ambient air temperature +35 °C
 W108
Weight
 kg22.7
Material characteristics
Material
  Sheet steel
Surface treatment
  Painting, phosphated and polyester powder coating
Surface finish
  Polyester powder coating
Phosphated
RAL 7035, light grey
Colour
  RAL 7035, light grey
Material characteristics
   
Type Door
  Doors with covered hinges
Can be removed from 90°
door opening angle
  100° (single mounting)
Door interlock
  Hinge handle with roller lever lock
Cylinder lock
Double-ward lock
Material properties
Mechanical
   
Impact resistance
  IK07
Cable entry
  Open cable entry, prepared for F3A flanges
Electrical
   
Rated operational voltage
UeV690
Rated frequency
fHz50
Rated operational current
IeCSA630
Max. admissible heat dissipation, ambient air temperature +35 °C
 W108
Earthings
  M6 weld stud (base frame)
M5 self-tapping screw (enclosure side plate, top/bottom panel)
M6 weld stud (door)
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
   
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees, calculated as per IEC 60890
   
Individual enclosure for wall mounting
PVCO57
Starting enclosure for wall mounting
PVCO54
Middle enclosure for wall mounting
PVCO51
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees, calculated as per IEC 60890
   
Individual enclosure for wall mounting
PVCO114
Starting enclosure for wall mounting
PVCO108
Middle enclosure for wall mounting
PVCO101
IEC/EN 61439 design verification
   
10.2 Strength of materials and parts
   
10.2.2 Corrosion resistance
  Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
  Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
  Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
  Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
  Not relevant to indoor installations.
10.2.5 Lifting
  Does not apply to enclosures without lifting aids.
10.2.6 Mechanical impact
  IK07
10.2.7 Inscriptions
  Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
  IP54
10.4 Clearances and creepage distances
  Is the panel builder's responsibility.
10.5 Protection against electric shock
  < 0.1 Ω; meets the product standard's requirements.
10.6 Incorporation of switching devices and components
  Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
  Is the panel builder's responsibility.
10.8 Connections for external conductors
  Is the panel builder's responsibility.
10.9 Insulation properties
   
10.9.2 Power-frequency electric strength
  Ui = 440 V AC
10.9.3 Impulse withstand voltage
  4 kV
10.9.4 Testing of enclosures made of insulating material
  Does not apply to metal enclosures.
10.10 Temperature rise
  The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
  Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
  Is the panel builder's responsibility.
10.13 Mechanical function
  Meets the product standard's requirements.

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.